Anti-Vortex Plates
This document from RainHarvest Systems outlines specifications and inspection requirements for anti-vortex plate assemblies in rainwater collection systems used for fire protection.
NFPA 22 (2013) mandates that every suction tank discharge outlet have an anti-vortex plate assembly.
The assembly includes a horizontal steel plate at least twice the outlet diameter on a long radius elbow fitting. This plate is positioned above the tank bottom at a distance equal to half the discharge pipe diameter, with a minimum distance of 6 inches.
Larger, standard-sized plates (48 inches x 48 inches) are…