Latest / HVAC School - For Techs, By Techs

Short #2 - Delta T
Today, Bryan discusses delta T (evaporator air temperature split) what it is, what it means, and how to avoid some common pitfalls.
Delta T is NOT the air temperature rise on a furnace, and it is NOT the design temperature difference (DTD). Instead, delta T refers to the temperature split between return air entering the evaporator coil and the supply air leaving the unit. Typically, 20 degrees (Fahrenheit) is a desirable split, but there is still a range based on relative humidity, enthalpy, and airflow. The range can be as high as 24 degrees.
To measure delta T properly, you need…
The skinny