Latest / NTC's Temporal 3 / Episode 33 | sprinkler systems, fire protection, inspection, testing, maintenance, and more
Transcript
- 0:02SPEAKER_02: Hello again, everyone, and welcome to the Temporal 3 Podcast.
- 0:06SPEAKER_02: I am joined by my co-host, Mr.
- 0:08SPEAKER_02: Charles Ulner.
- 0:09SPEAKER_02: Hello, Charles.
- 0:10SPEAKER_02: Howdy.
- 0:11SPEAKER_02: Good day, Brian.
- 0:13SPEAKER_02: And my other co-host, Mr.
- 0:15SPEAKER_02: Chris Godwin.
- 0:16SPEAKER_02: Hello, Chris.
- 0:17SPEAKER_02: Hey, what's going on?
- 0:19SPEAKER_02: Well, guys, first thing I'd like to talk about is the value of NIST certification.
- 0:24SPEAKER_02: Charles, in your opinion, is the rigor morrow and challenge and pain that you're going to go through to get NIST certified worth it.
- 0:33SPEAKER_00: I have two things to say about that.
- 0:35SPEAKER_00: First one is money.
- 0:38SPEAKER_00: So yes, it's definitely worth it.
- 0:41SPEAKER_00: Second one is nice at certification is one more step in building your professional credentials.
- 0:49SPEAKER_00: So absolutely worth it on both counts in my book.
- 0:53SPEAKER_02: Absolutely.
- 0:54SPEAKER_02: What do you mean about the money part?
- 0:55SPEAKER_02: I mean, do you mean that it's going to cost you money to get nice set certified?
- 0:59SPEAKER_02: Obviously, it is.
- 1:01SPEAKER_00: There is an expense associated with that, but the key thing about NICET certification is it's more money for you.
- 1:10SPEAKER_00: People who get that certification are just worth more in the marketplace.
- 1:15SPEAKER_00: Employers are willing to pay more, and that's proven out uh year over year in salary statistics that you can find on NISET's website, you can find in Industry Association uh reports such as the National Systems Contractors Association.
- 1:34SPEAKER_00: If you're NICET certified, at whatever level doesn't matter, you're going to be worth more in the market.
- 1:42SPEAKER_00: Uh, obviously, the higher up you go, the more money that you'll be worth.
- 1:47SPEAKER_02: Yeah, and I agree with that part of it.
- 1:48SPEAKER_02: And we've seen that from our students that have moved towards higher levels of certification and achieve more in their professional career, uh, more title and more money by achieving those higher levels of certification.
- 2:02SPEAKER_02: And I would agree with you too that uh the value of certification, because uh I live in North Carolina, you were recently, well, not so recently now, but lived in North Carolina, and we saw North Carolina's not a quote unquote NISAT state, but there was a lot of value placed on NICET certification uh in North Carolina, because even if it's not a state requirement, it's a contract requirement, or as you say, just a professional certification.
- 2:27SPEAKER_02: It's an indication that somebody is very serious about what they do.
- 2:31SPEAKER_00: Well, Brian, you know, before NISAT certification, I felt like the wimpy guy on a beach who the big tough guy would kick sand in my face.
- 2:41SPEAKER_00: As I progressed and I got more and more NISET certification under my belt, no big guy's gonna kick sand in my face.
- 2:49SPEAKER_00: Now I can tell you.
- 2:51SPEAKER_02: Yeah.
- 2:51SPEAKER_02: Well, and now that you're uh now that you're a sensei and uh black belt and all that in karate, uh, I don't think anybody's kicking sand in your face.
- 3:01SPEAKER_00: Chris, did nice at certification help you uh feel uh, I don't know, what word would you use to describe it?
- 3:12SPEAKER_01: Um competent.
- 3:14SPEAKER_01: Much more confident and confident with doing work.
- 3:20SPEAKER_01: It might not be something that's needed wherever you do work, but I do feel that it opens a lot of doors.
- 3:25SPEAKER_01: It brings a lot to you as the technician and a level of competency that is just it takes you to the next level, so to speak.
- 3:37SPEAKER_01: When I was out in out uh working out in the field still, where I was working didn't require it.
- 3:43SPEAKER_01: Well, my background before coming into fire was working in EMS.
- 3:47SPEAKER_01: And with EMS, you have the national registry and then you get licensed wherever you're doing work, and that's how you had to do work.
- 3:53SPEAKER_01: So when I found out going into FIRE, there was something similar.
- 3:57SPEAKER_01: You have a national thing and then you have the local licensing.
- 4:00SPEAKER_01: I was like, oh, same same.
- 4:02SPEAKER_01: It's the same thing.
- 4:03SPEAKER_01: So I uh I got my NISET certification before I got licensed locally.
- 4:10SPEAKER_01: And uh one day my employers came up to me and they were like, Hey, heard you got your NISAT certification.
- 4:16SPEAKER_01: And uh I was very excited because it was early on a Friday morning and that's never a good time to be awake still.
- 4:24SPEAKER_01: And um, I was like, they're gonna tell me congratulations and good job.
- 4:29SPEAKER_01: And I was so excited, and they said, uh, why'd you do that?
- 4:33SPEAKER_01: And I was like, no, mm-mm.
- 4:34SPEAKER_01: Nope.
- 4:35SPEAKER_01: You use the wrong words.
- 4:36SPEAKER_01: There are words and they have meanings, and you use the wrong ones.
- 4:40SPEAKER_01: I think what you were meaning to say was congratulations.
- 4:43SPEAKER_01: And uh they turned around and spun out, well, you don't need it, so we don't we just don't understand why you've got it.
- 4:49SPEAKER_01: And I explained my thought process behind it with the whole EMS side of it, but I also took it into another consideration of doesn't this make us as a company have much more credibility in the sense of our technicians' uh level of competency, doesn't that kind of provide a little bit more in the step of, well, we have technicians that are certified with this?
- 5:12SPEAKER_01: And at first, the company was like, okay, cool, yeah, we can, I guess, see how that works out.
- 5:19SPEAKER_01: Uh, a few months later, they started to recognize that because I had done the extra work, getting the certification, learning much more about the code and how the ins and out of fire alarm work.
- 5:32SPEAKER_01: They realized, hey, this guy's not a dummy.
- 5:34SPEAKER_01: He's he's actually pretty, pretty decent about what he's doing and how to do everything in the field.
- 5:40SPEAKER_01: And because of that, I actually was able to go from working in inspection and testing to service at a rate that the company's never done with any other technician.
- 5:49SPEAKER_01: Remember, I'm brand new to the field.
- 5:51SPEAKER_01: I had just left a career of EMS, and within a short amount of time, they were already saying, nope, move him to the next step, move him on to the next step, just because I was able to have that level of competency that getting NYSET certified provides.
- 6:05SPEAKER_01: It gives you that ability to understand and know how the code works.
- 6:09SPEAKER_01: So it was something that definitely helped out in my my uh my benefit to get certified.
- 6:17SPEAKER_02: I must say that uh nice holding NISET certification was definitely beneficial in my professional life, even though I've worked uh prior to NTC primarily in distribution, and distribution didn't see uh necessarily see value in nice set certification.
- 6:30SPEAKER_02: And I hold uh multiple NISET certifications, uh fire alarm, sprinkler, video, and audio, those last two they don't even offer anymore.
- 6:39SPEAKER_02: But where it hasn't benefited me in my personal life, because my wife still thinks I'm an idiot, even though I have multiple nice set certifications, and I try and tell her how important they are, but she says, oh, it doesn't matter, take out the trash, Mr.
- 6:51SPEAKER_02: NISET.
- 6:51SPEAKER_02: Well, great, guys.
- 6:52SPEAKER_02: I appreciate the uh feedback on the value of certification.
- 6:55SPEAKER_02: And uh as you all both said, that even if you're in an area that doesn't value it, even if your company doesn't necessarily see value in it, do it for yourself.
- 7:03SPEAKER_02: If you're going to be a fire protection professional, be a professional, get that credential.
- 7:09SPEAKER_02: Well, gentlemen, next thing I'd like to talk about is code.
- 7:12SPEAKER_02: I'd like to talk about NFPA 72, Chapter 14, specifically deficiency, impairment, and observation.
- 7:20SPEAKER_02: Now, these three terms are important as far as inspection, testing, and maintenance of fire alarm systems go, and are defined in chapter three.
- 7:29SPEAKER_02: Efficiency is defined as a condition that interferes with the reliability of a system or equipment.
- 7:36SPEAKER_02: Impairment is defined as an abnormal condition where the system component or function is not operable, so making it a little bit higher of a level of uh issue.
- 7:45SPEAKER_02: But there's an interesting that one that got introduced back in 2020.
- 7:51SPEAKER_02: Thank you, Chris.
- 7:51SPEAKER_02: You're you're much more in touch with the uh what changes addition to addition than I do.
- 7:56SPEAKER_02: 2022, and that's observation with a suggested correction that is not an impairment or deficiency.
- 8:02SPEAKER_02: So I find these uh terms to be very interesting, and the code provides, as a general description, a uh guideline as to what they are, and ultimately it is the AHJ's decision whether the system is deficient, impaired, or uh you're making an observation.
- 8:21SPEAKER_02: But I'd like to talk a little bit more about these.
- 8:24SPEAKER_02: Um specifically, I'd like to talk about examples.
- 8:28SPEAKER_02: So let me throw this to you, Chris.
- 8:30SPEAKER_02: Pull station behind a file cabinet, deficiency, impairment, observation.
- 8:36SPEAKER_01: The way I look at it, when we break it down to deficiency, impairment, or observation, does it work?
- 8:42SPEAKER_01: Well, it probably still works.
- 8:44SPEAKER_01: So, from that aspect, I'm not thinking that it's an impairment.
- 8:48SPEAKER_01: Um, it is something that is going to hinder the fire alarm's ability to do its job if we don't know it's there and if it's just pull stations in that building, you're not gonna be able to activate it if there's something in front of it.
- 8:59SPEAKER_01: So I would look at that more on the long along the lines of this is a deficiency.
- 9:04SPEAKER_01: It's a deficiency.
- 9:06SPEAKER_02: If you were to come across that uh as an inspector, Chris, uh, or as an inspection and testing technician, and you were to notice it, and uh, of course, point it out to the customer in your ultimate report, and your customer says, Well, gee, Chris, we don't need to put that on the report.
- 9:21SPEAKER_02: I don't want to black mark on my report.
- 9:23SPEAKER_02: I'll just move that file cabinet and you can erase it from your report.
- 9:27SPEAKER_02: How would you react to that?
- 9:29SPEAKER_01: Um well, even if it's moved, I'm putting it down as a deficiency.
- 9:35SPEAKER_01: And the reason behind that is documenting everything.
- 9:40SPEAKER_01: Have everything in documentation.
- 9:42SPEAKER_01: Um, as you like to say in class, cover your own back end with paper, right?
- 9:47SPEAKER_01: And so even if they if the building owner moves it directly right where I'm in and moves it out of the way, and I watch the whole thing, it's a deficiency first.
- 9:58SPEAKER_01: I'm having documentation that is deficiency first.
- 10:01SPEAKER_01: I'll take a picture of it beforehand, and once it's moved, after everything has been documented and put in as deficiency, what the company that I work for, we would typically do is put it in, send it off.
- 10:15SPEAKER_01: It's corrected right there on site, take pictures, document that it's been corrected on site and send it back in, and that removes the deficiency right then and there.
- 10:26SPEAKER_01: There's in in the in the event that anything happens after I leave and I haven't documented that as a deficiency, I am leaving myself open to getting into some serious problems down the line.
- 10:39SPEAKER_01: Because we all know it's gonna happen.
- 10:41SPEAKER_01: As soon as I'm gone, it's going right back where it was.
- 10:45SPEAKER_01: Whether it's the building owner's like, he's gone, put it back, or someone says, Why is this here?
- 10:49SPEAKER_01: It's going right back to where it was.
- 10:51SPEAKER_01: Without that documentation ahead of time, there's nothing to say that you did your job appropriately and wrote it up.
- 10:58SPEAKER_01: So yeah.
- 10:59SPEAKER_01: I'm I'm doing both.
- 11:01SPEAKER_02: Absolutely.
- 11:02SPEAKER_02: So, Charles, let me throw this one to you.
- 11:04SPEAKER_02: Missing smoke detector above the panel, deficiency, impairment, or observation?
- 11:09SPEAKER_00: So, before I answer that, I have to say I'm confused by this uh to the nth degree.
- 11:16SPEAKER_00: And I just wish there were clearer definitions of each of these.
- 11:21SPEAKER_00: I suspect each of you have experienced impairment in your lives before.
- 11:26SPEAKER_00: Is that true?
- 11:28SPEAKER_00: Yes.
- 11:30SPEAKER_00: Induced by some outside force into your body.
- 11:34SPEAKER_02: Yes, exactly.
- 11:36SPEAKER_00: Uh so impairment is something I have a limited familiarity with.
- 11:42SPEAKER_00: Uh deficiency, that's not induced from the outside.
- 11:47SPEAKER_00: That must be from the inside.
- 11:49SPEAKER_00: I don't know if I have any deficiencies that I can directly relate to.
- 11:54SPEAKER_00: Well, Brian, what do you think?
- 11:56SPEAKER_02: I think we ought to ask Erin.
- 11:57SPEAKER_02: She could probably your wife, she could probably name a whole bunch of them.
- 12:00SPEAKER_02: And I've known you for almost 30 years, over 30 years, so I'd say, yeah, I could probably even name off a few as well.
- 12:07SPEAKER_02: But this is a short podcast, so I don't think we're going to be able to get into that topic.
- 12:11SPEAKER_00: So uh this whole impairment deficiency thing is kind of mixed up in my head to tell you the truth.
- 12:18SPEAKER_00: But if we have a non-functioning smoke detector, uh that is a big issue.
- 12:24SPEAKER_00: It's uh definitely an impairment.
- 12:27SPEAKER_00: And when you think about it, how many smoke detectors are on the system?
- 12:32SPEAKER_00: If your fire alarm system has one and that one detector is non-functioning, that's a pretty serious issue at that point.
- 12:43SPEAKER_00: If your fire alarm system has fifty thousand and you have one that doesn't work, well maybe there's some alternate means of detection that could be uh working in its favor.
- 12:58SPEAKER_00: I don't know.
- 12:59SPEAKER_00: So I would throw that in the impairment category myself.
- 13:03SPEAKER_00: Chris, what are your thoughts?
- 13:05SPEAKER_01: I'm definitely along a similar line with it.
- 13:08SPEAKER_01: And this is and and this is another reason why I don't like how the code defines both of these terms, because you're right, if it's one, if it's one smoke detector in a building and it's the and it's missing, that's 100% going to be an impairment.
- 13:23SPEAKER_01: But if it is you have 50,000 throughout an entire building, one missing isn't really that big of an issue.
- 13:31SPEAKER_01: It's an issue that the device doesn't work.
- 13:34SPEAKER_01: And what I have seen in the field myself when it comes to things like that is you can impair the system or you can impair the device.
- 13:44SPEAKER_01: And a lot of that is how does your AHJ interpret it?
- 13:48SPEAKER_01: Which makes it really difficult from a national level of looking at it from is that an impairment?
- 13:54SPEAKER_01: Is that a deficiency?
- 13:56SPEAKER_01: Now, that being said, uh what I was taught out in the field was work or not.
- 14:04SPEAKER_01: Does it work?
- 14:05SPEAKER_01: Okay, then it's not an impairment.
- 14:07SPEAKER_01: Does it not work?
- 14:08SPEAKER_01: That's an that's an impairment.
- 14:09SPEAKER_01: And you can do system impairment or you can do device impairment.
- 14:14SPEAKER_01: We always weird on the side of caution.
- 14:16SPEAKER_01: And uh, if that system was not 100% functional, the system was impaired.
- 14:22SPEAKER_01: So and again, AHJ interpretation with it.
- 14:25SPEAKER_02: Yep.
- 14:26SPEAKER_02: Better safe than sorry, I agree with you there.
- 14:29SPEAKER_02: So, next example, I'm uh got it on my list here, is a strobe that is set to the incorrect candela, and I would call that one a deficiency.
- 14:37SPEAKER_02: Just because a strobe is set to the incorrect candela, does that mean it doesn't work?
- 14:42SPEAKER_02: Now, if it has, if it's supposed to be 75 according to the drawings and it's set to 110, is that really an issue?
- 14:49SPEAKER_02: Maybe there's a reason why.
- 14:51SPEAKER_02: But even if it's set supposed to be at 75 according to the drawings and it's set at 15, if it still works, may not meet the intensity requirements, but I would call that deficient rather than impaired.
- 15:05SPEAKER_02: Would you guys agree with me on that?
- 15:06SPEAKER_01: I would say it's a deficiency only once.
- 15:09SPEAKER_01: Only once.
- 15:10SPEAKER_01: That's at acceptance.
- 15:11SPEAKER_01: Uh and that's more of a that's more of a out in the field kind of thing, too, is if it was accepted that way, the HJ walked the system during acceptance.
- 15:22SPEAKER_01: They saw that that strobe when it was activated, and they said it's okay.
- 15:26SPEAKER_01: And that's why I would say it's a deficiency one time and it's at acceptance.
- 15:31SPEAKER_01: Because after acceptance during testing, we're not looking at candela rating.
- 15:36SPEAKER_01: So that's that's why I say it's a deficiency, but only the one time.
- 15:39SPEAKER_02: I would say it's a deficiency one to two times per second.
- 15:47SPEAKER_02: Inside joke for fire alarm.
- 15:50SPEAKER_02: Chris, similar to my uh question to Charles about smoke above the panel, what if we have an activated heat detector and the panel's not an alarm?
- 15:57SPEAKER_02: Would you consider that a deficiency or impairment or observation?
- 16:00SPEAKER_01: I would say that's more likely going to be an impairment.
- 16:03SPEAKER_01: I mean, again, looking at it from the argument of does it work or does it not work, the device might be working.
- 16:12SPEAKER_01: And now, when you say an activated heat, what we're seeing a lot more out in the field are electronic heats.
- 16:19SPEAKER_01: But with mechanical heats, if it's activated, it's done.
- 16:23SPEAKER_01: It is never working again.
- 16:25SPEAKER_01: It is done.
- 16:26SPEAKER_01: With an activated electronic heat, it's not sending a signal that is alarm to the panel.
- 16:32SPEAKER_01: And with that in mind, I'm looking at that as uh on the side of caution.
- 16:37SPEAKER_01: I'm making that an impairment if it's an electronic.
- 16:39SPEAKER_01: If it's mechanical, it's an impairment.
- 16:41SPEAKER_01: If it's mechanical, it's done.
- 16:43SPEAKER_01: I can't get it to work ever again, it's done.
- 16:46SPEAKER_01: So it is one of those that I guess phrasing, phrasing on it and how we look at it, but air on the side of caution with it.
- 16:55SPEAKER_01: There's no alarm at the panel.
- 16:56SPEAKER_01: That device is supposed to be setting an alarm typically, and unless we have uh unless it's used for something as a supervisory, I'm putting that as an impairment.
- 17:06SPEAKER_02: Absolutely.
- 17:08SPEAKER_02: Well, guys, last thing I'd like to talk about today is questions from the field about sprinkler systems and supervision of a sprinkler system.
- 17:15SPEAKER_02: And our student had a question about the different types of sprinkler systems from a high level, not a uh not a sprinkler tech level, but a fire alarm technician level.
- 17:24SPEAKER_02: And what kind of connection would they expect to make to these systems?
- 17:29SPEAKER_02: So I'll start this off by talking about the type of sprinkler system that is actually preferred by NFPA 13, as that is a wet sprinkler system.
- 17:39SPEAKER_02: And with a wet sprinkler system, we have water-filled piping that goes all the way to the sprinkler head.
- 17:45SPEAKER_02: It's already, there's water already in the pipe at each sprinkler head.
- 17:49SPEAKER_02: But the problem with this is you can only use it in areas that are not subject to freezing.
- 17:55SPEAKER_02: So if the building itself is subject to freezing, a wet system is out.
- 17:59SPEAKER_02: And the wet systems are better because there's more rapid water delivery.
- 18:03SPEAKER_02: But if that water freezes in the pipe, first of all, it doesn't move.
- 18:07SPEAKER_02: Second, it's probably going to eventually burst that pipe.
- 18:10SPEAKER_02: And when the water, when the when the building thaws, it's going to be a huge mess.
- 18:14SPEAKER_02: Uh certainly not uh desirable in a lot of situations.
- 18:18SPEAKER_02: And typically with a wet system, we're using a vein type water flow.
- 18:22SPEAKER_02: You don't want the one with the paddle that goes into the uh into the um uh riser, thank you, and a valve supervisory.
- 18:31SPEAKER_02: And uh that that's about it, unless we have other equipment connected to it.
- 18:35SPEAKER_02: What about dry systems, Chris?
- 18:38SPEAKER_01: Dry systems, you're not gonna have that vein type water flow.
- 18:41SPEAKER_01: You have a pressure switch monitoring the pressure as you are losing air in the piping and then water's overtaking it.
- 18:48SPEAKER_01: But you're also gonna have a control valve switch, and you're more likely gonna have some additional what we call hilos, just continuously monitoring that air pressure through the system.
- 19:00SPEAKER_01: So you've got a a bit more with a dry pipe system, there's no water.
- 19:04SPEAKER_01: There's no water in the pipe until it's time.
- 19:06SPEAKER_01: And that is when we look at a building that may be subjected to freezing, it's what you're gonna use in most instances is a dry pipe system.
- 19:15SPEAKER_01: And yeah, depending on what else is connected to it, you're probably gonna have more than what you would on a wet system.
- 19:22SPEAKER_01: The more uh the more that connections that you have, the more that you're gonna have to worry about additional devices too.
- 19:30SPEAKER_02: Yep, absolutely.
- 19:32SPEAKER_02: Charles, when you were in the field, did you do much connection to sprinkler systems?
- 19:37SPEAKER_02: Uh we did, yes.
- 19:39SPEAKER_02: Both dry and wet.
- 19:40SPEAKER_02: Dry and wet.
- 19:41SPEAKER_02: And uh I guess a lot of uh flow switches.
- 19:43SPEAKER_02: Did you install the uh the supervisory devices yourself or did you uh let the uh let the sprinkler people do it?
- 19:50SPEAKER_00: Um we had both situations.
- 19:53SPEAKER_00: So I've installed a fair number of OS and Ys and uh PIV uh control valves uh myself.
- 20:01SPEAKER_00: The these two devices, the OS and Y and PIV, control the water supply to a riser.
- 20:08SPEAKER_00: So it's a way to shut off the water supply in case maintenance needs to be done on the sprinkler system.
- 20:14SPEAKER_00: And we want to monitor that monitor that so if the water supply is shut off to the sprinkler system, we know about it.
- 20:23SPEAKER_00: Um it's a really important aspect of uh sprinkler supervisory.
- 20:29SPEAKER_00: And uh in the old days, and you may still see this out there, they'd take a chain and lock these things so they couldn't be turned off.
- 20:38SPEAKER_00: So you may see uh OS and Y, one of those hand wheels with a chain looped through it and a padlock on it.
- 20:46SPEAKER_00: That's the old way of preventing it from being shut off without authorization.
- 20:51SPEAKER_00: Uh, we do that electronically now with the fire alarm panel.
- 20:55SPEAKER_00: Exactly.
- 20:56SPEAKER_02: And uh the new environmentally friendly way is to let a tree grow up through it so you can't close it.
- 21:05SPEAKER_02: So pre-action systems are detection-controlled dry pipe systems.
- 21:11SPEAKER_02: They are similar to dry pipe in that there is air under pressure in the piping.
- 21:15SPEAKER_02: There's no water directly to the heads until water is released into the system.
- 21:19SPEAKER_02: But unlike a dry pipe system where it releases the air pressure and lets the water in when a head pops, there's also an additional function, a solenoid, that controls it.
- 21:27SPEAKER_02: And that solenoid is controlled by a detection system, by pulse station, smokes, heats, etc.
- 21:33SPEAKER_02: And with this one, similar to dry, you're gonna have a pressure-based water flow instead of a paddle.
- 21:38SPEAKER_02: You won't want that paddle flipping off, ripping off rather, when uh the water comes rushing through.
- 21:43SPEAKER_02: There's air pressure supervisory as uh Chris said a high low switch typically, and of course, valve supervisory.
- 21:49SPEAKER_02: Chris, since this is a personal favorite of yours, I want you to talk about Deluge.
- 21:54SPEAKER_01: Uh Deluge is also gonna be detection controlled.
- 21:57SPEAKER_01: Uh you're dealing with all open heads.
- 22:00SPEAKER_01: More more often than not, not necessarily open heads and open nozzles in a lot of instances.
- 22:04SPEAKER_01: And with Deluge, you don't actually have any pressure in the piping because everything's all open.
- 22:13SPEAKER_01: So what you're really only relying on is that automatic detection.
- 22:18SPEAKER_01: So you've got automatic detection tied back to the fire alarm panel.
- 22:21SPEAKER_01: You've got the valves that are going to be supervised.
- 22:24SPEAKER_01: You also got the solenoid.
- 22:26SPEAKER_01: You've got the solenoid that's got to be supervised as well.
- 22:30SPEAKER_01: So it is it's it's a lot like a dry system without any of the pressurization.
- 22:37SPEAKER_01: And we see deluge as a necessity when we need to quickly get the fire under control, quickly and as fast as possible, disperse as much water as as as we can immediately.
- 22:51SPEAKER_01: So really cool systems to watch go off.
- 22:54SPEAKER_01: Um, as long as you're setting them off on purpose.
- 22:57SPEAKER_01: If it's an accident, it's a lot less cool.
- 23:00SPEAKER_01: It's not as uh as good as uh as of a time.
- 23:04SPEAKER_01: It's still cool to watch.
- 23:05SPEAKER_01: It's just uh we weren't supposed to do that.
- 23:08unknown: Yep.
- 23:09SPEAKER_02: So, Chris, all the systems in the movies, what kind of sprinkler systems are in all the movies we see?
- 23:14SPEAKER_02: Lies.
- 23:15SPEAKER_01: They're all lies, is what they are.
- 23:17SPEAKER_01: Um every single movie and TV is just so exaggerated.
- 23:23SPEAKER_01: And it's like every single one is a deluge system.
- 23:26SPEAKER_01: And you know how they set off every single pipe in every movie and TV?
- 23:30SPEAKER_01: Get a lighter and put it to the sprinkler head.
- 23:33unknown: Yep.
- 23:34SPEAKER_01: Deluge systems don't have heads.
- 23:36SPEAKER_01: Yep.
- 23:36SPEAKER_01: They don't have heads at every system in every single movie and TV, every single head goes off.
- 23:42SPEAKER_01: It's just it's for the effect.
- 23:44SPEAKER_01: It's for the effect.
- 23:45SPEAKER_01: Yep.
- 23:46SPEAKER_01: Well, the other thing that gets me too is the water's always clean.
- 23:49SPEAKER_01: Nobody, nobody complains about the smell.
- 23:52SPEAKER_01: Yeah.
- 23:54SPEAKER_00: Well, one other aspect of uh sprinkler systems that's common are fire pumps that pump the uh water from a reservoir to the sprinkler system, and you'll see that frequently as well.
- 24:08SPEAKER_00: We have to monitor the fire pump too.
- 24:11SPEAKER_00: Make sure that there's power to the pump, make sure that it's wired correctly.
- 24:15SPEAKER_00: These are all things that we monitor with the fire alarm system as well.
- 24:20SPEAKER_00: Uh you'll see facilities with big lakes or ponds or pools next to them.
- 24:26SPEAKER_00: That's a water reservoir for the sprinkler system, most likely.
- 24:30SPEAKER_00: And a fire pump pumps that water through the sprinkler pipes in case it's needed.
- 24:36SPEAKER_00: Uh, Chris, in Vegas, do they have such things as that?
- 24:40SPEAKER_01: They have they have a lot of them.
- 24:42SPEAKER_01: They have a lot of different uh examples of them.
- 24:44SPEAKER_01: What you will see, because Vegas is all about show, um, you have these places that have water shows, uh, such as the Bellagio.
- 24:55SPEAKER_01: Um, used to be Treasure Island, or not used to be as in Bellagio, used to be Treasure Island, but Treasure Island used to have a water show as well.
- 25:02SPEAKER_01: Uh, they kind of got done with that.
- 25:04SPEAKER_01: But those same fountain areas are also utilized for the sprinkler.
- 25:10SPEAKER_01: That's a that's another reservoir for the sprinkler systems.
- 25:13SPEAKER_01: So you'll see that in a lot of different instances of that.
- 25:17SPEAKER_01: Um, there are actually some ponds, which is very strange for desert to have any additional freestanding water that hangs out.
- 25:25SPEAKER_01: But um, they'll use that as well, pumping that in for the system.
- 25:30SPEAKER_01: You see pumps needed in a lot of different applications, and especially when you have high rise, you might not have enough pressure getting all the way to those top floors, and that's where we'll see the necessity for the pump.
- 25:42SPEAKER_01: And with that comes a lot more supervision.
- 25:45SPEAKER_01: Absolutely.
- 25:47SPEAKER_00: Absolutely.
- 25:47SPEAKER_00: So sometimes a sprinkler system just needs to be pumped up, Brian.
- 25:53SPEAKER_00: Maximum pumpitude.
- 25:56SPEAKER_02: You don't want a gurley man sprinkler system.
- 26:00SPEAKER_02: If y'all are old enough to remember, if our listeners are old enough to remember that reference, welcome to the club.
- 26:06SPEAKER_02: All right, guys.
- 26:07SPEAKER_02: Well, thanks for pumping me up today talking about fire alarm.
- 26:11SPEAKER_02: I feel like I am at maximum pumpitude today.
- 26:14SPEAKER_02: All right.
- 26:15SPEAKER_02: I want to thank all our listeners again for joining us.
- 26:17SPEAKER_02: Remember to like and subscribe, and we will see y'all next time.