- 0:01Speaker 1: Chapter six of Silent Sentinels by Westinghouse Electric and Manufacturing Company.
- 0:09Speaker 1: This LibriVox recording is in the public domain. Relay settings,
- 0:16Speaker 1: the selection of the proper current tap in time index,
- 0:21Speaker 1: lever setting, or induction type over current relays demands a
- 0:25Speaker 1: knowledge of the load conditions in the circuit or portion
- 0:29Speaker 1: of the circuit to be protected, and the amount of
- 0:33Speaker 1: short circuit current available under minimum generating capacity conditions. It
- 0:39Speaker 1: is also desirable to know the amount of short circuit
- 0:43Speaker 1: current available under maximum generating conditions, but in case the
- 0:48Speaker 1: data is not available, the interrupting ability of the oil
- 0:52Speaker 1: circuit breaker will service a first approximation. While there are
- 0:57Speaker 1: minor modifications in the actual set of the relays dependent
- 1:02Speaker 1: on the particular type of protection employed. The following remarks
- 1:07Speaker 1: will outline the general considerations with reference to the simpler
- 1:11Speaker 1: cases current tap settings on radio and loop feeders, the
- 1:18Speaker 1: proper current tap is determined largely by the current transformer
- 1:22Speaker 1: ratio and the full load current in the feeder. In general,
- 1:27Speaker 1: the current tap is so chosen to be at least
- 1:30Speaker 1: two hundred percent of the secondary current from the current
- 1:34Speaker 1: transformers when carrying full load in the line. In cases
- 1:40Speaker 1: where the load is subject to violent fluctuations, it may
- 1:44Speaker 1: be necessary to make normal operating current for the relay
- 1:48Speaker 1: three hundred percent of the secondary current corresponding to normal
- 1:53Speaker 1: full load. The current tap should not, however, be chosen
- 1:58Speaker 1: so high that the wheels delay winding receives less than
- 2:02Speaker 1: three hundred percent of its current setting under short circuit
- 2:06Speaker 1: with minimum generating capacity on the system, as otherwise, the
- 2:11Speaker 1: time of operation will be so long as to completely
- 2:15Speaker 1: disrupt service. Time settings on radial feeders, the proper time
- 2:22Speaker 1: of operation of the relay is determined by its location
- 2:27Speaker 1: with respect to the source of power and other relays
- 2:31Speaker 1: on the same circuit. For a radio feeder system, the
- 2:35Speaker 1: outermost relay is set for the shortest time, and the
- 2:39Speaker 1: relays towards the generating station for successively longer times. The
- 2:44Speaker 1: relays at the source of power must be set sufficiently
- 2:49Speaker 1: long to allow any outlying faulty section to be cleared.
- 2:53Speaker 1: With induction type relays and direct current operated circuit breakers,
- 2:59Speaker 1: it is common practice to set successive relays for time
- 3:03Speaker 1: intervals zero point five seconds apart, with the outermost relay
- 3:07Speaker 1: set for zero point one second, adopting a maximum of
- 3:12Speaker 1: two point one seconds, as the longest time of fault
- 3:16Speaker 1: should remain on this system. We therefore find that five
- 3:19Speaker 1: sections is about the most that should be protected by
- 3:23Speaker 1: selective timing alone. Although some systems are operating satisfactorily with
- 3:29Speaker 1: relays set zero point three or zero point four seconds apart,
- 3:33Speaker 1: such systems achieve success only by extreme care in the
- 3:38Speaker 1: maintenance of the oil circuit breaker mechanism and careful adjustment
- 3:42Speaker 1: of relays in trip circuit mechanisms. Time intervals closer together
- 3:48Speaker 1: than zero point five second are not to be recommended
- 3:51Speaker 1: for average systems. The time of operation should be that
- 3:56Speaker 1: required when the relay is operating on the flat or
- 4:00Speaker 1: minimum time interval of the time current curve i e.
- 4:04Speaker 1: When the second current is five hundred percent or more
- 4:07Speaker 1: of the relay current tap setting time settings on loop
- 4:12Speaker 1: feeders for the simple loop system involving only one source
- 4:18Speaker 1: of power, the relay time settings are described in the
- 4:22Speaker 1: paragraph on time settings on radio feeders. The loop is
- 4:27Speaker 1: opened at one of the generating station breakers and the
- 4:30Speaker 1: relays on the outgoing sides of the substations set for
- 4:34Speaker 1: successively higher times of operation from the outermost substation. Considering
- 4:41Speaker 1: the feeder as straight radio to the generating station. The
- 4:46Speaker 1: loop is then closed up and the other generating station
- 4:50Speaker 1: breaker opened. The time settings on the remaining relays being
- 4:54Speaker 1: determined is already outlined. Starting on the loop at any
- 4:59Speaker 1: point and approaching the generating station, it will then be
- 5:04Speaker 1: observed that the relays set to trip for power flowing
- 5:08Speaker 1: from the generating station will be set for increasingly longer
- 5:13Speaker 1: times of operation, whereas the relays set to trip for
- 5:17Speaker 1: power flowing towards the generating station will be set for
- 5:21Speaker 1: increasingly shorter times of operation. The loop system, which receives
- 5:28Speaker 1: power at two or more points in the ring, is
- 5:31Speaker 1: especially difficult to relay. If the various substation relays are
- 5:37Speaker 1: timed for one source of power, as outlined in the
- 5:41Speaker 1: preceding paragraph, the timing is wrong when considering the other
- 5:46Speaker 1: source or sources of power. Parallel lines between any two
- 5:51Speaker 1: points can of course use some form of balanced protection
- 5:56Speaker 1: for parallel operation, but this is not a place likable
- 6:00Speaker 1: when the lines are operating singly. In applying a series
- 6:05Speaker 1: of time settings to such a system, it is generally
- 6:09Speaker 1: necessary to consider both the amountain source of short circuit
- 6:14Speaker 1: current available. Selection usually can be obtained by working on
- 6:19Speaker 1: the inverse portion of the time current curve of the relay.
- 6:24Speaker 1: Parallel feeders protected by type CD relays four lines protected
- 6:31Speaker 1: by Type CD relays, It is usual to set the
- 6:35Speaker 1: relay to operate on a differential current of three ampers.
- 6:40Speaker 1: For through short circuits, the current in the two equal
- 6:44Speaker 1: lines will be balanced so that there will be a
- 6:47Speaker 1: very slight amount of differential current tending to trip the relays.
- 6:52Speaker 1: For the somewhat infrequent case where type CD relays protect
- 6:57Speaker 1: two parallel lines of unequal impedance, but equipped with current
- 7:01Speaker 1: transformers of the same ratio type, a current balance auto
- 7:06Speaker 1: transformers should be used to make equal the currents flowing
- 7:10Speaker 1: through the relay windings. The time setting is generally on
- 7:14Speaker 1: the order of zero point one or zero point two
- 7:18Speaker 1: second settings for ground relays. Ground relays are set the
- 7:25Speaker 1: same as line relays, except that ground current flow differs
- 7:30Speaker 1: in magnitude from the current flow for a line to
- 7:34Speaker 1: line short circuit. End of Chapter six