- 0:04SPEAKER_02: Hello, everyone, and welcome again to the Temporal 3 Podcast, where we talk all about fire alarm.
- 0:10SPEAKER_02: We are joined by a special guest today, Mr.
- 0:12SPEAKER_02: Mike McGuinness.
- 0:13SPEAKER_02: Good morning, Mike.
- 0:14SPEAKER_02: How y'all doing?
- 0:16SPEAKER_02: And my usual co-host, Mr.
- 0:17SPEAKER_02: Charles Olner.
- 0:18SPEAKER_02: Hello, Charles.
- 0:19SPEAKER_02: Hi, Brian.
- 0:20SPEAKER_02: Good day, everyone.
- 0:21SPEAKER_02: Hey, everyone.
- 0:22SPEAKER_02: Well, Mike, let's start talking about you.
- 0:24SPEAKER_02: So tell us a little bit about your background, how you got into this industry, uh, why NICET certification became important to you.
- 0:32SPEAKER_01: Right.
- 0:32SPEAKER_01: Well, you know, I have lived in or around uh Hickory, North Carolina, most of my life.
- 0:38SPEAKER_01: And my parents know that from your accent.
- 0:41SPEAKER_01: Yeah, clearly, yeah.
- 0:43SPEAKER_01: But they really like it when I go up north.
- 0:45SPEAKER_01: It's very amusing to them.
- 0:46SPEAKER_01: So anyway, I worked for my parents who ran an installing company and a remote signaling station.
- 0:53SPEAKER_01: They combine it with like an answering service.
- 0:57SPEAKER_01: And if there was anything that we pull could pull wire for, we would go do it.
- 1:01SPEAKER_01: And I I remember from, you know, the youngest times I can remember, my stepdad would walk me into a place, even if we were on vacation, and we'd walk into a hotel hallway and he'd say, Okay, we just went through a door, how far to the first smoke detector and stuff like that.
- 1:18SPEAKER_01: And so we'd get into it.
- 1:20SPEAKER_01: And uh so we did a whole lot of bird stuff too, because we were using equipment primarily from Moose products at that time.
- 1:29SPEAKER_01: If anybody remembers Moose products, they know that they were purchased by AirTech, and then that was purchased by Central, and then that formed Interlogics before it was consumed by GE.
- 1:40SPEAKER_01: And, you know, uh it proves that proton decay does occur because it just disintegrated in the universe, you know, somewhere.
- 1:48SPEAKER_01: Um so I can talk about a company that's not there anymore, right?
- 1:53SPEAKER_01: I mean, absolutely.
- 1:56SPEAKER_01: So um one of the things that happened as these companies, as we acquired these companies, um, or as they acquired us, is we started running into, well, we're dealing with we make smoke detectors, and we have a single commercial fire panel, and it was a real simple one.
- 2:13SPEAKER_01: But more and more we had to start saying, well, can we do this?
- 2:16SPEAKER_01: Can we do this?
- 2:17SPEAKER_01: And there was this one guy from the Portland tech support unit, and he was like, nice at four.
- 2:22SPEAKER_01: And he was all the time telling us, you can't do that, you can't tell, you know, stop telling people to hook up class two transformers and plug them in the wall for this thing.
- 2:31SPEAKER_01: And at that same time, I would have trips and I would be um situation where it says uh, you know, go around and meet the uh uh dealers and the distributors, and I had met Charles, and Charles was you know just beginning with the information from NTC, and he had publications and it had lots of one-liners, and it also had the strategies on how to, you know, best approach the tests, and you know, but I did make it to level three.
- 3:02SPEAKER_01: I had all the elements for level four, but I had worked for manufacturers so long I didn't have a project that I had approved.
- 3:10SPEAKER_01: So I had to pretty much stop there.
- 3:12SPEAKER_01: Unfortunately, I had um a very bad situation.
- 3:16SPEAKER_01: Um, my heart stopped at the top of a really beautiful uh set of marble stairs, and they got my heart going pretty quick, but they didn't realize how much damage they had done to my body or the thing had happened.
- 3:29SPEAKER_01: So I've been out of action really fighting this, you know, disability, but I started studying more and more, and and I talked to Charles about possibly, you know, coming in and just uh working with these guys.
- 3:41SPEAKER_01: And and the first thing I started doing was I sat in on one of Chris's courses and I learned some things that I talked to Charles about.
- 3:48SPEAKER_01: Maybe we'll have time to get into it later.
- 3:51SPEAKER_01: Um, that uh, you know, this style about just thinking you can look it up and and instantly find it in the index and you're gonna go straight to it.
- 4:00SPEAKER_01: It it just flat out doesn't work.
- 4:03SPEAKER_01: And so the strategies that I've been given, especially in the Red Book from NTC, the stuff that I had there to use has proven to be a really good tool.
- 4:14SPEAKER_01: And I'm just excited to be here.
- 4:15SPEAKER_01: So I'll shut up at this point and let you guys talk.
- 4:18SPEAKER_01: Okay.
- 4:18SPEAKER_01: Okay.
- 4:20SPEAKER_02: Well, Mike, one of the things though it's interesting how uh from the manufacturer's side, that nice set certification was important to you.
- 4:28SPEAKER_02: My career prior to NTC was entirely in distribution.
- 4:31SPEAKER_02: Um, I felt nice at certification was important, although not a requirement in distribution was something that was professional credential.
- 4:39SPEAKER_02: Charles, you worked on the install side.
- 4:42SPEAKER_02: Uh, and so you obviously saw the value in NISAT from the install side.
- 4:45SPEAKER_02: So all of us, whether it be install, distribution, manufacturing, uh all see value in NISAT certification as a professional credential.
- 4:55SPEAKER_02: Now, one of the unfortunate things that uh good thing bad things happen to good people, I almost said it the other way, that uh happens is sometimes your NISAT certification expires for whatever reason.
- 5:07SPEAKER_02: I know for me personally, it was a matter of moving.
- 5:10SPEAKER_02: Didn't get my this is when they used to mail them.
- 5:13SPEAKER_02: I didn't get my mail forwarded, um, and it wasn't expired, but it was uh uh going to be if I didn't get if I didn't pay NISAT some money.
- 5:21SPEAKER_02: Mike, you recently had some experience with that as well.
- 5:25SPEAKER_02: And um, I wanted to talk about NISAT and how they handle this.
- 5:30SPEAKER_02: For anybody out there, if they uh haven't paid their renewal, what you need to do, the first thing you need to do is contact NISAT.
- 5:39SPEAKER_02: If there's a question, contact them.
- 5:42SPEAKER_02: You know, if you haven't gotten your renewal or you know your renewal laps, you said, you know what, I left the industry.
- 5:48SPEAKER_02: Uh, I hear that all the time, got out of the industry for X amount of time.
- 5:52SPEAKER_02: First thing you want to do is contact NYSAT.
- 5:54SPEAKER_02: Find out exactly where your certification status is.
- 5:58SPEAKER_02: Uh, important to remember that certifications from NYSET are good for three years, and they recertify you based on the previous three years' activity.
- 6:06SPEAKER_02: So, for recertification, Charles, what are they looking for?
- 6:10SPEAKER_00: They're looking for continued professional development.
- 6:13SPEAKER_00: NYSET calls them CPDs, continuing professional development courses.
- 6:19SPEAKER_00: Uh, they want to see six hours a year, is what it basically turns out to, plus active practitioner in the industry.
- 6:30SPEAKER_00: So over the course of three years, you get 90 continuing professional development points.
- 6:39SPEAKER_00: 72 of those come from being an active practitioner.
- 6:43SPEAKER_00: So that means over three years we have 18 that we have to get through training or other means.
- 6:49SPEAKER_02: Renewal or the recertification notice, I get all mine by email.
- 6:53SPEAKER_02: I think you know, previously back in the old days when NYSET mailed everything, and uh, Mike and Charles, you can relate to this about contacting Nice and having them mail you a program detail manual.
- 7:04SPEAKER_02: Kind of comical.
- 7:05SPEAKER_02: What's wrong with you two?
- 7:07SPEAKER_00: First, Mike talks about wooden pencils.
- 7:10SPEAKER_00: When's the last time you bought one of those?
- 7:13SPEAKER_00: Now you're talking about Pony Express stuff.
- 7:16SPEAKER_02: Pony Express, that's right.
- 7:18SPEAKER_02: That's right.
- 7:19SPEAKER_02: But now generally they come email, and here's the thing with NICET that when you get a renewal, which they send out several months before it is due.
- 7:28SPEAKER_02: And I always encourage our students, I say, look, don't sit on that.
- 7:31SPEAKER_02: Don't wait, oh, I'm gonna get to it, I'm gonna get to it.
- 7:33SPEAKER_02: No, deal with it ASAP.
- 7:35SPEAKER_02: Make sure you got your CPDUs lined up.
- 7:38SPEAKER_02: Get it going, because if they do not receive payment by your resert date, you are not renewed.
- 7:45SPEAKER_02: And now you're in a situation where you may have to pay a reinstatement fee, or after three years, they expunge you.
- 7:53SPEAKER_02: They remove you after three years.
- 7:56SPEAKER_02: So automatically not paying them is going to be a fee.
- 8:00SPEAKER_02: Three years means you start over from nice at zero and have to go through the entire prep uh program again.
- 8:07SPEAKER_00: Well, Brian, you said that if you're late, you may have to pay an extra fee.
- 8:13SPEAKER_00: Is that the way it works?
- 8:14SPEAKER_00: Maybe you do.
- 8:16SPEAKER_02: I think that no, from my experience, if you're late, you will pay an extra fee.
- 8:20SPEAKER_00: Yeah, there's no maybe about that.
- 8:25SPEAKER_01: I have I have two experiences on that, first of all.
- 8:29SPEAKER_01: When I was practicing the trade, and I remember realizing that I was like on the absolute deadline when I was on vacation with my wife in a resort down in Orlando, and like I had to call my set and have them fast me the forms to the resort, you know, and I started filling them out real quick and everything, and of course, and I had to like then get a check and then overnight it so that I could fit in that time.
- 8:57SPEAKER_01: Um, unfortunately, the situation I'm in right now, I I do want to mention something.
- 9:03SPEAKER_01: The administrator there, um, I his name is Chip, I believe.
- 9:08SPEAKER_01: And um he really listened to me.
- 9:12SPEAKER_01: When I had this accident, it was like everybody was gonna say, it's time to put Mike out on the porch with a rocking chair or something.
- 9:21SPEAKER_01: And when I talked to him about what I was trying to do, and Chip, you know, he was honest with me.
- 9:26SPEAKER_01: He says, you know, Mike, at this amount of time, because you consider since 2019 till really me starting this effort just recently, um, he said, you know, Mike, there's gonna be some retesting.
- 9:40SPEAKER_01: And I knew right then, I said, I need to give Charles a call.
- 9:44SPEAKER_01: You know, I said, I gotta figure out how to do this.
- 9:47SPEAKER_01: And he said, work experience, we're gonna, we're gonna have to figure out what you've done or are doing.
- 9:55SPEAKER_01: And so, like associating myself with NTC, taking as many classes as I can.
- 10:02SPEAKER_01: I've signed up with the uh local uh Harvard on the highway here in community about an NEC course and some things like that.
- 10:10SPEAKER_01: And I'm still getting calls here on my personal cell about uh panels that we made years ago from guys that just remember my name and had my phone.
- 10:22SPEAKER_01: But I I started making a log of that stuff because I need something to prove it.
- 10:27SPEAKER_01: So I'm in that that eight ball behind the eight-ball situation there because um I am going to have to do this and see also to get my other credentials, like to get my alarm license back in North Carolina, I'm gonna have to approach the electrical licensing board.
- 10:46SPEAKER_01: And they have a similar criteria.
- 10:48SPEAKER_01: You know, 2,000 man hours counts as a year, and you have to have two years of work in the trade.
- 10:56SPEAKER_01: And I held the license, and the the interesting thing is I taught the very first continuing ed class for the electrical board in North Carolina.
- 11:07SPEAKER_01: I actually created the course, I set it up.
- 11:10SPEAKER_01: So I'm gonna have to go back to these people and make a case that, you know, there are some special situations where people are ADA that are not covered by the traditional catch-up rules.
- 11:24SPEAKER_01: So I'll leave it with that.
- 11:26SPEAKER_01: There's people like me that you're gonna have to really jump some hoops and get there.
- 11:31SPEAKER_01: And then there's not some of you that are like, you're just late.
- 11:36SPEAKER_01: The first thing you do is get the check in, okay?
- 11:40SPEAKER_01: And then, you know, go online and get the papers work set up there.
- 11:44SPEAKER_01: Absolutely.
- 11:45SPEAKER_01: Yeah.
- 11:45SPEAKER_01: Sorry, didn't want to take so long.
- 11:48SPEAKER_02: Quite all right.
- 11:49SPEAKER_02: So, yeah, and you mentioned Chip Hollis at NYSET, who is just a phenomenal individual at NYSET.
- 11:56SPEAKER_02: Um, I'm gonna share his email address.
- 11:58SPEAKER_02: Chip may not like me doing this.
- 12:00SPEAKER_02: Well, Chip doesn't mind.
- 12:01SPEAKER_02: He's very supportive of NYSET's uh certificates.
- 12:04SPEAKER_02: It's C Hollis, H-O-L-L-I-S at nyset.org.
- 12:09SPEAKER_02: You can also call the NYSET number, the uh 888 is NISET, and request him.
- 12:14SPEAKER_02: You'll probably get his voicemail because he travels quite extensively, but he does respond.
- 12:19SPEAKER_02: And he is a huge credit to NYSET for individuals, whether you're in Mike's situation or having any kind of issue with NYSET, that will help you out.
- 12:28SPEAKER_02: And he's a very sympathetic ear and we'll try to figure out a way for you to get where you need to be with NYSET.
- 12:35SPEAKER_02: Well, enough of the uh depressing stuff about reinstating an expired nice set certification.
- 12:40SPEAKER_02: Let's talk about our favorite topic in the whole world, guys, code.
- 12:44SPEAKER_02: So cable and device support.
- 12:48SPEAKER_02: Are there requirements in the NEC, Charles, about cable and device support?
- 12:52SPEAKER_02: Nope.
- 12:53SPEAKER_02: Nope.
- 12:53SPEAKER_02: Absolutely.
- 12:54SPEAKER_00: Doesn't have any requirements at all.
- 12:56SPEAKER_00: Nothing at all.
- 12:57SPEAKER_00: That's what it's all about there, Brian.
- 13:01SPEAKER_00: Uh cableing is the NEC's thing.
- 13:05SPEAKER_00: That's its uh claim to fame.
- 13:07SPEAKER_00: And yes, it does have specific requirements for cabling in terms of support and uh installation and what we have to do.
- 13:16SPEAKER_02: And there's um a couple that I I like to key on supported by permanent building structure.
- 13:21SPEAKER_02: What does that mean?
- 13:22SPEAKER_02: Well, you can't attach it then anything that's not part of the permanent building structure.
- 13:27SPEAKER_02: And uh Sprinkler piping's part of the sprinkler piping, yeah.
- 13:31SPEAKER_00: Part of the permanent building structure, right?
- 13:33SPEAKER_02: Yeah, the sprinkler guys love it when you do that.
- 13:36SPEAKER_02: They will cut your wire with good reason.
- 13:39SPEAKER_02: And uh, you know, other things like hanging it, supporting it on the uh the drop ceiling.
- 13:43SPEAKER_02: That's not part of the permanent building structure because what happens when that when there's a fire, what's gonna happen to that drop ceiling?
- 13:50SPEAKER_02: That's gonna collapse.
- 13:51SPEAKER_02: That's gonna collapse.
- 13:53SPEAKER_01: I had a fire marshal who spent some time with me on that.
- 13:57SPEAKER_01: I have learned so much about code is by doing so many things wrong, unfortunately, and be then being corrected.
- 14:06SPEAKER_01: And I was very bad about on a grid system, you know, laying the wire on top of tile grid and then going to the grid itself and then drilling pilot holes through the section of the grid to mount the detector and this kind of thing.
- 14:21SPEAKER_01: And and I thought, you know, I'm doing a great job until a fire marshal comes along and says, Well, let's have a little come to Jesus talk here.
- 14:29SPEAKER_01: And he says, first of all, that grid is designed for the the weight of those tiles, not for your detector.
- 14:36SPEAKER_01: And just by drilling into it, you compromise that.
- 14:40SPEAKER_01: And the most important thing he talked about is he says, the the polymer that is the insulation on the cabling that you lay up there, at some point the fire is going to exceed its protection ratio.
- 14:56SPEAKER_01: And it's since it's a petroleum-based product, it will actually become a component of the fire.
- 15:04SPEAKER_01: And if you've got a bunch of fire marshals and they're using these high-pressure hoses and they blow this stuff down on top of themselves, then you've created a bigger problem than you've ever solved.
- 15:18SPEAKER_01: Wow.
- 15:18SPEAKER_01: And so, like I said, you know, um, I'm confessing my sins here.
- 15:23SPEAKER_01: I'll, you know, go find me a priest or a preacher or something later and everything.
- 15:27SPEAKER_01: But I I was blessed at that time that I had a fire marshal in Hickory that he viewed his whole job was not to just come out and write you up, but to explain to you this is why you need not or need to do this, you know.
- 15:46SPEAKER_01: So yeah.
- 15:48SPEAKER_01: Wow.
- 15:49SPEAKER_02: That's that's fantastic that you had one that explained it.
- 15:51SPEAKER_02: You're right.
- 15:52SPEAKER_02: A lot of them are just kind of uh, you know, Dr.
- 15:54SPEAKER_02: No, they want to tell you no, no, no, and here's everything you're doing wrong.
- 15:57SPEAKER_02: But one that obviously had a fireman background because he knew what was going to happen or had some education in it.
- 16:04SPEAKER_02: And if, you know, we we can open those lines of communication or get firemen, fire marshals, AHJs that will help educate the technician, I think uh, you know, from your perspective, understanding why you shouldn't do that, I think made a heck of a lot more difference to you than just being told, just don't do that without an explanation.
- 16:22SPEAKER_01: This guy was very good.
- 16:24SPEAKER_01: I hope Tommy Bradshaw doesn't mind me using his name because he went to become an insurance inspector.
- 16:32SPEAKER_01: If you talk about the difference between the more stringent about what people will do, an insurance company will come in here and say, we don't care what the fire marshal said.
- 16:43SPEAKER_01: If we're going to insure this, this is the way it's gonna be.
- 16:46SPEAKER_01: But he would actually donate something like a Saturday out of his month to get with an alarm association or a group or somebody, even if it was other fire inspectors or fire marshals, and say, this is what we're doing, this is why we're doing it.
- 17:02SPEAKER_01: The other cool thing is he he talked about the most common things he cites people on.
- 17:08SPEAKER_01: So I want to get an extra word there for Tommy.
- 17:11SPEAKER_02: Well, next topic I'd like to talk about today, guys, is our question from the field.
- 17:16SPEAKER_02: And our question from the field is what are the location and spacing considerations of combination initiating devices?
- 17:22SPEAKER_02: Charles, what the heck is a combination initiating device?
- 17:26SPEAKER_00: It's a device that has multiple detection capabilities.
- 17:31SPEAKER_00: As an example, a smoke detector and a heat detector.
- 17:34SPEAKER_02: Yeah, that's real really it.
- 17:35SPEAKER_02: I mean, basically it's a detector that has multiple detection methods.
- 17:39SPEAKER_02: There's combination, like you say, smoke heat, there's multi-criteria, multi-sensor, which have uh different variables depending upon how they process signals.
- 17:48SPEAKER_02: But we'll we'll stay focused on the smoke heat combo because that again is the one that most of us will encounter.
- 17:54SPEAKER_02: And um, with smoke heat combinations, the interesting thing about smoke heat, and this is a code requirement, it doesn't necessarily impact the uh fire alarm technician, at least not directly, is that when you have a combination smoke heat, the heat detector in that device has to have a 50-foot list listed spacing.
- 18:14SPEAKER_02: Charles, does that mean I can place those smoke detectors 50 feet apart since the heats are 50 foot listed?
- 18:19SPEAKER_00: No, the device is a smoke detector, so you have to follow the rules for smoke detectors.
- 18:25SPEAKER_00: 30-foot spacing nominal is what we have to use for those.
- 18:28SPEAKER_00: Absolutely.
- 18:29SPEAKER_00: In open areas.
- 18:30SPEAKER_01: Or you could view it that you have to go with the the more stringent of the two that way as well.
- 18:37SPEAKER_01: It is smoke and it is heat, but the more stringent in this case, whether whether you went with 30 foot or 0.7, it wouldn't matter.
- 18:47SPEAKER_01: It would that would still be a shorter distance than 50 feet spacing there.
- 18:53SPEAKER_00: Mike, I might uh throw the consideration out there that uh the device is a smoke detector.
- 19:02SPEAKER_00: That heat detector element is auxiliary or supplemental.
- 19:08SPEAKER_00: Right.
- 19:08SPEAKER_00: So yeah, it has a heat detector on it, but that's really not the purpose of the device.
- 19:14SPEAKER_00: Right.
- 19:14SPEAKER_00: A smoke detector is life safety.
- 19:17SPEAKER_00: A heat detector is not a life safety device.
- 19:21SPEAKER_00: Right.
- 19:21SPEAKER_00: So that auxiliary function, sure, it's there, but smoke detector rules are what we have to follow for that thing.
- 19:31SPEAKER_02: And I'm willing to bet if you look at the listing on the detector, it probably is listed as the UL standard for smoke detector, which of course at the moment escapes me.
- 19:39SPEAKER_02: I know it's 217 for smoke alarms.
- 19:41SPEAKER_02: I can't remember what the one is for smoke detector.
- 19:46SPEAKER_01: Yeah.
- 19:47SPEAKER_02: Thanks, guys.
- 19:48SPEAKER_02: Yeah, I was having a mental block.
- 19:50SPEAKER_02: So when we have that hypothetical smoke heat combo, and this is one that uh Charles and I have uh had some discussion about, and Mike, we've we've talked about a little bit.
- 20:01SPEAKER_02: There's a difference in 72 for how we space them.
- 20:06SPEAKER_02: So smoke detectors have a 30-foot accepted spacing.
- 20:10SPEAKER_02: Charles, what do we mean by accepted spacing?
- 20:13SPEAKER_00: Uh that means the code allows us to use 30-foot spacing for smoke detectors.
- 20:21SPEAKER_00: It's not an actual listed spacing like we have for heat detectors, because UL doesn't actually test it that way.
- 20:30SPEAKER_00: So the code says we're allowed to use 30-foot for smokes, whereas a heat detector has a listed spacing, typically a rate of rise is 50 feet.
- 20:43unknown: Yep.
- 20:44SPEAKER_02: And then you've got heats that have, as you mentioned, listed spacing, which can be anywhere from 15, 1, 5 to 70.
- 20:50SPEAKER_02: There are some newer heat detectors, electronics out there that have uh a 70-foot listed spacing.
- 20:57SPEAKER_02: And um, as you mentioned, Charles, I'm with you guys that what no matter what the reasoning is, that if it's a combination smoke heat, it's 30 feet.
- 21:06SPEAKER_02: Um and if we're placing them in the corner with smokes, there's no restriction on the distance from the corner if it's wall or ceiling mounted.
- 21:13SPEAKER_02: That changed in 2013, I want to say.
- 21:16SPEAKER_02: Uh 72-2013.
- 21:18SPEAKER_02: But for heats, we still have that uh that exclusion triangle, as I like to call it, where you can't be closer than four inches from the sidewall and Ford 12 from the ceiling if it's a wall mount.
- 21:30SPEAKER_02: But there are no specific guidelines in 72 if it's a combination device as to how you locate the device.
- 21:38SPEAKER_02: So again, we go back to, and I'm I'm curious to hear y'all's thoughts on this.
- 21:43SPEAKER_02: More stringent requirement, as Charles pointed out, listing of the device, how do you place it?
- 21:48SPEAKER_02: Charles, what's your take on this?
- 21:49SPEAKER_00: Well, I think it's apparent.
- 21:53SPEAKER_00: If I'm installing the device as a smoke detector, it's listed as a smoke detector.
- 22:00SPEAKER_00: I follow the smoke detector rules regardless of what ancillary device might be on the the thing as well.
- 22:07SPEAKER_00: So it's apparent to me that smoke detector requirements are what we have to follow.
- 22:14SPEAKER_00: Mike, what do you think on this topic?
- 22:16SPEAKER_01: Well, uh you know, I I played devil's advocate when uh Charles and you and I had discussed this.
- 22:22SPEAKER_01: My point was what if the ruling AHJ comes up to you and says, well, um that has a heat detector and must comply with the placement for heat detectors.
- 22:34SPEAKER_01: You know, the you've got the the whole base and then the shell of the detector, but in the very core, you have the smoke sensor element of either photoelectric or you know, an ionization device there.
- 22:52SPEAKER_01: But you also have these on each end of that two little thermostats.
- 22:56SPEAKER_01: And now that thermostat is gonna be in that so-called dead space for heat.
- 23:03SPEAKER_01: And what if I want to just be a prick?
- 23:05SPEAKER_01: I'm the AHA, you know, I've got this badge and everything.
- 23:08SPEAKER_01: I can just come in and cause havoc everywhere.
- 23:11SPEAKER_01: I'm I know I'm gonna get some beat up from that.
- 23:14SPEAKER_01: And it's okay.
- 23:16SPEAKER_00: Hey, Tommy Bradtraw's coming after you, buddy.
- 23:20SPEAKER_01: My email is ccon1 at charter.net, and I welcome your your viewpoint that that's Fire Marshall Bradtraw, go get him.
- 23:32SPEAKER_01: Somebody's gonna get upset about that.
- 23:35SPEAKER_01: And so I I felt the question I came is asked you that, well, if you're gonna wall mount, then you know, you can maintain the integrity of it by coming down below the four inch.
- 23:51SPEAKER_01: And I think what it used to say is like some part had to be between four and twelve inches on wall mount.
- 24:00SPEAKER_01: If you're doing ceiling mount, um, you know, just coming out of there four inches isn't that really big a deal.
- 24:09SPEAKER_01: And um, you know, the the way they and I was taught is that the smoke will plume into the corner, but he is protected by a pocket of air where the hotter air has risen and has forced the cooler air in into those little pockets and things like that.
- 24:30SPEAKER_01: So I guess I took the devil co devil's advocate view opposing Charles, saying, you know, somebody could say something, and to avoid the whole thing, let's let's just stay out of there, you know.
- 24:45SPEAKER_00: So well, and I guess you could look at it two ways.
- 24:50SPEAKER_00: Is it a smoke detector with an ancillary heat detector?
- 24:55SPEAKER_00: Or is it a heat detector that it has uh as an auxiliary function smoke detection?
- 25:01SPEAKER_00: And obviously, if we're installing smokes, that's the primary life safety function right there.
- 25:10SPEAKER_00: It's listed as a 268 smoke detector.
- 25:13SPEAKER_00: Uh it seems clear-cut to me.
- 25:16SPEAKER_00: There are RAHJs out there that could uh stipulate whatever they want on a job, sure.
- 25:25SPEAKER_00: But the code seems pretty clear.
- 25:27SPEAKER_01: There used to be a franchise company, and they would do this trick and come out and show in to consumers, and they had a little device that had a tube and it had a butane source of heat.
- 25:43SPEAKER_01: They'd show their device sitting on it, which oddly enough was spring wound.
- 25:50SPEAKER_01: Okay.
- 25:51SPEAKER_01: So there was no battery or anything like that.
- 25:54SPEAKER_01: It just had you had to go back and make it after it was used.
- 25:58SPEAKER_00: And of course it didn't have a battery.
- 26:00SPEAKER_00: They hadn't been invented yet back then.
- 26:02SPEAKER_01: And the well, now this these guys were actually in the electronic industry.
- 26:07SPEAKER_01: We were we weren't doing touch screens yet, but they were doing heat detectors.
- 26:12SPEAKER_01: And so they would show how their heat detector would go off instantly.
- 26:16SPEAKER_01: Then they take a battery-operated smoke detector that, of course, worked on a photoelectric principle, not an ionization principle, and they would lay in over the top of it, and the smoke detector would literally melt and start falling apart way before it ever went into alarm.
- 26:37SPEAKER_01: And I kept telling people, I said, look at their detector.
- 26:41SPEAKER_01: It has to say it's not a life safety device that's required.
- 26:46SPEAKER_01: But even in residential, the products of combustion available in the premise are usually wood paper based and carpet has formaldehyde in it and all those things.
- 27:01SPEAKER_01: And it's going to create a product that a smoke detector uh by obscuration can detect.
- 27:09SPEAKER_01: Whereas a heat detector won't see it until the heat detector's position itself has reached the rated temperature.
- 27:18SPEAKER_01: So, you know, a guy would call me up when I was working for my parents.
- 27:23SPEAKER_01: It's like, I want you to ask this guy to come back over and I want you to take some materials from the house, some a piece of the curtain, a piece of something else, and throw it in his butane burner and then see how quick the smoke detector goes off because there's no such thing as a clean burn environment.
- 27:42SPEAKER_01: So I just don't want people to get the thought that um I'm gonna put it here and that's always gonna be right because number one, there could be an AHA that says, hmm, I just disagree with you, and you really don't have an option at that point.
- 27:59SPEAKER_01: I don't know that anybody is ever even really gonna face that.
- 28:03SPEAKER_00: Maybe some guys will say and I think an important consideration there from a smoke detector perspective, is it acceptable for a smoke detector to be located in either of those places?
- 28:17SPEAKER_00: Yeah.
- 28:18SPEAKER_00: So neither one is a code violation.
- 28:20SPEAKER_00: Right, right.
- 28:21SPEAKER_02: Well, Mike, I appreciate the story on that.
- 28:23SPEAKER_02: I was I always wondered how spring-wound devices ended up in chapter 29 of 72.
- 28:29SPEAKER_02: I've seen them in there, yeah, and I always said, I've never seen one.
- 28:33SPEAKER_02: I've been doing this 45 years.
- 28:35SPEAKER_02: I've never seen one.
- 28:36SPEAKER_02: So now you kind of clarified that for me.
- 28:38SPEAKER_02: I'm gonna have to ask you offline uh what the name of that company was so I can look it up.
- 28:42SPEAKER_01: Yeah.
- 28:42SPEAKER_01: Well, the the the remember that section of 29 also was dealing with the old street box game well boxes where you you'd see a fire.
- 28:53SPEAKER_01: Remember, you you couldn't go to the nearest phone and and call 911 and you didn't have a cell phone.
- 28:59SPEAKER_01: So you went to this red box, uh, and it's usually made by either Game Well or Wells Fargo.
- 29:06SPEAKER_01: And then when the fire was over, this thing had to be wound back up.
- 29:11SPEAKER_01: Sure.
- 29:12SPEAKER_01: And it was doing some interesting stuff because the city was trying to save money, so they would run wire from box to box to box to box back to the fire department, and that's where the McCullough loop things, you know, are their original use was in place with you know a hard pair going from point A to C and D and E and so on.
- 29:35SPEAKER_00: So but I think for all that history crap that none of us will ever experience.
- 29:40SPEAKER_01: Yeah, yeah.
- 29:42unknown: Yeah.
- 29:43SPEAKER_01: Well, it's I am familiar with that.
- 29:45SPEAKER_02: I am familiar with that.
- 29:46SPEAKER_02: I was talking about a household.
- 29:47SPEAKER_01: I help you.
- 29:48SPEAKER_01: I help uh I help write stuff for Wikipedia too that people will never use.
- 29:53SPEAKER_01: You know, it's like you know, and my daughter, you know, I pulled this thing on my daughter when she was real young, and I said, when I was young, you had to get up to change the TV channel.
- 30:05SPEAKER_01: And as quick as a whip, she comes back and she said, Yeah, but grandma said you you only had three channels back then.
- 30:11SPEAKER_02: Right, right, yeah.
- 30:14SPEAKER_01: But yeah, the history sometimes is helpful.
- 30:17SPEAKER_02: Absolutely.
- 30:18SPEAKER_02: All right, guys.
- 30:18SPEAKER_02: Well, hey, thank you again for an interesting and lively conversation.
- 30:22SPEAKER_02: Mike, thanks for joining us today.
- 30:25SPEAKER_02: And uh, you all heard Mike's email earlier if you want to hit Mike up on uh some of the things that he brought up and challenging on some things.
- 30:32SPEAKER_02: That's awesome.
- 30:33SPEAKER_02: Uh, I want to thank everybody for listening.
- 30:35SPEAKER_02: Please remember to like and subscribe, and we'll see y'all next time.
- 30:39SPEAKER_02: Thanks again, guys.
- 30:40SPEAKER_02: Thanks, Brian.
- 30:41SPEAKER_02: Thanks, Mike.
- 30:42SPEAKER_02: Thank you, guys.