Latest / Civil Engineering Made Simple / Fire Resistance of Structural Steel Framing
Transcript
- 0:00Speaker 1: Okay, let's unpack this. We're putting on our structural engineering
- 0:03Speaker 1: hats today for a critical deep dive into fire protection
- 0:07Speaker 1: for steel structures.
- 0:08Speaker 2: It's a huge topic.
- 0:09Speaker 1: It is, and this isn't just theory. We're talking about
- 0:11Speaker 1: life safety, cost and meeting some really strict standards. Our
- 0:16Speaker 1: main guide today is AISE Design Guide nineteen on fire resistance.
- 0:21Speaker 2: Which is pretty much the bible for this stuff exactly.
- 0:24Speaker 1: So what we're trying to do today is pretty simple. Really.
- 0:27Speaker 1: We want to translate the language of the codes, all
- 0:30Speaker 1: those engineering ratios into practical.
- 0:33Speaker 2: Knowledge, the kind of stuff you actually need to know
- 0:35Speaker 2: when you're stamping a drawing set.
- 0:36Speaker 1: We'll cover the codes, the materials, and the design logic.
- 0:39Speaker 2: It's so important because structural steel has this huge paradox.
- 0:45Speaker 2: On one hand, it's noncombustible, it won't actually burn or
- 0:48Speaker 2: add fuel to a fire, but on the other it's
- 0:51Speaker 2: incredibly vulnerable to the heat itself. It's mechanical properties just
- 0:55Speaker 2: while they fall off a cliff at high temperatures.
- 0:57Speaker 1: We're talking about yield, strength and stiffness.
- 1:00Speaker 2: Exactly, the very things that make it structural. If you
- 1:04Speaker 2: look at the numbers, steel keeps about eighty five percent
- 1:07Speaker 2: of its yield strength up to around eight hundred degrees fahrenheit.
- 1:10Speaker 1: Which sounds high, but a real fire gets much much
- 1:13Speaker 1: hotter than that.
- 1:13Speaker 2: Oh absolutely, Once you get into the range of say
- 1:16Speaker 2: thirteen hundred degrees fahrenheit, that yield strength can drop to
- 1:20Speaker 2: as low as twenty percent of what it should be.
- 1:22Speaker 1: And at that point you're looking at potential collapse.
- 1:24Speaker 2: That's the danger. The steel just loses its stiffness, its capacity,
- 1:29Speaker 2: and the whole goal of fire protection is just to
- 1:31Speaker 2: delay that, to slow down how fast the steel heats up.
- 1:34Speaker 1: So that's the key, that delay. And we have two
- 1:37Speaker 1: main ways to approach fire safety, right, active and passive YEP.
- 1:41Speaker 2: Active as your sprinklers, your alarms, things that actively fight
- 1:44Speaker 2: the fire.
- 1:45Speaker 1: But our focus today is entirely on the passive systems.
- 1:48Speaker 1: We're talking about insulating the steel, basically wrapping it in
- 1:51Speaker 1: something to keep the heat out.
- 1:53Speaker 2: Or using the steel section itself as a big heat sink.
- 1:56Speaker 2: It's all about slowing that temperature rise.
- 1:58Speaker 1: Okay, so where do we even start with a design?
- 2:00Speaker 1: What's the first step?
- 2:02Speaker 2: You have to start with the target, and that target
- 2:04Speaker 2: comes from the model building codes like the IBC the
- 2:07Speaker 2: International Building Code. That's what tells you the minimum you
- 2:11Speaker 2: have to do for public safety.
- 2:12Speaker 1: And there are two ways to meet that code, right,
- 2:14Speaker 1: a prescriptive path and a performance based one.
- 2:17Speaker 2: Correct. The prescriptive path is the simpler one. You use
- 2:20Speaker 2: pre approved, tested assemblies that are listed in a directory
- 2:24Speaker 2: like from US the cookbook approach kind of yeah. The
- 2:27Speaker 2: performance based route is much more complex. It involves a
- 2:30Speaker 2: lot of calculations to prove your specific design will survive
- 2:33Speaker 2: a fire.
- 2:34Speaker 1: So what determines that target that fire resistance rating, the
- 2:38Speaker 1: number of hours.
- 2:39Speaker 2: It's a mix of things. The building's use is a
- 2:41Speaker 2: big one. A hospital or a nursing home, for instance,
- 2:44Speaker 2: needs a higher rating than an office building because evacuation
- 2:47Speaker 2: is harder.
- 2:48Speaker 1: That makes sense.
- 2:48Speaker 2: The new factor in the building's area, it's height how
- 2:51Speaker 2: close it is to other buildings, and this is a
- 2:54Speaker 2: crucial one, whether you have active systems like sprinklers and all.
- 2:58Speaker 1: That leads to the different IBC construction types. We're focused
- 3:01Speaker 1: on Type I in two, which are the non combustible
- 3:04Speaker 1: ones where you'd find steel framing.
- 3:05Speaker 2: Right, And the main difference there is that Type I
- 3:07Speaker 2: allows you to build taller and with larger floor areas.
- 3:11Speaker 1: Which means it demands more fire resistance than Type two exactly.
- 3:15Speaker 2: Let's put some numbers on it. If you're designing a
- 3:17Speaker 2: high rise, you might be in Type IA construction. The
- 3:20Speaker 2: structural frame there typically needs a three hour fire.
- 3:24Speaker 1: Rating three hours.
- 3:25Speaker 2: Now, compare that to a smaller building, maybe Type IAB.
- 3:28Speaker 2: The frame there might be allowed a zero hour rating,
- 3:31Speaker 2: no protection needed at all. In some cases.
- 3:33Speaker 1: Wow, that's a huge difference, and achieving a three hour
- 3:37Speaker 1: rating must be expensive.
- 3:38Speaker 2: It is. It means thick layers of material. But this
- 3:41Speaker 2: is where knowing the code really helps, especially for high rises. Okay,
- 3:45Speaker 2: the code defines a high rise as any building with
- 3:48Speaker 2: an occupied floor more than seventy five feet above where
- 3:50Speaker 2: the fire department can get access. For those buildings, if
- 3:53Speaker 2: you add enhance safety.
- 3:55Speaker 1: Features like sprinklers everywhere, sprinklers.
- 3:58Speaker 2: A secondary water supply, things like that, the code lets
- 4:01Speaker 2: you reduce the minimum construction type.
- 4:03Speaker 1: So you could go from a Type IA to a
- 4:05Speaker 1: Type IB.
- 4:06Speaker 2: You could, and that often means dropping the rating from
- 4:08Speaker 2: three hours down to two.
- 4:09Speaker 1: And saving one hour of protection on an entire skyscraper.
- 4:14Speaker 1: That's got to be a massive cost saving.
- 4:16Speaker 2: It's huge both in materials and labor, and it even
- 4:20Speaker 2: reduces the dead load on the structure. It's a classic
- 4:23Speaker 2: design trade off.
- 4:24Speaker 1: Okay, so we've got our target rating. Let's say it's
- 4:26Speaker 1: two hours. How do we prove a specific column or
- 4:30Speaker 1: beam design meets that.
- 4:32Speaker 2: That's where the standard fire test comes in. The gold
- 4:34Speaker 2: standard is ASTM E one nineteen. You'll also see it
- 4:38Speaker 2: called NFPA two fifty one or UL two sixty three,
- 4:41Speaker 2: but they're all basically identical.
- 4:43Speaker 1: So what happens in this test.
- 4:44Speaker 2: You build a full scale specimen like a piece of
- 4:47Speaker 2: a floor, and you put it in a giant furnace.
- 4:50Speaker 2: Then you crank up the heat following a very specific
- 4:53Speaker 2: time temperature curve.
- 4:54Speaker 1: And you put a load on it.
- 4:55Speaker 2: Right, always, if it's a load bearing element like a beam,
- 4:57Speaker 2: it's tested under its full design load to perform under stress.
- 5:01Speaker 1: I thought. I read that columns are sometimes tested unloaded,
- 5:03Speaker 1: though they are and.
- 5:05Speaker 2: That's a bit of a simplification. Is because loading a
- 5:07Speaker 2: big column to failure at high temperature requires a massive
- 5:12Speaker 2: amount of force, more than most labs can generate. So
- 5:15Speaker 2: testing unloaded is a more conservative practical approach.
- 5:18Speaker 1: So what counts as a failure. It's not just when
- 5:20Speaker 1: it collapses, is it.
- 5:21Speaker 2: No, the criteria are more subtle for unrestrained elements. Yes,
- 5:25Speaker 2: failure is when it can no longer hold the load.
- 5:27Speaker 2: But for most assemblies, temperature is the key. The steel
- 5:30Speaker 2: fails if its average temperature gets above eleven hundred degrees fahrenheit,
- 5:35Speaker 2: or if any single point on the steel hits thirteen
- 5:38Speaker 2: hundred degrees. For those unloaded columns we mentioned, the limits
- 5:41Speaker 2: are a bit tighter, a thousand degrees average or twelve
- 5:44Speaker 2: hundred at any one spot.
- 5:46Speaker 1: That brings up a huge design point. When I look
- 5:48Speaker 1: at UL listings, I always see ratings for restrained versus unrestrained.
- 5:52Speaker 1: What's being restrained?
- 5:53Speaker 2: Talking about thermal expansion? Yeah, In a real building, a
- 5:56Speaker 2: beam is usually bolted or welded to columns, right, It's
- 5:59Speaker 2: part of a continued is framed. When that beam gets hot,
- 6:02Speaker 2: it tries to get longer, but the cold structure around
- 6:05Speaker 2: it holds it in place. It restrains that expansion, and
- 6:09Speaker 2: that restraint actually helps it carry load for longer.
- 6:12Speaker 1: So restrained is how most steel buildings are actually built.
- 6:14Speaker 2: Exactly, And this is so critical because an unrestrained rating
- 6:17Speaker 2: might require fifty to one hundred percent more fire protection material.
- 6:22Speaker 1: Wow.
- 6:22Speaker 2: So if a designer picks the wrong one, they could
- 6:25Speaker 2: be adding millions of dollars to a project for no reason.
- 6:28Speaker 2: Getting that classification right is a huge economic driver.
- 6:32Speaker 1: So the E one nineteen test is our benchmark, but
- 6:35Speaker 1: it's not perfect. It has limitations it does.
- 6:37Speaker 2: The biggest one is the time temperature curve itself just
- 6:40Speaker 2: keeps getting hotter. A real fire has a cooling phase
- 6:43Speaker 2: after the fuel burns off. The test ignores that.
- 6:47Speaker 1: And what about the load?
- 6:48Speaker 2: The test usually uses the full design load, but our
- 6:51Speaker 2: modern codes like ASEE seven let us use load reduction
- 6:54Speaker 2: factors for rare events like a fire. So the test
- 6:57Speaker 2: is often more severe than reality.
- 6:58Speaker 1: And it only measures suctual performance right, not smoke.
- 7:01Speaker 2: Correct, It tells you if the building will stand up.
- 7:05Speaker 2: It says nothing about smoke or toxic gases, which we
- 7:09Speaker 2: know are the primary killers in a fire.
- 7:11Speaker 1: All right, let's talk about the actual materials, the fun part.
- 7:13Speaker 1: How do they work? What's the science?
- 7:16Speaker 2: Well, they generally work in a few ways, phase change,
- 7:19Speaker 2: just being a big thermal mass or through a chemical reaction.
- 7:22Speaker 1: Let's start with gypsum, dry wool gypsum.
- 7:25Speaker 2: Is a powerhouse because it has chemically bound water in it,
- 7:28Speaker 2: calcium sulfate dihydrate. When you heat it up, that water
- 7:31Speaker 2: turns to steam at two hundred and twelve degrees fahrenheit
- 7:34Speaker 2: the boiling point of water, right, and that process of
- 7:37Speaker 2: creating steam sucks up a tremendous amount of heat energy.
- 7:40Speaker 2: It holds the temperature at that two hundred and twelve
- 7:42Speaker 2: degree plateau until all the water is gone, protecting the
- 7:45Speaker 2: steel behind it. We call that the plane of calcination.
- 7:49Speaker 1: Very cool. What about concrete? People use that for encasement
- 7:51Speaker 1: all the time.
- 7:52Speaker 2: Concrete is mostly about thermal mass, but it also has
- 7:54Speaker 2: that moisture content. The key with concrete, though, is the
- 7:57Speaker 2: aggregate you use. Lightweight aggregate like vermiculite or perlite give
- 8:02Speaker 2: you much better insulation than standard normal weight concrete. Even
- 8:06Speaker 2: the type of rock matters. Silicious aggregates from quartz don't
- 8:11Speaker 2: perform as well in a fire as carbonate aggregates like limestone.
- 8:15Speaker 1: That's a deep cut. I like it, Okay, Moving on
- 8:17Speaker 1: to the spray on stuff SFrm.
- 8:20Speaker 2: Spray applied fire resistant materials. It's that thick, almost fluffy
- 8:25Speaker 2: looking stuff you see on beams and parking garages. It's
- 8:27Speaker 2: a cement based or mineral fiber slurry that's just sprayed on.
- 8:31Speaker 1: It's essentially a thermal blanket.
- 8:33Speaker 2: A very effective and usually pretty cheap thermal blanket. Its
- 8:36Speaker 2: performance comes down to its thickness and its density, which
- 8:39Speaker 2: we'll get to.
- 8:39Speaker 1: And my favorite intermescent coatings, the stuff that looks like paint.
- 8:43Speaker 2: They are amazing. It's a thin chemical film. When it
- 8:45Speaker 2: gets hot, a chemical reaction happens and it swells up,
- 8:49Speaker 2: I mean to one hundred times its original thickness.
- 8:51Speaker 1: One hundred times yep.
- 8:53Speaker 2: It forms this thick, black char like foam. That's a
- 8:55Speaker 2: fantastic insulator. It's great when you want to keep the
- 8:58Speaker 2: look of the exposed steel.
- 9:00Speaker 1: Okay, this is great, but how do we decide how
- 9:02Speaker 1: much of this stuff to put on a given beam
- 9:04Speaker 1: or column?
- 9:05Speaker 2: Now we're getting to the heart of the design. It
- 9:07Speaker 2: all comes down to a single ratio, the wover D ratio.
- 9:11Speaker 1: Well, you're divided by D or.
- 9:12Speaker 2: Sometimes you'll see it as a over P which is
- 9:15Speaker 2: area overheated perimeter. It's the weight of the steel section
- 9:18Speaker 2: per foot divided by the perimeter that's actually exposed to
- 9:21Speaker 2: the fire.
- 9:22Speaker 1: Okay, let me see if I get this, A big, heavy,
- 9:25Speaker 1: compact section would have a high wover D ratio.
- 9:29Speaker 2: Exactly.
- 9:29Speaker 1: It's like trying to heat up a thick cast iron
- 9:31Speaker 1: skillet versus a thin sheet of aluminum foil. The still
- 9:36Speaker 1: it has more mass for its surface area, so it
- 9:38Speaker 1: heats up slower.
- 9:39Speaker 2: That is the perfect analogy. The higher the wover D,
- 9:42Speaker 2: the more thermal mass you have, and the slowerest temperature
- 9:45Speaker 2: will rise. That's why in fire protection, when we say
- 9:47Speaker 2: a larger section, we mean one with a larger wover
- 9:51Speaker 2: D ratio, not necessarily one that's physically bigger.
- 9:54Speaker 1: And this ratio lets us apply test results from one
- 9:57Speaker 1: beam to another.
- 9:58Speaker 2: It does, and this is the substitution rule. If a
- 10:02Speaker 2: test was done on a column with a smaller wover
- 10:05Speaker 2: D ratio, you are always allowed to use that same
- 10:08Speaker 2: thickness of protection on a column with a larger wover.
- 10:12Speaker 1: D ratio because the larger one already performs better on
- 10:15Speaker 1: its own.
- 10:15Speaker 2: Exactly. The UL listings are all based on this. They'll
- 10:18Speaker 2: tell you the minimum wover D ratio that was tested
- 10:22Speaker 2: for a given thickness and rating.
- 10:23Speaker 1: That must save an incredible amount of time. And money
- 10:26Speaker 1: on testing.
- 10:27Speaker 2: It's the only way the prescriptive path is workable. Think
- 10:30Speaker 2: about composite elements too, like a concrete filled.
- 10:33Speaker 1: Tube column an HSS column right.
- 10:35Speaker 2: Those performing credibly well in a fire because the concrete
- 10:38Speaker 2: inside acts as a massive heat sink with all its
- 10:41Speaker 2: moisture turning to steam.
- 10:43Speaker 1: But you have to be careful with that steam, don't
- 10:44Speaker 1: you You do?
- 10:45Speaker 2: This is a key detail. All that steam builds up
- 10:48Speaker 2: immense pressure inside the tube. If you don't give it
- 10:51Speaker 2: away to get out, it can literally cause the column
- 10:53Speaker 2: to explode.
- 10:54Speaker 1: So you need vent holes.
- 10:55Speaker 2: You must have vent holes top and bottom to let
- 10:58Speaker 2: that pressure escape safely. Life safety detail.
- 11:01Speaker 1: Let's touch on the engineered approach for a minute. For
- 11:04Speaker 1: something like a composite beam, a steel beam with a
- 11:07Speaker 1: concrete slab on top.
- 11:09Speaker 2: Right. In that case, the slab on top acts as
- 11:11Speaker 2: a huge heat sinc It protects the top flange of
- 11:14Speaker 2: the beam, so you get this nonlinear temperature gradient through
- 11:18Speaker 2: the steel.
- 11:18Speaker 1: The bottom flange gets way hotter than the.
- 11:20Speaker 2: Top, much hotter. A good rule of thumb is to
- 11:23Speaker 2: assume the top flange temperature is about twenty five percent
- 11:26Speaker 2: lower than the bottom flange.
- 11:28Speaker 1: And the system can even redistribute the load as the
- 11:31Speaker 1: beam heats up.
- 11:32Speaker 2: It's a really clever mechanism. As the bottom slange gets
- 11:35Speaker 2: hot and soft, the beam loses its positive moment capacity
- 11:39Speaker 2: at midspan, but because it's part of a continuous frame,
- 11:42Speaker 2: the load can redistribute into negative bending over the supports.
- 11:46Speaker 2: Using the reinforcing steel in the slab, the system finds
- 11:49Speaker 2: a new way to carry the load.
- 11:50Speaker 1: So, assuming the design is solid, the last piece of
- 11:53Speaker 1: the puzzle is making sure it's installed correctly. Quality control, and.
- 11:56Speaker 2: This is especially critical for the spray applied materials, the SFI.
- 12:00Speaker 2: If it's not put on right, your fire rating is meaningless.
- 12:04Speaker 1: So the IBC requires field testing.
- 12:06Speaker 2: Three main field tests, all referencing ASTM standards. First is thickness.
- 12:11Speaker 1: You just measure it with.
- 12:12Speaker 2: A little ping gag yes, and the frequency is spelled out.
- 12:15Speaker 2: You need at least four measurements for every one thousand
- 12:17Speaker 2: square feet on floors, and you have to test at
- 12:20Speaker 2: least twenty five percent of the individual beams and columns
- 12:23Speaker 2: on every floor.
- 12:24Speaker 1: Twenty five percent. That's a lot. What's next.
- 12:27Speaker 2: Density. The sfrm's performance is directly tied to its density.
- 12:32Speaker 2: If it's too light and fluffy. It won't provide the
- 12:34Speaker 2: insulation it's supposed to.
- 12:36Speaker 1: So how do you test that.
- 12:38Speaker 2: You have to cut out a small, known volume sample,
- 12:40Speaker 2: weigh it and calculate the density. You do that for
- 12:43Speaker 2: each floor or for every ten thousand square feet.
- 12:45Speaker 1: Okay, thickness and density. What's the third one?
- 12:47Speaker 2: Cohesion and adhesion. This is maybe the most important. It
- 12:51Speaker 2: measures how well the stuff is actually stuck to the steel.
- 12:53Speaker 1: Because if it falls off in a fire, it's useless.
- 12:56Speaker 2: The test uses a little cap that you glue the
- 12:58Speaker 2: material and then you pull it off with the device
- 13:00Speaker 2: that measures the force. The minimum bond strengthen out is
- 13:03Speaker 2: one hundred and fifty pounds per.
- 13:04Speaker 1: Square foot, and that ensures it stays put even with
- 13:08Speaker 1: all the vibration and thermal stress during a fire.
- 13:11Speaker 2: It has to stay put. That's the whole point.
- 13:13Speaker 1: So if we boil this all down, what's the big takeaway?
- 13:16Speaker 2: At the end of the day. Passive fire protection is
- 13:18Speaker 2: a calculated delay. That's all it is. It's an insurance
- 13:21Speaker 2: policy you hope you never need. It's buying time, time
- 13:25Speaker 2: for people to get out and time for the sprinklers
- 13:27Speaker 2: to do their job. All before the structure reaches that
- 13:30Speaker 2: critical failure temperature.
- 13:32Speaker 1: And for any of you designing these systems, the key
- 13:34Speaker 1: is to look past the tables and really understand the
- 13:36Speaker 1: engineering behind them. Know your thermal restraint and know your
- 13:40Speaker 1: wover D ratio.
- 13:41Speaker 2: And always always check your design against a listed assembly
- 13:45Speaker 2: in the UL directory.
- 13:47Speaker 1: All right, time for our deep dive review exercise. Something
- 13:50Speaker 1: for you to chew on.
- 13:51Speaker 2: Let's hear it.
- 13:52Speaker 1: You're asked to select fire protection for two columns. They're
- 13:55Speaker 1: the same shape. Column A has a wover D ratio
- 13:58Speaker 1: of one point two, d B has a WOD of
- 14:01Speaker 1: zero point eight. Now in ASTM E one nineteen test
- 14:05Speaker 1: assembly gives you a required thickness of protection for column B,
- 14:09Speaker 1: which was the minimum size tested. The question is what
- 14:13Speaker 1: is the accepted practice for applying that same thickness to
- 14:16Speaker 1: column A and why is the substitution allowed? Think about
- 14:19Speaker 1: the principles of thermal mass. We've done the deep dive.
- 14:22Speaker 1: Now you're well informed.