Latest / NTC's Temporal 3 / Episode 39 | 0.7 rule, NFPA 101, fire alarm design, fire alarm panels, exterior closets, and more
Transcript
- 0:05SPEAKER_00: Hello, everyone, and welcome to this episode of the Temporal Three Podcast.
- 0:09SPEAKER_00: I'm joined by my co-host, Mr.
- 0:11SPEAKER_00: Charles Elder.
- 0:12SPEAKER_00: Hello, Charles.
- 0:14SPEAKER_00: Good day, everyone.
- 0:15SPEAKER_00: Hi, Brian.
- 0:16SPEAKER_00: And Mr.
- 0:17SPEAKER_00: Chris Godwin.
- 0:18SPEAKER_00: Hello, Chris.
- 0:19SPEAKER_00: Hi, everybody.
- 0:21SPEAKER_00: Well, guys, today I'd like to talk about the way my AHJ wants it done.
- 0:27SPEAKER_00: Do we ever hear that in the from our students in classes?
- 0:30SPEAKER_00: My AHJ does it this way.
- 0:32SPEAKER_00: My AHJ wants it that way.
- 0:34SPEAKER_00: Set a common refrain.
- 0:37SPEAKER_01: That's not how we do it here.
- 0:39SPEAKER_01: Yeah, yeah.
- 0:42SPEAKER_00: How about you, Charles?
- 0:44SPEAKER_00: Yes, absolutely.
- 0:46SPEAKER_00: Yep.
- 0:47SPEAKER_00: And an important thing to remember about the way my AHJ wants it done is that's great for the real world.
- 0:57SPEAKER_00: You always do what the AHJ wants you to do unless it conflicts with the code.
- 1:03SPEAKER_00: And then you have a discussion with the AHJ about that code conflict.
- 1:07SPEAKER_00: But in the NICET exam, and on a lot of a lot of other exams that you may take, uh, they're based on the codes, not on AHJ preferences.
- 1:19SPEAKER_00: And that's where some people get into trouble.
- 1:21SPEAKER_00: They have that voice of the AHJ, the little AHJ perched on their shoulder telling them, do it this way, do it this way, do it this way.
- 1:28SPEAKER_00: And suddenly they get into the exam and they find out, well, they got a question wrong or they fail the entire exam because they listen to the voice of the AHJ rather than looking in the code.
- 1:38SPEAKER_00: Chris, could you think of an example of what we've seen recently where we've heard that or had that happen in the class?
- 1:46SPEAKER_01: I've had I actually had had a few happen over the last few weeks where uh we were talking about something from code and immediately was, well, that's not how it's done out in the field.
- 1:57SPEAKER_01: And you're right, out in the field things are very different.
- 2:01SPEAKER_01: But, you know, one that one that happens a lot is um your pull station mounting heights.
- 2:07SPEAKER_01: You know, what the code says is it's got to be between 42 to 48 inches above the finished floor um to the actuator.
- 2:14SPEAKER_01: Well, a lot of the interpretation comes out from the HJ on where that actual mounting is, and that might be they might look at it and say it's to the top of the device or to the bottom of the device.
- 2:24SPEAKER_01: It's the code says to the actuator, but the interpretation by the HJ is how it's set, you know, and and that's one aspect of it.
- 2:32SPEAKER_01: And another one is uh all fire alarm cable has to be red.
- 2:38SPEAKER_01: No, it doesn't.
- 2:39SPEAKER_01: Absolutely not.
- 2:41SPEAKER_01: Not according to identifiable.
- 2:44SPEAKER_01: My preference, sure.
- 2:45SPEAKER_01: Make it all red.
- 2:45SPEAKER_01: That makes it easier, but nothing in code says it has to be red.
- 2:49SPEAKER_01: And it's because of yeah, we get so hung up in how the HJ wants it done where we do work that we, you know, a lot of times it's impossible to see past that part.
- 3:01SPEAKER_01: This is how it's done all the time when I'm working.
- 3:03SPEAKER_01: That might be true, but that's not what the exam is going to be looking at.
- 3:08SPEAKER_01: The exam is going to be looking at the black and white words from the code, which are not going to be left for interpretation when you're in the exam.
- 3:16SPEAKER_00: I see a lot of uh age chays, sorry, Charles, uh, see a lot of Hs or a lot of students telling me, well, the H want the uh top of the pole station to 48 inches because that's the mounting height of the light switch.
- 3:27SPEAKER_00: And I said, that's great.
- 3:28SPEAKER_00: That's technically in compliance with the code for 42 to 48 or 3.5 to 4 feet.
- 3:34SPEAKER_00: And um that's great, but what does the code say specifically?
- 3:37SPEAKER_00: Well, as you said, the operable part of the pole station, 42 to 48.
- 3:41SPEAKER_00: And pole stations, most of them nowadays are middle operation, but there are some older ones that you grabbed from the top and reached in.
- 3:48SPEAKER_00: I've seen some explosion proof that you pull from the bottom.
- 3:51SPEAKER_00: Charles, you were gonna add something to that conversation?
- 3:54SPEAKER_02: One thing I think is really important is the fire alarm technician perception of the AHJ.
- 4:03SPEAKER_02: And not that this happens all the time, but I suspect on occasion, industry professionals hear what the AHJ says and interpret it in their own way.
- 4:17SPEAKER_02: Does the AHJ want to violate the code?
- 4:20SPEAKER_02: And my answer to that is absolutely not.
- 4:24SPEAKER_02: Fire alarm professionals such as ourselves, we're experts in the code.
- 4:31SPEAKER_02: Age typically come from the firefighter side.
- 4:35SPEAKER_02: They have limited knowledge of the code, uh, and they may say something that's in conflict with the code, and it's our responsibility to guide them to what the code actually requires.
- 4:48SPEAKER_02: Yep, absolutely.
- 4:50SPEAKER_00: So another one that I uh encounter quite frequently is the 0.7 rule, and that is one that is near and dear to my heart for a specific reason.
- 4:58SPEAKER_00: And when I first started working for NTC and we would teach that in class, that was the thing that I struggled the most with.
- 5:06SPEAKER_00: I honestly can tell you all that it took at least a year, maybe even two, before I could three, okay.
- 5:15SPEAKER_00: That I could explain that.
- 5:18SPEAKER_00: I could not get my brain around it.
- 5:20SPEAKER_00: I don't know why.
- 5:21SPEAKER_00: I had a mental block about that.
- 5:23SPEAKER_00: And um, Charles would help work with me on it and say, here's how you explain it, blah, blah, blah.
- 5:28SPEAKER_00: And I just struggled with that.
- 5:30SPEAKER_00: I can understand it conceptually.
- 5:32SPEAKER_00: I could look at the requirements in the code, but I really had a problem with that.
- 5:36SPEAKER_00: Charles, you want to talk a little bit about the.7 rule?
- 5:39SPEAKER_02: Yeah, the 0.7 rule is a special rule in the code that we use sometimes for corridor applications, particularly.
- 5:47SPEAKER_02: And AHJs are familiar with uh standard spacing for smoke detectors, 30 feet, 15 feet off of the sidewall uh or end wall in the corridor.
- 6:02SPEAKER_02: And the 0.7 rule allows us to extend that distance because it's a narrower space.
- 6:09SPEAKER_02: Uh age Js have a difficult time with that as well, Brian.
- 6:14SPEAKER_02: You're not the only one.
- 6:16SPEAKER_02: And uh if you do get an AHJ who allows you to use the.7 rule, it's important to note that you're probably gonna require 15 feet off of that in the corridor, but not what the uh 0.7 rule would allow, out to 21 feet possibly, depending on the width of the corridor.
- 6:38SPEAKER_02: So keep that in mind.
- 6:40SPEAKER_02: The other aspect what you get approved on the plans may not be what the AHJ on site requires.
- 6:51SPEAKER_02: Chris, if you run into that.
- 6:53SPEAKER_01: Out in Vegas, we don't use they didn't use a the point seven rule often.
- 6:58SPEAKER_01: Uh often enough that I would even know about it from work.
- 7:02SPEAKER_01: But uh I've heard some stories.
- 7:04SPEAKER_01: I've heard some stories about uh around the country, they get it approved, go in, install based upon that, only to have somebody else come out and say, no.
- 7:14SPEAKER_02: Yeah, and that's a real common thing because the AHJ who's inspecting your job site is not the one who approved the plans.
- 7:22SPEAKER_02: So you may end up with discrepancies there.
- 7:25SPEAKER_02: Brian, have you heard of that happening?
- 7:27SPEAKER_00: Oh, yeah.
- 7:28SPEAKER_00: The big the big take from the AHJ is a lot of times, and it depends on who's reading the code and who's interpreting the code, most importantly of all, who's enforcing the code, is that Annex A is titled explanatory material.
- 7:40SPEAKER_00: And this 0.7 rule, at least the illustration of it in the corridor and uh corridors less than 30 feet wide or rooms less than 30 feet wide, is in Annex A and A176311G.
- 7:55SPEAKER_00: And a lot of HJs looking to say, well, that's explanatory material.
- 7:58SPEAKER_00: That's not code.
- 7:59SPEAKER_00: And they're absolutely right, it's not code.
- 8:02SPEAKER_00: But that requirement, the 0.7 rule, is based on the 0.7 rule within the code in 1774 that says all points along the ceiling have to be within 0.7 of the nominal spacing, which is 30 feet on a smoke detector or 21 feet.
- 8:19SPEAKER_00: And that technically complies with that.
- 8:21SPEAKER_00: So you run into an AHA who it is certainly their right to say, I don't accept that.
- 8:28SPEAKER_00: It's unfortunate when it happens after you've already had the plans approved.
- 8:32SPEAKER_00: But yeah, a lot of AHJs have a problem with that.
- 8:35SPEAKER_00: And there's nothing in the code that absolutely says they have to do something.
- 8:39SPEAKER_00: And more importantly, the HJs can basically go below the code requirements, or I should say go above the code requirements.
- 8:46SPEAKER_00: They could say, well, code says 30 feet for smokes, I want them 25 feet.
- 8:51SPEAKER_00: That's okay.
- 8:51SPEAKER_00: You could certainly argue with them, but that's problematic, obviously.
- 8:55SPEAKER_02: And Brian, one thing I would say about that, you alluded to it.
- 8:58SPEAKER_02: I'm gonna hit it on the head a little more directly.
- 9:02SPEAKER_02: That information in NXA explains what the actual code material in chapter 17 means.
- 9:10SPEAKER_02: Right.
- 9:11SPEAKER_02: It's not additional, it's not uh, oh, this is something totally new you could do.
- 9:17SPEAKER_02: It's just giving an example of, hey, this is what that code seven or uh chapter 17 information uh actually means.
- 9:26SPEAKER_02: Right.
- 9:28SPEAKER_00: Great point.
- 9:29SPEAKER_00: And that is the title of it, explanatory material.
- 9:32SPEAKER_00: But uh sometimes sometimes AHJs don't like things explained to them.
- 9:36SPEAKER_00: So the code information is the source material.
- 9:41SPEAKER_00: Actually.
- 9:43SPEAKER_00: Absolutely.
- 9:44SPEAKER_00: And why this matters, why we're discussing this, because the AHJ isn't specifically required to recognize that requirement, to recognize the 0.7 rule to allow you to do that in the real world, but in the NICET exam, they do.
- 9:58SPEAKER_00: And it's not uncommon, particularly at higher levels in the exam, to see questions that involve corridor spacing and minimum number of detectors that will apply the 0.7 rule.
- 10:08SPEAKER_00: So again, uh it doesn't matter what your AHJ says.
- 10:11SPEAKER_00: What matters is the code, and the code says you can do this.
- 10:16SPEAKER_00: Awesome.
- 10:17SPEAKER_00: Guys, next thing I'd like to talk about is uh one of our uh lesser used codes, both in NYSET and in the real world, and that's NFTA 101, life safety code.
- 10:29SPEAKER_00: It's actually one of the older codes, not as old as 72, but older than certainly older than IBC.
- 10:35SPEAKER_00: And um we delve into 101 a bit.
- 10:39SPEAKER_00: It's permitted in the level three exam, um, only in the level three exam for fire alarm.
- 10:46SPEAKER_00: So it's kind of a much ignored code.
- 10:48SPEAKER_00: And we've talked previously about where we find the fire alarm requirements in 101.
- 10:53SPEAKER_00: Charles, where do we find these sprinkler requirements in 101?
- 10:57SPEAKER_02: In 101, they're found in section 3.5 of every occupancy chapter.
- 11:05SPEAKER_00: And so conveniently located right after 3.4, right after finding the fire alarm requirements.
- 11:11SPEAKER_00: And there's two different types of sprinkler systems that are talked about in 3.5.
- 11:16SPEAKER_00: There's an approved automatic sprinkler system and an approved supervised automatic sprinkler system.
- 11:23SPEAKER_00: Chris, what's the difference?
- 11:25SPEAKER_01: The difference between the two of them, an approved automatic sprinkler system, you don't have to have it monitored by a fire alarm system, and typically you don't have off-site monitoring for it.
- 11:36SPEAKER_01: Whereas approved supervised automatic sprinkler system, you're gonna have a panel that's monitoring it, and it's more than likely gonna be sending signals off-site.
- 11:46SPEAKER_01: This is one of my gripes when it comes to NFPA 101, is that if you need it, it doesn't need to be monitored.
- 11:53SPEAKER_01: And uh with the IBC, if the building needs it, it's gonna be monitored.
- 11:58SPEAKER_01: And for me, it just it's it's just kind of how are you going to need a system and not have monitoring for it?
- 12:04SPEAKER_01: How are you gonna need any type of system and say that it might not need to be monitored?
- 12:09SPEAKER_02: So that's one of the frustrations that I have with 101 is if it requires a system, I feel like it should be monitored, but not all systems are absolutely well and I guess it kind of goes to the thought of what's the primary purpose of a fire alarm system?
- 12:28SPEAKER_02: Notification.
- 12:30SPEAKER_02: Right?
- 12:31SPEAKER_02: Hopefully, notification to evacuate people from the building.
- 12:35SPEAKER_02: Uh secondarily to get the fire department there to put the fire out.
- 12:40SPEAKER_02: If I get all the people out and the building burns down, is that really a big deal?
- 12:46SPEAKER_02: If you're the insurance company, it is.
- 12:48SPEAKER_02: Yeah, for the building owner it is.
- 12:50SPEAKER_02: But if the building owner dies, that's a good day.
- 12:54SPEAKER_02: So there is a thought process that runs along those lines, Chris, that may, hey, if the building burns, who cares?
- 13:01SPEAKER_02: At least we got all the people out.
- 13:04SPEAKER_01: Yeah, and I I get that.
- 13:06SPEAKER_01: I just make it monitored.
- 13:07SPEAKER_01: It's fine.
- 13:08SPEAKER_01: It's not that big a deal.
- 13:09SPEAKER_01: Luckily, though, most of the country doesn't really use 101.
- 13:12SPEAKER_01: But that's why this book is, especially for somebody that's not used to it, it's a frustration when you see stuff like this because it's so different.
- 13:21SPEAKER_01: And, you know, that is one of the reasons that we're bringing up this information because not a lot of people are that familiar with NFPA 101.
- 13:30SPEAKER_02: And Brian, what kind of projects would might require an FPA 101?
- 13:35SPEAKER_00: Usually it's government.
- 13:37SPEAKER_00: Yeah, it's a lot of times it's government.
- 13:39SPEAKER_00: Uh, a lot of times the government will use it.
- 13:41SPEAKER_00: Sometimes you'll have uh states, certain states that'll use it.
- 13:44SPEAKER_00: But as Chris said, majority of the country is using IBC.
- 13:48SPEAKER_02: Yeah, and I heard of projects with the federal government, with the Veterans Administration, with hospitals generally, they tend to use one-on-one rather than IBC.
- 14:01SPEAKER_02: And that would be stated in the interests.
- 14:04unknown: Yep.
- 14:05SPEAKER_00: And as fire alarm professionals, we need to be aware of this code, even though we may not use it every day.
- 14:10SPEAKER_00: And obviously, uh, just like any book, if we don't pick it up and look at it every day, we're gonna have certainly certainly be lacking in familiarity with it.
- 14:18SPEAKER_00: But we do need to know about it, not just for the nice exam, but just in general.
- 14:22SPEAKER_00: If we do a project, as Charles said, government, VA, hospitals, Chris said some universities, uh, we'll use it.
- 14:30SPEAKER_00: You know, we we just need to know it's there.
- 14:32SPEAKER_00: We need to know how to find information, know that it's broken down by occupancy chapter as opposed to system like the IBC.
- 14:40SPEAKER_00: I like to say 101 is an occupancy-centric code and uh IBC is a system-centric code.
- 14:46SPEAKER_00: So where is an IBC?
- 14:47SPEAKER_00: We have 907 for all fire alarm in 101.
- 14:50SPEAKER_00: Okay, what kind of occupancy are we looking at?
- 14:52SPEAKER_00: And then we go to that chapter and find fire alarm and sprinkler.
- 14:56SPEAKER_00: But I'm also with Chris, too, that uh I I like the IABC that basically sprinkler systems with more than six sprinklers got to be monitored.
- 15:05SPEAKER_00: And uh it's not just the salesperson and me talking.
- 15:08SPEAKER_00: Of course, the salesperson to me always says, well, every building should have a fire alarm and every building should have a monitored sprinkler system.
- 15:14SPEAKER_00: But uh, you know, that's just me.
- 15:16SPEAKER_00: That's my personal preference.
- 15:18SPEAKER_00: All right, guys.
- 15:19SPEAKER_00: Well, we have our question from the field today from a student.
- 15:22SPEAKER_00: I have a fire alarm control panel located in an exterior closet.
- 15:26SPEAKER_00: What are the requirements?
- 15:28SPEAKER_00: Chris, I know this one's in your wheelhouse from Las Vegas because you had a lot of fire alarm panels outside in the 150-degree heat of Vegas, or it should say in outside closets in that 150-degree heat of Vegas.
- 15:40SPEAKER_01: Exterior closets, they uh I we've seen them, we've had a lot of them with an exterior closet.
- 15:46SPEAKER_01: And it's got to be air conditioned.
- 15:48SPEAKER_01: You've got to be able to make sure that the control equipment's got to be, you know, within an environment where it's not going to be beyond 120 degrees.
- 15:57SPEAKER_01: And or heated.
- 15:58SPEAKER_01: Or heated and heated as well during the winter time.
- 16:01SPEAKER_01: And with that in mind, in Vegas, when we would have these that were in these exterior closets, they were just it was just terrible.
- 16:11SPEAKER_01: It was just awful because yeah, it's inside of it.
- 16:14SPEAKER_01: Yes, it's air conditioned, but they'd a lot of the times they'd install the closet on either the east or the west side of the building and right and direct sun the whole day, or right in direct sun from the other half of the day.
- 16:29SPEAKER_01: And so, regardless of the fact that they're they're air conditioned, they'd always be so, so hot.
- 16:36SPEAKER_01: So you gotta have you gotta have air conditioning, you gotta have heating, you've got to be aware that it it is going to be you're gonna have dirt, dust, and debris as well.
- 16:47SPEAKER_01: So you gotta go through some certain measures to ensure that the that room stays as clean as you can make it.
- 16:53SPEAKER_01: Um my suggestion is don't put it in an exterior closet, put it somewhere inside.
- 17:00SPEAKER_01: Um, electric, even if you're putting it in an electrical room or in the riser room, is a better option than in an exterior closet.
- 17:09SPEAKER_02: Well, we talked earlier about the AHJ.
- 17:12SPEAKER_02: What AHJ is gonna approve a fire alarm panel in a location?
- 17:17SPEAKER_02: A lot.
- 17:17SPEAKER_02: A lot in Vegas.
- 17:19SPEAKER_02: Yeah.
- 17:20SPEAKER_02: Um and I think a lot of a concern than whether my smoke detector is 15 or 18 feet off of the sidewalk.
- 17:28SPEAKER_01: Yeah.
- 17:29SPEAKER_01: And I think a lot of the idea behind it is they don't worry too much about it because, hey, it's got air conditioning, it's got heating, it's got what it needs to have that controlled environment for the equipment.
- 17:42SPEAKER_01: And I mean, yeah, but you know what happens real fast is that that heat, that that air goes out.
- 17:48SPEAKER_01: It works too hard or it doesn't have enough uh force because it's a smaller closet, so it's not able to keep that area cool.
- 17:56SPEAKER_01: So it is one of those things where you do see that you have the air conditioning, you have the heating going to the space, but it's not enough.
- 18:06SPEAKER_01: We did have one that wasn't necessarily in an exterior closet, but it was in a parking garage.
- 18:11SPEAKER_01: It was uh the parking garage was not environmentally controlled, but it was for elevator recall.
- 18:18SPEAKER_01: And they didn't, it was in shade all day, so I mean I guess they had a little bit of a little bit better wiggle room for that, but it was just mounted on the wall in the parking garage, locked up.
- 18:30SPEAKER_00: So, Charles, there are there code requirements that come into play here.
- 18:33SPEAKER_00: Chris talked about the application, and I can certainly uh say a requirement for air conditioning is for the convenience of the technician.
- 18:40SPEAKER_00: No technician wants to work in an outside closet in Vegas without AC.
- 18:44SPEAKER_00: Wants to work anywhere in Vegas without AC, but Charles, are there code requirements?
- 18:48SPEAKER_02: They may not want to work in Alaska in 60 below zero either.
- 18:53SPEAKER_02: Vegas is only one location in the country.
- 18:56SPEAKER_02: There are thousands of others that have similar issues, right?
- 19:00SPEAKER_00: Absolutely.
- 19:01SPEAKER_00: But are there code requirements that come into play here that we're concerned about?
- 19:05SPEAKER_00: Sure.
- 19:05SPEAKER_02: Uh NFTA 72 has specific requirements, NFTA 70 has specific requirements that have to be met.
- 19:14SPEAKER_02: Um for 72, we need to have our control equipment, all electronic equipment, installed within a certain temperature range, within a certain humidity range, so that the uh equipment continues to operate into the future.
- 19:35SPEAKER_00: Absolutely.
- 19:36SPEAKER_00: And those numbers are 32 to 120.
- 19:39SPEAKER_00: Chris mentioned the high end, 120, 32.
- 19:41SPEAKER_00: So it can't go below freezing, but it can't get above 120.
- 19:45SPEAKER_00: The humidity has to be uh 85% or less, and I guess that's not an issue in Vegas, right?
- 19:52SPEAKER_00: Humidity Orlando, it would be.
- 19:54SPEAKER_00: Orlando, yes, absolutely.
- 19:56SPEAKER_00: Florida in general, Florida's a big swamp.
- 19:59SPEAKER_00: Um, yeah, that's it's 100% humidity year-round in Florida, at least from my experience growing up there.
- 20:05SPEAKER_00: Um, so yeah, that's that's a big concern.
- 20:08SPEAKER_00: Chris, what about uh, you know, we have a requirement for a smoke detector above the fire panel.
- 20:12SPEAKER_00: How do we handle that in those closets?
- 20:14SPEAKER_00: How did you how did your company handle it in those closets?
- 20:18SPEAKER_01: Well, um originally because there's an air conditioning and a, we'll call it a controlled environment, we would have a smoke.
- 20:25SPEAKER_01: But the problem is a heat's gonna be a better application for that.
- 20:30SPEAKER_01: For that particular in in in Vegas with an exterior closet, especially if it's gonna be on one of the east or west walls because of constant heat on it all the time, it would be it's gonna be a better idea to use a heat detector because a lot of times you'd be pumping in the AC, but where that pump it that where that vent is is not necessarily always gonna be at the top falling in.
- 20:54SPEAKER_01: And so you'd have your device above it and it's way hotter.
- 20:58SPEAKER_01: So what we'd normally don't end up having to do with these particular types of closets is do a heat detector.
- 21:04SPEAKER_01: Code calls for a smoke, but if the if the uh environment's not gonna be hospitable for a smoke detector because of not being within that temperature range or humidity or um anything of that nature, heat detector is what you're gonna use.
- 21:21SPEAKER_01: And so for a lot of those closets, we had heats instead.
- 21:24SPEAKER_02: Well, two points on that.
- 21:25SPEAKER_02: The first one is Brian, why do you keep bringing Vegas up?
- 21:29SPEAKER_02: There are all kinds of places all over the country.
- 21:32SPEAKER_02: Vegas seems to be your uh obsession right now.
- 21:37SPEAKER_02: I just bring up that's where Chris is from, that's why.
- 21:40SPEAKER_02: If the uh environment isn't appropriate for a smoke detector, it's certainly not appropriate for a panel either.
- 21:47SPEAKER_02: So if you say, hey, a smoke detector is not the right device for this environment, we shouldn't have a panel there either.
- 21:56SPEAKER_02: And if we do find panels located in such areas.
- 22:00SPEAKER_02: We're probably going to have service issues and they should be moved to a more appropriate location.
- 22:06SPEAKER_00: Absolutely.
- 22:07SPEAKER_02: Absolutely.
- 22:08SPEAKER_00: You know, that detector above the panel, too, and or smoke or heat above the panel that uh you fellas were talking about, no matter what the environment is, that only that isn't just a requirement for the fire panel.
- 22:22SPEAKER_00: That's for fire alarm control equipment, which includes NAC extenders and also communications equipment as well.
- 22:29SPEAKER_00: And sometimes what we'll see is NAC extenders in large buildings.
- 22:33SPEAKER_00: You know, if they're wherever they're located, you got to have a smoke or a heat above them, depending on the environment.
- 22:38SPEAKER_00: Uh, you put your cellular communicator higher up in the building or towards the outside of the building for better coverage.
- 22:44SPEAKER_00: Hey, that's communication.
- 22:45SPEAKER_00: You've got to put a smoke above it or heat above it to protect it.
- 22:48SPEAKER_00: So that's something that often gets overlooked and um something we need to remember as well.
- 22:54SPEAKER_00: But Charles, I agree with you that uh that temperature range, no matter where you are in the country, if you're outside that temperature or humidity range, because uh smoke detectors are actually 32 to 100, and um, you know, if it's getting pretty darn close, the 20 degrees difference there.
- 23:10SPEAKER_00: Generally, if it's a bad environment for a panel uh smoke, it's going to be a bad environment for a panel as well, no matter where you are in the country.
- 23:17SPEAKER_02: So, Brian, what's your favorite game in Vegas?
- 23:23SPEAKER_01: I think Brian's mind's on Vegas because uh the conference is coming up.
- 23:28SPEAKER_00: That's true.
- 23:28SPEAKER_00: I'm thinking about how much money I can lose, afford to lose there again this year.
- 23:32SPEAKER_00: It isn't the winners that keep the lights on.
- 23:34SPEAKER_00: I'd say uh I'm a roulette guy.
- 23:36SPEAKER_00: I like uh I like roulette.
- 23:38SPEAKER_00: Really?
- 23:38SPEAKER_00: Yeah, the slot I like the slots too, the poker slots, but um roulette I've had good luck with the past couple times.
- 23:45SPEAKER_00: The uh automated one, not the one with the dealer.
- 23:47SPEAKER_00: I like I like the fast pace with the automated one.
- 23:49SPEAKER_02: Well, Chris mentioned conference.
- 23:52SPEAKER_02: Are you looking forward to conference, Chris?
- 23:55SPEAKER_02: I know I am.
- 23:56SPEAKER_02: Yeah.
- 23:58SPEAKER_02: Absolutely.
- 23:59SPEAKER_00: Me too.
- 24:00SPEAKER_00: It's always a fun trip.
- 24:02SPEAKER_02: Yeah, so that was a lead in to help have you explain a little bit about conference there, Chris.
- 24:08SPEAKER_02: It wasn't just a guest.
- 24:10SPEAKER_01: So uh our NTC conference, national training conference, gonna be happening in Las Vegas November 3rd through the 5th.
- 24:19SPEAKER_01: Uh, we have a lot of classes going on.
- 24:21SPEAKER_01: Uh, from what I have seen, we've got our normal typical fire alarm classes that we nor have been putting on.
- 24:27SPEAKER_01: The inspection testing class, the hands-on of that design are nice at classes like we normally would.
- 24:35SPEAKER_01: Uh, we're gonna be looking at the sprinkler classes that we typically have for INT.
- 24:41SPEAKER_01: But this year we've got other classes.
- 24:45SPEAKER_01: Am I right on that?
- 24:46SPEAKER_01: We're doing some low voltage stuff.
- 24:48SPEAKER_00: We're doing some low voltage, we're doing video access, fire alarm installation.
- 24:52SPEAKER_00: We're also doing the ERCSES classes uh that we did last year.
- 24:56SPEAKER_00: And uh Mike Brownson will be participating in that.
- 24:59SPEAKER_00: And it's a three-day that includes a hand on hands-on component.
- 25:02SPEAKER_00: So anybody who's interested in moving into that area, uh, Mike's got 50 plus years of experience in radio, so you get to learn from somebody who's been doing it for a long time and learn the right way to put in an ERGSE system.
- 25:15SPEAKER_00: And learn that.
- 25:17SPEAKER_02: The one I'm most excited about is uh fire alarm design.
- 25:20SPEAKER_02: That track is uh really an important track in our industry, in my view.
- 25:28SPEAKER_02: And uh Chris, I think you're gonna be uh uh focused on that one to a degree.
- 25:36SPEAKER_01: I'm gonna say I am I am doing that one with Gene.
- 25:41SPEAKER_01: I want to say it's me and Gene on on the design.
- 25:44SPEAKER_00: So yeah, that's that's an important career path uh track for sure.
- 25:48SPEAKER_00: It's three days of design from basic through advanced and using software.
- 25:53SPEAKER_00: Courtesy of our friends at FireCAD who are going to give every student a 30-day license of the software.
- 25:59SPEAKER_00: Uh, so it's definitely somebody who wants to have a career where you're not climbing up and down ladders anymore because that stuff gets old after a while.
- 26:08SPEAKER_00: Um, you know, the knees start giving out and everything else.
- 26:11SPEAKER_00: Um, that's a that's a career path thing.
- 26:13SPEAKER_00: And you can really become very, very well versed in design principles and in Firecat in that class.
- 26:20SPEAKER_00: Awesome.
- 26:20SPEAKER_00: Well, guys, thank you again for the lively and interesting discussion.