Latest / NTC's Temporal 3 / Episode 47 | Fire Alarms & Sprinklers: What Every Tech Should Know | Temporal 3 Podcast
Transcript
- 0:03SPEAKER_02: Hello, everyone, and welcome again to the Temporal 3 Podcast where we talk all about fire alarm.
- 0:09SPEAKER_02: Check that.
- 0:10SPEAKER_02: We're going to talk about fire alarm and sprinkler because we do have a special guest today with us, Mr.
- 0:15SPEAKER_02: Wyatt Winning.
- 0:16SPEAKER_02: Hello, Wyatt.
- 0:16SPEAKER_02: How are you?
- 0:17SPEAKER_02: I'm pretty good, Neil.
- 0:18SPEAKER_02: Good, good.
- 0:19SPEAKER_02: We also have my usual, one of my usual co-hosts, Mr.
- 0:22SPEAKER_02: Chris Godwin.
- 0:23SPEAKER_02: Hello, Chris.
- 0:24SPEAKER_02: Hey, everyone.
- 0:26SPEAKER_02: So, first of all, Wyatt, why don't you tell our listeners a little bit about you, what your experience is and what you do?
- 0:32SPEAKER_00: Well, I'm working in Rapid City, South Dakota.
- 0:35SPEAKER_00: I have a master's degree in mechanical engineering from South Dakota School of Mines.
- 0:39SPEAKER_00: I spend my days doing fire sprinkler layout.
- 0:42SPEAKER_00: I'll do anything from fire sprinklers, standpipe systems, fire pumps, some water tanks, underground, uh really anything that is encompassed in water-based layout is my daily work.
- 0:56SPEAKER_02: Awesome.
- 0:57SPEAKER_02: Awesome.
- 0:58SPEAKER_02: Great.
- 0:58SPEAKER_02: And I know you are NISET certified, correct?
- 1:01SPEAKER_00: Correct.
- 1:02SPEAKER_00: I have a NISET uh level two in water-based systems layout.
- 1:06SPEAKER_02: And hopefully on your way to three and four eventually.
- 1:09SPEAKER_00: Hopefully.
- 1:13SPEAKER_02: How important is NISET certification on in the work that you do?
- 1:17SPEAKER_02: Is that something that you uh got into it said, you know, I need to have this?
- 1:21SPEAKER_00: Yes.
- 1:21SPEAKER_00: Uh with the work that I'm doing, it's not just in South Dakota.
- 1:26SPEAKER_00: I'm doing work nationwide.
- 1:27SPEAKER_00: I've done everything from California all the way out to Virginia.
- 1:32SPEAKER_00: So with as many states as require NISAT certification, it's necessary to actually do this work.
- 1:39SPEAKER_02: Well, one thing our listeners, I always encourage our listeners to do, and again, we are fire alarm focused, but we uh also recognize and talk about some of the other certifications that NISAT offers is first of all, as I mentioned said to you just a moment ago about going for the maximum certification as your experience permits, go as far as you can because higher levels are always better.
- 2:00SPEAKER_02: I call it the NISET pyramid.
- 2:02SPEAKER_02: The closer you get to the top, there are less people that hold that certification, which makes it more valuable.
- 2:06SPEAKER_02: But also I say if you have experience in other areas, seek those other areas.
- 2:12SPEAKER_02: And there are a lot of related certifications as the water-based layout, water-based INT, and special hazards that a lot of people that deal in fire alarm, whether from the design, installation, or INT perspective, may have experience in those areas as well.
- 2:29SPEAKER_02: And uh, Chris, when they're when somebody's working on that or considering that, what should they do about their experience?
- 2:34SPEAKER_01: When it comes to experience, NYSAD is uh they look at, you told us you have experience, and and uh that experience plays throughout everything.
- 2:45SPEAKER_01: So when you start looking at doing multiple different different types of certifications, they don't like that as much.
- 2:53SPEAKER_01: And they make it a lot harder, is how I kind of interpret that, because you've got to watch out how you document everything.
- 3:00SPEAKER_01: For example, my certifications are all in fire alarm.
- 3:04SPEAKER_01: I have a background in inspection testing of water-based systems.
- 3:07SPEAKER_01: And if I were to go take that test, pass that test, and go to send in everything for documentation, well, most of your experience says you were fire alarm.
- 3:18SPEAKER_01: It says nothing here that you did water-based inspection and testing.
- 3:22SPEAKER_01: It says you were 100% fire alarm.
- 3:24SPEAKER_01: So are you lying now or are you lying then?
- 3:27SPEAKER_01: And what is, and then it comes down to you're starting fresh.
- 3:31SPEAKER_01: You're gonna have to, you know, provide two fresh years of just water-based inspection testing that can't be part of your fire alarm documentation.
- 3:41SPEAKER_01: So when we are looking at documenting, it is one of the trickiest things.
- 3:47SPEAKER_01: It is a very difficult thing because, yeah, you might not know like five years down the road, you're gonna need water-based inspection testing as well.
- 3:56SPEAKER_01: And you put down your 100% fire alarm.
- 3:59SPEAKER_01: So it is a very, it is a lot of hoops to jump through just for the documentation process.
- 4:06SPEAKER_02: Absolutely.
- 4:07SPEAKER_02: We don't want to uh, I never encourage people to uh falsify their records with dice.
- 4:13SPEAKER_02: I always say be as truthful as possible.
- 4:14SPEAKER_02: But as you said, you know, the bulk of the work you did was in fire alarm.
- 4:18SPEAKER_02: You had some uh water-based INT experience, but you were going for the fire alarm certification.
- 4:22SPEAKER_02: You wanted those years, those months, those years to be able to get the certification.
- 4:26SPEAKER_02: So I think a lot of people, if they decide, well, I do have the water-based experience or the special hazards experience, I want to go for that certification now.
- 4:37SPEAKER_02: And it's important to remember that you can't change the past with NISAT, that what you sent to them originally was everything that they expected.
- 4:46SPEAKER_02: So you could start from the start fresh, as you said, Chris, exactly.
- 4:50SPEAKER_02: I plan on getting water-based certified.
- 4:53SPEAKER_02: So from this point forward, uh, you could say you're 100%, but unless you're 100%, I wouldn't do that.
- 4:59SPEAKER_02: It may take a little bit longer to get there, because remember, NISA bases it on percentages of work.
- 5:05SPEAKER_02: So you you know, probably don't want to say you're abandoning fire alarm completely, but now you may want to say, okay, from this point forward, 50% of my work is fire alarm, 50% is water-based IET, water-based layout, special hazards, whatever the case may be.
- 5:18SPEAKER_02: Uh, it'll get you there.
- 5:19SPEAKER_02: There may be a longer path, absolutely.
- 5:22SPEAKER_02: But as with many things in life, it's the hard things in life that are worth doing.
- 5:26SPEAKER_02: And that's where you're going to get the benefit.
- 5:28SPEAKER_02: And as I like to say, the more acronyms you have after the end of the name, you're better off you are.
- 5:34SPEAKER_02: Yeah, absolutely.
- 5:36unknown: Absolutely.
- 5:37SPEAKER_02: So uh next thing I'd like to talk about is IBCs.
- 5:40SPEAKER_02: Let's talk about code.
- 5:42SPEAKER_02: And since we have Wyatt with us, I wanted to talk a little bit about uh a couple sections of the IBC that are interrelated, section 903 and 907.
- 5:53SPEAKER_02: Wyatt, how much do you deal in section 903?
- 5:57SPEAKER_00: Unless it's an engineering job, it's we're usually restricted to NFPA 13.
- 6:01SPEAKER_00: But the moment we get into engineering, then we have to start paying attention to IBC and more often than not, IFC.
- 6:09SPEAKER_00: Uh, of the two, IFC governs a lot more of the sprinkler stuff that we're dealing with on a day-to-day basis in terms of layout, but the IBC is where we get our most basic requirements for where and when we will need these systems installed.
- 6:24SPEAKER_02: And you were saying there's some other uh considerations that we on the fire alarm don't have to deal with.
- 6:28SPEAKER_02: For example, uh, what is that organization again?
- 6:32SPEAKER_02: Uh FM?
- 6:33SPEAKER_00: Yep.
- 6:34SPEAKER_00: FM Global.
- 6:35SPEAKER_02: FM Global, yeah.
- 6:36SPEAKER_02: Yeah.
- 6:37SPEAKER_02: And uh I have a small degree of familiarity.
- 6:40SPEAKER_02: I am water-based layoff certified.
- 6:41SPEAKER_02: I do have some familiar with the FM Global requirements, and I know that it does make things a little bit more complicated for the Sprint of people for sure.
- 6:48SPEAKER_02: So you fire alarm people, be grateful we only have to worry about 72.
- 6:51SPEAKER_02: We don't have to worry about all these other fun things that Wyatt has to deal with.
- 6:55SPEAKER_02: But um, one of the things I noticed about in my experience primarily is with IBC, and I noticed like in 903, a lot of the focus of on 903 is fire area.
- 7:08SPEAKER_02: And one thing I like to remind our listeners about the IBC is that any word that is italicized in the IBC is in the chapter three definitions.
- 7:17SPEAKER_02: So you'll see by two, chapter two, Brian.
- 7:20SPEAKER_02: Chapter two, I'm sorry.
- 7:21SPEAKER_02: Thank you, Chris.
- 7:22SPEAKER_02: Chapter two.
- 7:23SPEAKER_01: We we are so back and forth with those with those books too.
- 7:26SPEAKER_01: NFPA is a chapter three, IBC, they were like, no, we don't, we're gonna do it differently.
- 7:31SPEAKER_01: We're gonna be different.
- 7:32SPEAKER_01: Of course.
- 7:33SPEAKER_02: Absolutely.
- 7:34SPEAKER_02: And uh yeah, it's so the fire area is based on the floor area enclosed by walls, and a lot of the sprinkler requirements are based on fire area or on sort of footage requirements.
- 7:45SPEAKER_02: Whereas with 907, our focus more is about occupant load and story.
- 7:49SPEAKER_02: So the sprinkler people uh tend to focus on a different aspect of the building than the fire alarm people do, which is kind of interesting.
- 7:57SPEAKER_02: And one thing we often encounter with sprinkler people is that, well, the IBC section 903 says a sprinkler system is required in this building, so I need to design my fire alarm based on a sprinkler system being in a building.
- 8:10SPEAKER_02: Is that always the case, Wyatt?
- 8:12SPEAKER_00: I don't think it would be.
- 8:13SPEAKER_00: Any given point, code is the floor.
- 8:16SPEAKER_00: So even if there's a situation where you don't necessarily explicitly have to put it in, it's probably gonna be a good idea to put it in, especially with fire alarms, as those are there to warn occupants of the building that, hey, you need to get out now.
- 8:32SPEAKER_00: So even if there isn't a sprinkler, you can still evacuate the building and hopefully avoid something really bad from happening.
- 8:39SPEAKER_02: Better to get better to get notified by the horns and strobes and notified when you get wet or burnt.
- 8:45SPEAKER_01: I'll even I'll even take it on the other side of that same coin.
- 8:48SPEAKER_01: Most of the time, if there's a sprinkler system, most buildings are still going to have just about everything and above what it needs per what the IBC would look at from both sides of that of that um section, 903 and 907.
- 9:04SPEAKER_01: And that's what I've encountered a lot more out in the field is less likely are you going to see what you know with the IBC, if you've got a sprinkler system, you don't need to have pool stations throughout.
- 9:15SPEAKER_01: And a lot of times you don't need to have uh smoke detectors throughout.
- 9:20SPEAKER_01: And I have seen it where it's like, yeah, it's a fully sprinklered building.
- 9:24SPEAKER_01: Pool stations are everywhere.
- 9:25SPEAKER_01: Not only are they using smoke detection, but in certain areas they're using more, and it's like IBC, as you said, Wyatt, it's the floor.
- 9:34SPEAKER_01: Your codes are the floor, it's a starting point.
- 9:37SPEAKER_01: And a lot of times from a real-world perspective, your AHA goes above and beyond, or even the building owner wants to be above and beyond.
- 9:46SPEAKER_02: Absolutely.
- 9:48SPEAKER_02: And Wyatt brings up an excellent point about the code being the floor.
- 9:51SPEAKER_02: And is it okay for the AHA to go above the minimum?
- 9:54SPEAKER_02: Absolutely it is.
- 9:55SPEAKER_02: And Chris, you mentioned pull stations throughout.
- 9:57SPEAKER_02: And I always want to talk about that with one glaring exception.
- 10:01SPEAKER_02: Pull stations throughout can be eliminated in many buildings where they have a sprinkler system that activates the fire alarm, but there is a glaring exception for that where they don't require it, and that's R2, apartment buildings.
- 10:11SPEAKER_02: Unless it's used for fire.
- 10:12SPEAKER_01: Most frustrating group.
- 10:13SPEAKER_01: Most frustrating group.
- 10:16SPEAKER_01: When I get into it, I I'm it's just yes, you need it.
- 10:20SPEAKER_01: Oh, wait, no, you don't.
- 10:21SPEAKER_01: Wait, maybe you do.
- 10:23SPEAKER_01: No, yeah.
- 10:24SPEAKER_01: Make up your mind.
- 10:25SPEAKER_02: Yeah.
- 10:26SPEAKER_02: It's in a different part of the code, of course, can't be right in there in 907.2.whatever for uh R2.
- 10:32SPEAKER_02: And of course, too, thank thanks to the IBC, we do get to work with the sprinkler people because um if a building has a sprinkler system, the IBC requires it to be monitored.
- 10:42SPEAKER_02: And so now we're putting in at minimum a dedicated functioning fire alarm system.
- 10:46SPEAKER_02: If there's a building fire alarm, we're going to connect to it, but at a minimum, we're going to monitor it.
- 10:50SPEAKER_02: So there's a there's always an opportunity for us on the fire alarm side to be able to partner with uh the sprinkler people to be able to make that connection.
- 10:58SPEAKER_02: Finally, uh from the field, since we have Wyatt with us today, I'd like to talk about Wyatt from your perspective.
- 11:04SPEAKER_02: What do you, as a sprinkler person, wish that fire alarm people knew about sprinkler systems?
- 11:10SPEAKER_00: Well, the first two things come to mind right away is one, don't attach wire to the sprinkler pipe, whether that be for hanging purposes or grounding.
- 11:21SPEAKER_00: The only time that sprinkler pipe ends up getting grounded is when there's protection from lightning that's actually required and built into the building.
- 11:30SPEAKER_00: Otherwise, it is its own dedicated system.
- 11:32SPEAKER_00: Nothing else should attach to it, whether it be electrically or mechanically.
- 11:37SPEAKER_00: It doesn't matter if it's ductwork, other plumbing, electrical, don't hang from the sprinkler pipe.
- 11:43SPEAKER_00: Bad idea.
- 11:44SPEAKER_00: It is the hangers are not sized to carry that additional load.
- 11:48SPEAKER_00: So it could result in pipe getting uh damaged.
- 11:51SPEAKER_00: There could be leaks that result from the extra load at joints where couplings come together.
- 11:56SPEAKER_00: All sorts of bad things can happen as a result of that.
- 12:01SPEAKER_00: Uh the second instance would be with specialized systems such as our dry systems.
- 12:07SPEAKER_00: There's a few things that can happen with those dry systems.
- 12:11SPEAKER_00: Uh, first and foremost, they have different devices compared to a wet system.
- 12:16SPEAKER_00: The wet systems oftentimes have a paddle type flow switch in them.
- 12:20SPEAKER_00: So as water flows by, it's going to hit that paddle and trip the uh connections in there and kick off an alarm state.
- 12:28SPEAKER_00: Whereas dry systems, they don't use those same paddle-type flow switches.
- 12:32SPEAKER_00: They run a pressure switch that's monitoring the air pressure.
- 12:36SPEAKER_00: And what they're not looking for isn't an increase in pressure, it's a drop in that air pressure.
- 12:42SPEAKER_00: Because when that sprinkler head, that glass bulb pops, it's gonna release all that air through the head and it's gonna exit the pipe faster than the air compressor can refill it.
- 12:51SPEAKER_00: So it's important to keep in mind that they are different devices, they're gonna function differently.
- 12:56SPEAKER_00: With that, there's also different inspection requirements that come with it.
- 13:00SPEAKER_00: With dry systems, you have to flow water through the pipe to prove your delivery time whenever one gets installed.
- 13:07SPEAKER_00: However, it's possible that at the end of that test, you close all your valves and you forget that you need to drain that pipe back all the way to the valve and get rid of any trapped water in that pipe.
- 13:20SPEAKER_00: Uh, whenever a dry pipe system is installed, it's usually installed because freeze protection is required.
- 13:25SPEAKER_00: And if you don't drain out any of that, if you forget even one trap section of that pipe, there's a chance that it can freeze.
- 13:33SPEAKER_00: And then now you have a burst pipe, it's not going to fill with air.
- 13:36SPEAKER_00: The valve's gonna trip because it thinks that there's a sprinkler activated, and it just results in an even bigger mess the moment you try and put that system back into service.
- 13:44SPEAKER_02: Yep, yep, absolutely.
- 13:47SPEAKER_02: So, Chris, you are you are of the field uh recently.
- 13:50SPEAKER_02: Have you seen fire alarm people attach fire alarm cable to sprinkler pipe?
- 13:55SPEAKER_01: Um I have seen the outcome.
- 13:58SPEAKER_01: See I I have seen the effects of electrolysis through that.
- 14:05SPEAKER_01: Um, and um I personally, the company that I worked for and everything, we it was kind of really just ingrained into us.
- 14:18SPEAKER_01: You cannot do this, do not do this.
- 14:21SPEAKER_01: Um, we were out doing a job connecting to the water flow switch, just a switch.
- 14:28SPEAKER_01: And all I'm doing at that point is I'm just connecting.
- 14:34SPEAKER_01: Not getting the wires set for where they're gonna eventually you know stay.
- 14:39SPEAKER_01: And uh my boss comes over and goes, hey, you know, you need to move this away.
- 14:42SPEAKER_01: You need to get like immediately.
- 14:44SPEAKER_01: But yeah, that is a it that is the the the whole thing with that is water and electricity want to be the best of friends, but they can't be, you know, and uh if you have if you have your wire on the piping, you're gonna have that electricity trying to get to the water, trying to get through the pipe.
- 15:07SPEAKER_01: And I I've seen pipes that have had the holes because of that.
- 15:13SPEAKER_01: And and unfortunately enough, it was something that was caught early when they kept getting water flow alarms.
- 15:19SPEAKER_01: Why do we keep getting water flow alarms?
- 15:21SPEAKER_01: Because you got water flowing from the hole in the pipe.
- 15:26SPEAKER_01: So I I've seen it.
- 15:28SPEAKER_01: Um, it's not something that you see a lot, but I have seen it out in the field, and so it is one of those things as soon as it gets brought up, you're like, they just want to be friends.
- 15:39SPEAKER_01: They just want to be friends.
- 15:40SPEAKER_01: They can't.
- 15:41SPEAKER_01: They can't.
- 15:42SPEAKER_01: So yeah.
- 15:44SPEAKER_01: I I've seen I've seen a few.
- 15:46SPEAKER_02: Yeah, you you've uh you've uh seen you know some things because you've seen some things.
- 15:51SPEAKER_02: Yeah.
- 15:51SPEAKER_02: And the uh the dry system thing that too that uh Wyatt brings up, I think, is particularly interesting because a lot of times with fire alarm people, you know, we're there inspecting the system.
- 16:00SPEAKER_02: Part of our job is to inspect those connections, you know, and closing and opening a control valve is one thing.
- 16:06SPEAKER_02: Uh testing a water flow.
- 16:09SPEAKER_02: I've heard horror stories of people who have tested wet systems.
- 16:12SPEAKER_02: And one of our instructors actually, we won't mention any names, Ed, uh filled his customer's car with sprinkler water uh when he was flow testing his system.
- 16:21SPEAKER_02: Wasn't his fault.
- 16:22SPEAKER_02: He put up all the signs and everything, but it was still pretty funny that he asked that he did that.
- 16:27SPEAKER_01: It wasn't Ed's fault.
- 16:28SPEAKER_02: It wasn't Ed's fault, but it's still pretty funny.
- 16:31SPEAKER_02: We had another instructor that worked for us that uh under the instructions of his boss, fortunately, uh was testing a dry pipe and did not let the air pressure out of the dry uh pipe valve slowly enough, and the valve went wham open and it bent the paddle.
- 16:47SPEAKER_02: And uh, long story short, two weeks of fire watch and$5,000 later, they've had to put a new valve in.
- 16:53SPEAKER_02: So uh, yeah, there's besides the thing that Wyatt talked about, the freezing water in pipes.
- 17:00SPEAKER_02: If you live anywhere north of Orlando, Florida, you know about freezing water in pipes.
- 17:06SPEAKER_02: And uh, you know, that's the electrolysis thing that Chris that you talked about, Wyatt, the freezing water in the pipes.
- 17:12SPEAKER_02: Guys, if you think a false alarm find and a fire alarm is a huge pain in the butt, imagine thousands or hundreds of thousands of dollars of water damage caused by you or one of your technicians.
- 17:25SPEAKER_02: And it really kind of drives home the point that respect the other trades.
- 17:30SPEAKER_02: You know, there's there's certain things that maybe you don't know about uh what's going on with that, and there's reasons why the code requires certain things.
- 17:39SPEAKER_02: Would you fellas agree with that?
- 17:41SPEAKER_01: Yeah, absolutely.
- 17:43SPEAKER_01: Um, out in the field, there is there is a sometimes spoke sometimes spoken, but usually it's an unspoken rule until you see somebody doing it.
- 17:53SPEAKER_01: Um it's the uh don't touch my stuff.
- 17:56SPEAKER_01: Yeah.
- 17:56SPEAKER_01: So don't touch my stuff.
- 17:58SPEAKER_01: Um and that definitely plays with a dry pipe system, because look for for frame of reference, when it comes to what fire alarm is doing with a sprinkler when it comes to inspection testing, signal.
- 18:13SPEAKER_01: I need signal.
- 18:15SPEAKER_01: Now, for that signal to come through, I don't necessarily need a full sprinkler technician on site with me.
- 18:24SPEAKER_01: Don't touch my stuff, still applies, but you know, uh what we what we usually end up doing, because I need to get signal.
- 18:31SPEAKER_01: And that's all that fire alarm's really looking at.
- 18:33SPEAKER_01: So we'll tickle the switch, which is uh a field term for you you take off the cover and you you you know you tickle the switch.
- 18:43SPEAKER_01: You close a close a uh control valve, stuff that, you know, those things aren't going to have a massive impact with that sprinkler system going.
- 18:52SPEAKER_01: The problem is that you can you will still have technicians that will go out, watch with this with the sprinkler tech for the inspection testing and see that you got to flow water to do water flow alarm.
- 19:03SPEAKER_01: Okay, cool.
- 19:04SPEAKER_01: And that is true on a wet system.
- 19:07SPEAKER_01: It's not true on a dry system.
- 19:09SPEAKER_01: And since uh from a fire alarm side of it, we are not trained in the different types.
- 19:15SPEAKER_01: We're not, we may not have the full understanding.
- 19:18SPEAKER_01: You do sometimes get technicians that go out there and they will go and flow water on a dry system.
- 19:25SPEAKER_01: And it's like, no, no, no, no.
- 19:28SPEAKER_01: And then we run into the issues that Wyatt brought up of the system doesn't get drained back down.
- 19:33SPEAKER_02: And uh, you know, you pay me now or you pay me later, because uh it certainly the fire alarm people aren't going to be qualified to go out there and find all the low point drains and properly drain the system.
- 19:43SPEAKER_02: So uh yeah, it's better to coordinate and like you said, Chris, don't touch my stuff.
- 19:48SPEAKER_02: And I will summarize that in this discussion too, uh, by quoting Mark Twain that good judgment is the result of experience, and experience is the result of bad judgment.
- 19:58SPEAKER_02: Uh we we've all experienced bad judgment or seen people use bad judgment sometimes, and uh, we want to try and avoid that or learn from other people's mistakes.
- 20:08SPEAKER_02: Sure.
- 20:09SPEAKER_02: Well, gentlemen, I appreciate the interesting and lively conversation today.
- 20:14SPEAKER_02: Wyatt, thank you again for taking the time to join us.
- 20:17SPEAKER_02: I want to remind all our listeners to uh please like and subscribe, and we'll see everybody next time.