NFPA 13 - Small Room Rule

Summary of the Small Room Rule

The Small Room Rule, as defined in Section 3.3.22 of the NFPA 13 – Sprinkler Systems (2016 edition), applies to compartments meeting the following criteria:

Light hazard occupancy classification.

Unobstructed construction.

Floor area not exceeding 800 ft2 (74 m2).

When these conditions are met, certain sprinkler system installation requirements are modified:

Section 8.6.2.1.2 states that the standard requirements for determining the protection area of coverage for each sprinkler do not apply in a small room. Instead, the protection area for each sprinkler is…