NFPA 13 Wet Pipe Systems: Alarm Check Valves, Retard Chambers & Waterflow Alarms | MN Journeyman Exam Prep
The plain-Jane system nobody studies. How an alarm check valve and retard chamber actually work (and why a plugged retard drain makes the outside bell ring like a drunk church), gauges above and below the check, the relief valve "175 psi or 10 over, whichever is greater," the more-than-20-sprinklers local alarm, 3/8-inch vs. 3/4-inch alarm piping, the 3/4-inch strainer, alarm bypass test connections, paddle switches (wet only), and the wet inspector's test connection: 1 inch, smooth bore, smallest K-factor or less, anywhere downstream of the flow device, alarm within 5 minutes.