Latest / HVAC School - For Techs, By Techs

Non-bleed TXVs and Hard Starts - Short #257
In this short podcast episode, Bryan talks about non-bleed TXVs and whether they need hard starts.
A non-bleed (hard shutoff) TXV is a metering device that shuts off during the off cycle; it closes shut when there is no superheat. This strategy prevents refrigerant migration, especially in cases where we have long line sets. Liquid refrigerant stays in the condenser and is kept out of the evaporator, suction line, and compressor crankcase.
When we have a non-bleed TXV, the compressor may have a hard time starting under the conditions created by the hard shutoff TXV (high head pressure, low…