- 0:07SPEAKER_01: What challenges are there to transformer reliability?
- 0:14SPEAKER_00: The mindset of customers.
- 0:17SPEAKER_00: So if we specifically talk about India, a lot of customers they talk about asset reliability and maintaining transformer, improving the life expectancy of transformers.
- 0:29SPEAKER_00: However, the practices what they follow is not aligning with the current practices.
- 0:35SPEAKER_00: So I think they need to improve their condition monitoring.
- 0:38SPEAKER_00: They need to invest in some of the condition monitoring systems in order to have the real-time life check, health check of their transformers, which will help them understand the real condition of the transformer and hence the life expectancies can be improved.
- 1:00SPEAKER_01: What is dissolved gas analysis?
- 1:05SPEAKER_00: Before I break down about DGA, in a very lame language, if I break down what is what does the transformer oil do for the transformer, I can give a very basic analogy of a human body.
- 1:21SPEAKER_00: So our blood, okay, so you blood what we uh have in our human body, you can relate it with the transformer oil, what is there in the transformer.
- 1:31SPEAKER_00: So it helps transformer to maintain and keep the insulation property alive, and which help transformer not to have any arcing or any sort of partial discharge happening.
- 1:44SPEAKER_00: So it is very important to keep the uh the transformer oil intact and keep tracking the the reliability of the transformer oil.
- 1:53SPEAKER_00: In order to do that, there are certain tests we need to perform on the transformer oil.
- 1:58SPEAKER_00: Starting with DGA, what you talk about, it is a dissolved gas analyzing process.
- 2:04SPEAKER_00: Uh a majority of customers uh out there they do DGA testing uh offline.
- 2:09SPEAKER_00: So they they try to take out some oil sample, send it to a third-party lab, or probably the lab what they have in their premises, they do this kind of testing and uh based on the results, uh they try to take further actions.
- 2:24SPEAKER_00: However, what I feel is um there are two major challenges here.
- 2:29SPEAKER_00: Number one, whenever you are taking manual samples, uh there are possibilities of having uh a lot of human errors.
- 2:37SPEAKER_00: Uh probably the the container what they are using for sampling could be contaminated, and hence whatever the results uh will be coming will not be worthy of taking any further actions.
- 2:49SPEAKER_00: And the second part of it, there are a lot of other um testing needs to be done on the uh transformer oil.
- 2:56SPEAKER_00: One will be uh the BDB testing, which is breakdown voltage, to check the actual insulating property of the oil.
- 3:03SPEAKER_00: And the second is moisture content in the oil, which is we call it as a PPM test, Carl Fisher, uh, which is also very important to understand and correlate uh the insulating property of the oil.
- 3:17SPEAKER_01: Is testing every six months enough?
- 3:22SPEAKER_00: Um, not definitely.
- 3:24SPEAKER_00: Um a lot of transformers I have proven data available uh all over the web that sometimes a transformer can fail within less than six months, depending upon the condition.
- 3:37SPEAKER_00: And uh while we are talking about DJ, these all gases, uh certain gases can go up so rapidly that a transformer from a very healthy condition can fail within two to three months as well.
- 3:49SPEAKER_00: So having a sampling rate of six months is not at all feasible for the majority of the customer.
- 3:56SPEAKER_00: Yeah.
- 3:58SPEAKER_01: What challenges do customers face when taking manual oil samples?
- 4:04SPEAKER_00: Uh I think moving from uh manual sampling uh to continuous monitoring of transformer oil helps them get the real check of the health of the transformer.
- 4:15SPEAKER_00: And in order to achieve that, there are two options, which one which you mentioned, a full-stack DGA uh will give you a number of gases, eight gases and moisture.
- 4:24SPEAKER_00: However, the cost of a DJ, which is uh which can cost them a lot, um, to replace that, we have a very simple but a very effective solution, which is called H2 scan, uh, which can give you majorly four parameters, and those four parameters can give you a real-time health condition of your transformer.
- 4:45SPEAKER_00: So those four parameters are starting with hydrogen.
- 4:49SPEAKER_00: So just to give everybody context about different types of gases, hydrogen is one of the gas which starts very early generating within the transformer oil because of any sort of anomaly.
- 5:02SPEAKER_00: If any anomaly is there, the first gas to be introduced is hydrogen.
- 5:06SPEAKER_00: And it that uh introduction of hydrogen will remain constant throughout different phases of failure.
- 5:12SPEAKER_00: So that is number one.
- 5:14SPEAKER_00: The second uh parameter what H2 scan gives you is the transformer oil temperature.
- 5:20SPEAKER_00: Okay, so OTI and WTI, these are indicators uh which gives you temperature indication.
- 5:26SPEAKER_00: However, the location of indicators is slightly away from the actual actual initiation of uh transform uh temperature increase, which gives the transformer uh which gives the temperature delay of two to three hours, sometimes more than that.
- 5:43SPEAKER_00: Having a temperature sensing within this uh H2 scan will give you a real check on the temperature as well.
- 5:50SPEAKER_00: The next two parameters are also very critical.
- 5:53SPEAKER_00: Uh the moisture content.
- 5:55SPEAKER_00: As I told you, um while doing manual sampling, uh we usually check the moisture content in the oil to understand the BDV value of the oil.
- 6:04SPEAKER_00: And then the last one is the pressure.
- 6:06SPEAKER_00: So uh in the process of generating more gases, it increases the pressure inside the transformer tank, and it is very critical to understand and keep a check on the real-time pressure as well.
- 6:18SPEAKER_00: So these are the more these are the four uh parameters what H2 scan can give you.
- 6:25SPEAKER_01: Does H2 scan require regular calibration?
- 6:31SPEAKER_00: So that is one of the um unique features what H2 scan uh provides that uh the technology what they use it is called uh solid state hydrogen sensing.
- 6:43SPEAKER_00: And it is it has auto-calibration feature.
- 6:46SPEAKER_00: It doesn't require any calibration for lifetime.
- 6:49SPEAKER_00: And the the amazing part of about this sensor is it comes with a 10-year sensor warranty.
- 6:54SPEAKER_00: So it shows you the reliability of sensor and can give you um real-time results without um any hassle of uh calibration.
- 7:06SPEAKER_01: What are some real-world examples?
- 7:11SPEAKER_00: Yeah, so uh I have some uh uh documented cases.
- 7:15SPEAKER_00: Uh one of the cases where uh in a nuclear uh power plant facility, there was a transformer um uh uh around uh 1100 KVA.
- 7:27SPEAKER_00: Uh this particular transformer has uh some sort of uh partial discharge issues uh going on.
- 7:33SPEAKER_00: And uh because of this uh Corona discharge within the transformer, uh there was uh introduction of hydrogen gas, and the customer was using a full-stack DGA.
- 7:44SPEAKER_00: So uh they have recorded this uh data while the the amount of hydrogen increase in 48 hours was almost 10x versus the other gases was nearly 7 to 8% increase in a couple of days.