- 0:00Speaker 1: Chapter three, Part two of Silent Sentinels by Westinghouse Electric
- 0:05Speaker 1: and Manufacturing Company. This LibriVox recording is in the public domain.
- 0:12Speaker 1: Section three Methods of clearing ground faults solidly in low
- 0:18Speaker 1: resistance grounded neutral systems. These systems, when protected by types CO,
- 0:24Speaker 1: CR and CD relays, require no additional relays. For wired
- 0:28Speaker 1: to ground faults, three current transformers and three relays are
- 0:32Speaker 1: necessary for the complete protection of each circuit breaker. However,
- 0:36Speaker 1: where type CZ impedance relays are used in order to
- 0:39Speaker 1: obtain the minimum time for clearing faults, two sets of
- 0:42Speaker 1: impedance elements are required for phase to phase and phase
- 0:45Speaker 1: to ground faults. The reason for this is that a
- 0:48Speaker 1: ground fault on one wire results in fifty seven point
- 0:51Speaker 1: seven percent voltage being maintained across two sides of the
- 0:54Speaker 1: voltage triangle and one hundred percent voltage across the third side.
- 0:58Speaker 1: The voltage between the grounded wires and neutral is, of
- 1:01Speaker 1: course zero or nearly so. If only three elements having
- 1:06Speaker 1: their directional element potential coils connected in STAR are used,
- 1:10Speaker 1: a wired to wire short circuit will reduce the voltage
- 1:13Speaker 1: across each relay coil from fifty seven point seven per
- 1:16Speaker 1: cent of the line voltage to twenty eight point eight
- 1:18Speaker 1: percent line voltage, so that each relay still has fifty
- 1:22Speaker 1: percent normal voltage impressed across it. With fifty percent normal
- 1:26Speaker 1: voltage acting on the potential coil of the CZ relay,
- 1:29Speaker 1: The time required to close the contacts is entirely too
- 1:32Speaker 1: long for satisfactory operation, and two sets of elements must
- 1:36Speaker 1: be employed for complete protection, medium resistance, grounded neutral systems.
- 1:44Speaker 1: Relay equipment, and additional to that required for line short circuits,
- 1:48Speaker 1: is required to care for phase to ground failures. For
- 1:51Speaker 1: those installations where the magnitude of the ground current in
- 1:55Speaker 1: the circuit and the ratios of the current transformers are
- 1:58Speaker 1: such as to produce a single phase curve cur of
- 2:00Speaker 1: at least two ampers in the secondary of one current
- 2:02Speaker 1: transformer for a fault from that wired to ground, a
- 2:06Speaker 1: type co relay having a low current winding is inserted
- 2:09Speaker 1: in the neutral connection between the neutral point of the
- 2:12Speaker 1: line relays and the neutral point of the current transformer secondaries.
- 2:16Speaker 1: The low current type COO relay has taps for operation
- 2:19Speaker 1: at zero point five, zero point six, zero point eight,
- 2:23Speaker 1: one point zero, one point five, two point zero, and
- 2:27Speaker 1: two point five ampers. It can generally be operated on
- 2:31Speaker 1: the zero point five amper tap without danger of tripping improperly.
- 2:35Speaker 1: As under normal operation, there is no current flowing in
- 2:37Speaker 1: the neutral connection. Fig. Forty one shows the connections for
- 2:41Speaker 1: the ground relay. When the circuit breaker is controlled by
- 2:44Speaker 1: type CO over current relays, it will be observed that
- 2:48Speaker 1: the tripping contacts of the ground relay parallel to the
- 2:50Speaker 1: tripping contacts of the line relays. The same scheme of
- 2:54Speaker 1: current and tripping connections is employed when non directional single
- 2:57Speaker 1: impedance element type CZ impedance relay are used to protect
- 3:01Speaker 1: the feeder against line faults. When the circuit breaker is
- 3:05Speaker 1: controlled by type CR directional overcurrent or type CZ single
- 3:09Speaker 1: impedance element relays for phase to phase faults, the low
- 3:13Speaker 1: current relay is inserted in the neutral circuit. For ground
- 3:16Speaker 1: fault protection. The tripping contacts do not, however, go directly
- 3:21Speaker 1: to the circuit breaker trip coil, but are connected in
- 3:23Speaker 1: series with the directional contacts of the line relays. To
- 3:27Speaker 1: secure proper directional indication on ground faults as well as
- 3:30Speaker 1: line faults, a tap must therefore be provided on the
- 3:34Speaker 1: line relays between the directional element contacts and the overcurrent
- 3:38Speaker 1: or impedance element contacts. Fig. Forty two shows the connections
- 3:43Speaker 1: using three type CR line relays and one type CO
- 3:46Speaker 1: low energy ground relay. The same tripping circuit connections hold
- 3:50Speaker 1: when Type CZ impedance relays are used for line faults.
- 3:55Speaker 1: This arrangement should be used with care. It has been
- 3:58Speaker 1: found that a high resistance at the point point where
- 4:00Speaker 1: an accidental ground occurs will limit the current to such
- 4:03Speaker 1: a small value that the load current flowing through the
- 4:05Speaker 1: CR relays will be greater than the ground current and
- 4:08Speaker 1: the CR relays will not operate in the proper direction.
- 4:12Speaker 1: A low current Type CD selective differential current relay is
- 4:15Speaker 1: available for ground protection at those locations protected against line
- 4:19Speaker 1: faults by type CD relays. Each winding is provided with
- 4:24Speaker 1: taps for zero point five, zero point six, one point
- 4:27Speaker 1: two and two point zero ampers operating current. One winding
- 4:31Speaker 1: is connected in each neutral connection of the balance pair
- 4:34Speaker 1: of lines. Fig. Forty three shows the complete connections for
- 4:38Speaker 1: line and ground protection on two balanced lines for both
- 4:41Speaker 1: balanced and single line operation. High resistance grounded neutral system
- 4:49Speaker 1: protection against wired to ground faults on high resistance grounded
- 4:52Speaker 1: neutral systems cannot be readily provided in less the magnitude
- 4:56Speaker 1: of the ground current in the circuit and the ratio
- 4:58Speaker 1: of the current transformers are such says to provide one
- 5:01Speaker 1: and a half to two ampers in the secondary of
- 5:03Speaker 1: one current transformer with a ground fault on that wire.
- 5:07Speaker 1: Since the ground current is less than the load current
- 5:10Speaker 1: in the circuit to be protected, a directional element which
- 5:13Speaker 1: shall be independent of load is required. Fig. Forty four
- 5:17Speaker 1: shows complete line and ground protection for two parallel lines
- 5:21Speaker 1: on a high resistance grounded neutral system. The line potential
- 5:25Speaker 1: transformers are connected star star with the star points grounded.
- 5:29Speaker 1: The line relay potential coils are energized by the delta
- 5:32Speaker 1: voltages of this bank. If the potential transformers are chosen
- 5:37Speaker 1: as to give one hundred and fifteen volt single phase
- 5:39Speaker 1: secondary when energized by a single phase voltage of line
- 5:42Speaker 1: to line value, the line relay should be provided with
- 5:45Speaker 1: one hundred and twenty five vault potential coils. The secondaries
- 5:49Speaker 1: of the line potential transformers also energize an auxiliary bank
- 5:53Speaker 1: of three two hundred to one hundred voult potential transformers
- 5:56Speaker 1: connected star on the primary side. The star point being
- 5:59Speaker 1: can acted to the two star points to the line
- 6:01Speaker 1: potential transformers. The secondaries of the auxiliary bank of transformers
- 6:07Speaker 1: form a closed delta through the potential coil of the
- 6:10Speaker 1: ground relay. A low current low energy directional type CR
- 6:15Speaker 1: relay having the same current winding as the low current
- 6:18Speaker 1: type co previously mentioned, is required for ground protection. The
- 6:23Speaker 1: current coil of this relay is connected between the neutral
- 6:26Speaker 1: point of the current transformer secondaries and the neutral point
- 6:29Speaker 1: of the line relays. When a fault from one wire
- 6:33Speaker 1: to ground occurs, the distortion of the voltage triangle caused
- 6:36Speaker 1: by a current being fed to the ground fault by
- 6:38Speaker 1: the potential transformer develops sufficient voltage across the potential coil
- 6:42Speaker 1: of the directional relay to obtain in conjunction with the
- 6:46Speaker 1: residual current in the relay the proper directional indication. The
- 6:50Speaker 1: proper time of operation for the relay is secured by
- 6:53Speaker 1: an adjustment of the time index lever of the over
- 6:56Speaker 1: current element. When power transformer banks are can connected star
- 7:00Speaker 1: delta and the star point is grounded through a resistor,
- 7:04Speaker 1: the potential for the directional ground relays can be secured
- 7:07Speaker 1: by connecting the primary of a two hundred to one
- 7:09Speaker 1: hundred volt potential transformer between ground and a point on
- 7:13Speaker 1: the resistor which is two hundred volts above ground. When
- 7:17Speaker 1: carrying the maximum ground current. The secondary of the potential
- 7:20Speaker 1: transformer energizes the potential coil of the relay. Section four.
- 7:28Speaker 1: Calculation of short circuit current. In applying any protective scheme,
- 7:33Speaker 1: it is necessary to determine the short circuit currents which
- 7:35Speaker 1: may develop under all conditions. It is unfortunate that the
- 7:39Speaker 1: term overload has ever come into use in connection with
- 7:42Speaker 1: sectionalizing distribution systems, because it implies that the relays should
- 7:47Speaker 1: be set to operate at a value determined by the
- 7:49Speaker 1: normal load on the feeder. Such a setting is possible
- 7:53Speaker 1: if definite time limit relays are used, but where a
- 7:56Speaker 1: relay having inverse time characteristics is used, is necessary to
- 8:00Speaker 1: consider the current that occurs during times of trouble, and
- 8:03Speaker 1: that may be tens or even hundreds of times greater
- 8:06Speaker 1: than the normal current. An approximate method of determining the
- 8:10Speaker 1: possible short circuit current is to observe the voltage drop
- 8:13Speaker 1: between two stations at normal load. Short circuit current equals
- 8:17Speaker 1: normal voltage divided by voltage drop times load current. For example,
- 8:23Speaker 1: if a certain load current causes a drop of five
- 8:26Speaker 1: percent in voltage between the generating station and the substation,
- 8:30Speaker 1: the maximum short circuit current would be twenty times the
- 8:32Speaker 1: load current. Results obtained in this way are likely to
- 8:36Speaker 1: be too large, particularly in lines having high inductance. In
- 8:41Speaker 1: order to determine more accurately the RMS current, an analysis
- 8:45Speaker 1: of short circuit phenomena on an alternating current network is necessary,
- 8:49Speaker 1: and it may be desirable to call attention to some
- 8:51Speaker 1: of the conditions under which relays may be called upon
- 8:54Speaker 1: to function. A short circuit is a transient condition, and
- 8:59Speaker 1: this current at any point in an electrical system is
- 9:01Speaker 1: a variable depending on the resistance, inductance, electrostatic capacity, magnetic capacity,
- 9:08Speaker 1: point on the voltage wave at which the disturbance takes place,
- 9:12Speaker 1: and current conditions of the circuit immediately preceding any change
- 9:15Speaker 1: in the steady condition of that circuit. It represents a
- 9:18Speaker 1: readjustment of the stored electromagnetic and electrostatic energy in the
- 9:22Speaker 1: system from an initial steady state condition until a final
- 9:26Speaker 1: steady condition is reached. It is manifested during every change
- 9:30Speaker 1: in the condition of the circuit, although its effects on
- 9:33Speaker 1: the circuit are usually not appreciable under certain conditions, such
- 9:38Speaker 1: as short circuits. The effects of the transient current, however,
- 9:41Speaker 1: are of prime importance. Short circuiting a system at any
- 9:45Speaker 1: point immediately causes an abnormal current rush to occur on
- 9:48Speaker 1: that system. During the first complete cycle following the short circuit,
- 9:53Speaker 1: the current usually rises to maximum value. If now the
- 9:58Speaker 1: generator field circuit is assumed to remain unchanged by automatic
- 10:01Speaker 1: generator voltage regulators or similar devices than during succeeding cycles,
- 10:07Speaker 1: the current will rise to lesser and lesser values until
- 10:10Speaker 1: a steady condition again exists on the system. The current
- 10:14Speaker 1: wave during the transient period, as shown by assilograms, may
- 10:18Speaker 1: be symmetrical or asymmetrical with respect to the line representing
- 10:22Speaker 1: zero current, depending on the point on the voltage pressure
- 10:26Speaker 1: wave at which the short circuit occurred. The transient current
- 10:30Speaker 1: is said to be symmetrical when the assumed line connecting
- 10:34Speaker 1: points on the current wave midway between the peaks coincides
- 10:37Speaker 1: with the line of zero current. Similarly, a transient current
- 10:41Speaker 1: is said to be symmetrical when the assumed line connecting
- 10:45Speaker 1: points on the current wave midway between the peaks does
- 10:48Speaker 1: not coincide with the line of the zero current. The
- 10:52Speaker 1: value of the current at any point on the current
- 10:54Speaker 1: wave during the transient condition, if referred to the line
- 10:57Speaker 1: representing zero current, is a measure of the effects produced
- 11:01Speaker 1: by the current at that point. Some of these effects
- 11:04Speaker 1: are indicated by the breaking of insulators supporting buses, the
- 11:07Speaker 1: displacing of windings of transformers and generators, the distortion of
- 11:12Speaker 1: oil circuit breaker connections, and the fusing of conductors. In
- 11:15Speaker 1: various parts of electrical systems, the value of the current
- 11:20Speaker 1: at any point on the current wave during the transient
- 11:22Speaker 1: condition is frequently referred to an assumed zero line between
- 11:26Speaker 1: the peaks. This values used to calculate the electrical constants
- 11:29Speaker 1: of a circuit, such as impedance, reactants, etc. The maximum
- 11:34Speaker 1: asymmetrical value of a transient current in RMS ampers during
- 11:38Speaker 1: a short circuit on an ordinary alternating current generator is
- 11:42Speaker 1: approximately equal to one point eight times the generated voltage
- 11:45Speaker 1: pressure of the generator in volts immediately preceding the short circuit,
- 11:50Speaker 1: divided by the impedance of the circuit in omes between
- 11:53Speaker 1: the point of power supply and the point of short circuit.
- 11:56Speaker 1: The maximum symmetrical value of the transient current is a
- 11:59Speaker 1: proximately equal to zero point five to five times the
- 12:02Speaker 1: maximum asymmetrical value. The transient of an electrical system at
- 12:08Speaker 1: a point remote from the source of power supply will
- 12:10Speaker 1: be different from that at the terminals of an alternating
- 12:13Speaker 1: current generator. Its amplitude and duration will depend upon the
- 12:17Speaker 1: electrical constants of the system and the distance between the
- 12:20Speaker 1: point of short circuit and the source of power supply.
- 12:24Speaker 1: In general, the greater the distance between the source of
- 12:26Speaker 1: power and the point of short circuit, the less the
- 12:29Speaker 1: amplitude of the transient, and the shorter its duration. Automatic
- 12:34Speaker 1: generator voltage regulators introduce system transients differing from those which
- 12:38Speaker 1: occur in systems not so equipped. They tend to maintain
- 12:41Speaker 1: constant the system pressure, but on account of the inherent
- 12:44Speaker 1: time lag of the iron portions of the generator and
- 12:48Speaker 1: exciter armatures and fields, their effect is not felt immediately.
- 12:52Speaker 1: The effect of automatic voltage regulators on system transience may
- 12:56Speaker 1: be predicted for any known set of conditions, and account
- 12:59Speaker 1: taken as such effects in the application of relays. Fig.
- 13:03Speaker 1: Forty five is a typical acilogram showing the current flowing
- 13:07Speaker 1: in one phase of the external circuit when a system
- 13:10Speaker 1: is short circuited under ordinary operating conditions. In this diagram,
- 13:15Speaker 1: O is the origin of the coordinates and is taken
- 13:18Speaker 1: at the instant at which the short circuit occurs. Ox
- 13:22Speaker 1: is the axis of absissa, and the absissa represent time.
- 13:27Speaker 1: O Y is the axis of ordinates and the ordinance
- 13:30Speaker 1: represent current. CD is a curve passing through the maxima
- 13:34Speaker 1: of the wave of total current, and EF is a
- 13:37Speaker 1: current passing through the minima. AB is a curve which
- 13:41Speaker 1: cuts the vertical everywhere midway between CD and EF. The
- 13:47Speaker 1: wave of total current, which the crests lie along curve
- 13:50Speaker 1: CD and EF, and of which ordinates are measured from
- 13:54Speaker 1: the axis OX, may be regarded as having two components,
- 13:58Speaker 1: namely one a direct component, two an alternating component. The
- 14:05Speaker 1: direct component is represented at any time by the ordinate
- 14:08Speaker 1: to the curve AB, or at the time X by
- 14:12Speaker 1: the coordinate GH. The alternating component is a wave whose
- 14:16Speaker 1: cress value at any time is the difference between the
- 14:20Speaker 1: ordinance to the curve CD and AB. This difference at
- 14:24Speaker 1: the time X has the value HJ. The RMS values
- 14:29Speaker 1: of this alternating component are shown on curve st At
- 14:33Speaker 1: any instant, this component is considered to have the same
- 14:36Speaker 1: RMS value as an alternating wave of constant amplitude whose
- 14:41Speaker 1: CRESS value is represented by one half the distance between
- 14:44Speaker 1: curve CD and EF at that instant. The RMS value
- 14:49Speaker 1: of the total current wave under short circuit at any
- 14:52Speaker 1: instant is the square root of the sum of the
- 14:54Speaker 1: squares of the value of the direct component and the
- 14:57Speaker 1: effective value of the alternating component at that instant. The
- 15:01Speaker 1: correct application of relays to an electrical system requires that
- 15:04Speaker 1: certain characteristics of the system be known or assumed. These
- 15:08Speaker 1: system characteristics are one normal voltage, two maximum current carried
- 15:15Speaker 1: by the circuit in which the relay is connected, three
- 15:20Speaker 1: normal frequency section, four maximum CAVIA capacity of synchronous apparatus, transformers, reactors,
- 15:28Speaker 1: and lines. Five transind current characteristics during short circuit or overload.
- 15:35Speaker 1: The RMS current at any point of a system under
- 15:38Speaker 1: short circuit conditions is affected by the following factors. One
- 15:43Speaker 1: the total CAVA, reactants and transient characteristics of the synchronous
- 15:48Speaker 1: machines connected to the system. Two number reactance, resistance, capacitance,
- 15:56Speaker 1: and arrangement of all circuits over which power can be
- 16:00Speaker 1: supplied to the point of short circuit. Three CAVA arrangement
- 16:06Speaker 1: resistance reactants and capacitance of all reactors and transformers through
- 16:11Speaker 1: which power can be supplied to the point of short circuit. Four,
- 16:16Speaker 1: contact resistance at the short circuit. Five, the nature of
- 16:20Speaker 1: the short circuit, whether single phase or polyphase. Six, the
- 16:26Speaker 1: CAVA and power factor of the load being carried at
- 16:28Speaker 1: the time of short circuit. Seven, the point of the
- 16:32Speaker 1: voltage pressure wave at which the short circuit was established.
- 16:38Speaker 1: Eight the use of automatic voltage regulators. The short circuit
- 16:43Speaker 1: transient for systems may be determined by tests, by calculation,
- 16:47Speaker 1: or less closely by assumption. Obviously, the determination by test
- 16:53Speaker 1: for all circuits of a large system is expensive and
- 16:56Speaker 1: involves considerable time and interruption to service. This will be
- 17:00Speaker 1: practical in but a few cases. The determination by calculation
- 17:04Speaker 1: is also a matter of considerable labour, but is feasible
- 17:08Speaker 1: if only the important factors listed above are considered practical.
- 17:12Speaker 1: Approximate selection sufficiently accurate for most cases can be made
- 17:17Speaker 1: by using only reactants and an accepted group of time.
- 17:20Speaker 1: Current decrement curves table IE gives decrement factors for three
- 17:25Speaker 1: phase short circuits. These factors are intended primarily for use
- 17:29Speaker 1: in relay application and setting where minimum short circuit values
- 17:33Speaker 1: are important. The effect of using RMS values instead of
- 17:37Speaker 1: peak values is to appreciably reduce the ratio between short
- 17:41Speaker 1: circuit and rated ampers. For example, assuming ten per cent
- 17:45Speaker 1: reactants and a short circuit current containing the maximum possible
- 17:49Speaker 1: direct component, the ratio of the peak value of the
- 17:53Speaker 1: first alternation of the short circuit current to the peak
- 17:56Speaker 1: value of rated current is roughly twenty. Under the same condition,
- 18:00Speaker 1: the ratio of the RMS value of the first alternation
- 18:03Speaker 1: of the short circuit current to the RMS value of
- 18:06Speaker 1: the sinusoidal rated current is roughly seventeen. The effect of
- 18:12Speaker 1: using the flux at rated voltage and the assumed load
- 18:15Speaker 1: instead of at rated voltage and no load is to
- 18:18Speaker 1: increase the short circuit current by a somewhat lower percentage
- 18:21Speaker 1: than the alternator reactance percentage. This effect in alternating current
- 18:26Speaker 1: generators of low reactants is relatively unimportant, but becomes of
- 18:30Speaker 1: increasing importance as the generator reactants increases. The characteristic shapes
- 18:36Speaker 1: of the time current decrement curves have been reached by
- 18:39Speaker 1: analysis of generator tests, including a celigraph studies of short
- 18:43Speaker 1: circuits occurring when the generators were excited to full voltage
- 18:46Speaker 1: and were carrying various loads at various power factors. In
- 18:51Speaker 1: the curse or total reactancies up to including fifteen percent,
- 18:55Speaker 1: the reactance is assumed to be wholly within the alternating
- 18:57Speaker 1: current generators, and for higher values of reactants, the generators
- 19:03Speaker 1: were taken at fifteen percent, and due allowance was made
- 19:06Speaker 1: by calculation for the effect of the external reactancies. In
- 19:10Speaker 1: the latter case, if alternating current generators of the other
- 19:14Speaker 1: reactants had been used, the results would have been somewhat different,
- 19:17Speaker 1: but the error is not large enough to be of
- 19:19Speaker 1: practical importance. The final values of current ie the sustained
- 19:25Speaker 1: short circuit current have been assumed in accordance with experience
- 19:28Speaker 1: and tests, and are based on the behavior of machines
- 19:32Speaker 1: of predominating design. The study of representative assilograms of short
- 19:36Speaker 1: circuit tests showed that in most cases, the direct component
- 19:40Speaker 1: disappeared within zero point five second and that the transient
- 19:43Speaker 1: portion of the alternating component disappeared within three seconds. These
- 19:48Speaker 1: time values have therefore been used in constructing the characteristic
- 19:51Speaker 1: decrement curves. Several alternating current generators with the same reactants
- 19:57Speaker 1: and synchronous impedance will not necessarily they have the same
- 20:00Speaker 1: rate of RMS current decay. This has been considered in
- 20:04Speaker 1: constructing the characteristic curves, and the decrement curves may therefore
- 20:08Speaker 1: safely be taken as representing the greatest RMS current that
- 20:12Speaker 1: will be given by modern alternating current generators of normal design.
- 20:18Speaker 1: The percentage reactance in any leg of a circuit is
- 20:21Speaker 1: a reactance drop in that leg of the circuit at
- 20:23Speaker 1: normal rated current, expressed as a percent of the voltage
- 20:26Speaker 1: to neutral of that circuit. For single and two phase systems,
- 20:31Speaker 1: this is the voltage between phase wires divided by two.
- 20:34Speaker 1: For three phase systems, this is the voltage between phase
- 20:37Speaker 1: wires divided by one point seventy three. The percentage values
- 20:41Speaker 1: in Table I are initial values based on a symmetrical
- 20:44Speaker 1: sin wave and on the maximum rating of the machines
- 20:47Speaker 1: connected to the bus. The percentage of reactants of generators
- 20:52Speaker 1: varies from about eight percent to thirty percent. The percentage
- 20:56Speaker 1: reactance of transformers varies from about three percent to fifteen percent.
- 21:02Speaker 1: Nature of short circuits. When making current calculations, it should
- 21:06Speaker 1: always be assumed that a short circuit is due to
- 21:09Speaker 1: a metallic connection between the conductors In a high voltage
- 21:13Speaker 1: aerial line using wooden pins and cross arms. It sometimes
- 21:16Speaker 1: happens that an insulator is broken, with the result that
- 21:19Speaker 1: the wood is gradually heated by the passage of the
- 21:21Speaker 1: current through it, until it finally bursts into flame, thus
- 21:25Speaker 1: causing an arc between conductors. A little consideration shows that
- 21:29Speaker 1: the flow of current is small until the arc is established,
- 21:33Speaker 1: and that it is wrong to speak of automatically disconnecting
- 21:35Speaker 1: a section of line which has such a high resistance
- 21:38Speaker 1: short circuit. It has sometimes been assumed that an arc
- 21:42Speaker 1: has a high resistance, but this is not the case,
- 21:45Speaker 1: and in general the presence of an arc at the
- 21:47Speaker 1: point of short circuit will not decrease the short circuit
- 21:50Speaker 1: current by more than a few percent. Incidentally, it may
- 21:54Speaker 1: be of interest to note that on a high voltage
- 21:56Speaker 1: ungrounded neutral system, the capacity current to ground through an
- 22:00Speaker 1: arc is greater than it is through a direct ground.
- 22:05Speaker 1: There is only one case where a short circuit is
- 22:08Speaker 1: likely to increase in intensity as it develops, and that
- 22:11Speaker 1: is on a system where the neutral is grounded through
- 22:13Speaker 1: a resistance A cable breakdown, for instance, frequently occurs first
- 22:18Speaker 1: between one conductor and the sheath, and the current flow
- 22:21Speaker 1: may be limited by the neutral resistance. The trouble will
- 22:24Speaker 1: quickly involve all the conductors in the cable, resulting in
- 22:27Speaker 1: a heavy short circuit, but it is possible that it
- 22:30Speaker 1: will require an appreciable time to do this, in which
- 22:33Speaker 1: case the relay operation may be unsatisfactory. This is particularly
- 22:37Speaker 1: liable to happen if the neutral is not grounded at
- 22:40Speaker 1: every substation. Section five. The protection of AC apparatus overload protection.
- 22:51Speaker 1: Overload protection of the larger type of electrical apparatus, as
- 22:55Speaker 1: a general rule, receives little special attention inasmuch as the
- 22:58Speaker 1: relays provided for short circuit protection serve also for overload
- 23:02Speaker 1: protection of the apparatus of the system in addition to this,
- 23:06Speaker 1: in generating. In substations where there are operators in attendance,
- 23:09Speaker 1: the load on the apparatus is usually under their supervision
- 23:12Speaker 1: and is governed by them accordingly, except in cases of
- 23:15Speaker 1: short circuit trouble on the system. In small installations where
- 23:19Speaker 1: some scheme of overcurrent protection is necessary, the CO overcurrent
- 23:23Speaker 1: relay or CW overpower relay can generally be used to
- 23:27Speaker 1: give satisfactory protection protection against internal faults. Protection against internal
- 23:36Speaker 1: faults in the windings of electrical apparatus is receiving much attention.
- 23:40Speaker 1: In present day practice, these internal faults might be roughly
- 23:44Speaker 1: classified as phase to phase short circuits, short circuited turns,
- 23:48Speaker 1: open circuits, and grounds. Experience has shown that most of
- 23:52Speaker 1: the internal faults developed in larger types of rotating electrical
- 23:55Speaker 1: apparatus develop originally as a ground from the phase windings
- 23:59Speaker 1: to the frame. If the neutral is not grounded, a
- 24:02Speaker 1: fault of this sort will not unbalance the phase current,
- 24:05Speaker 1: and it is therefore rather difficult to locate until it
- 24:08Speaker 1: is developed into a phase to phase short circuit. Thus,
- 24:12Speaker 1: from the consideration of protection, it is best, wherever possible
- 24:17Speaker 1: to have the neutral grounded. Grounds are more likely to
- 24:19Speaker 1: occur near the line end rather than the neutral end
- 24:22Speaker 1: of a winding, but in the event of the latter,
- 24:25Speaker 1: the current which flows may be relatively small, especially if
- 24:28Speaker 1: a high resistance ground is used. The fact that the
- 24:31Speaker 1: fault current is often very small at the beginning, and
- 24:34Speaker 1: that it is highly desirable to detect such a fault
- 24:37Speaker 1: and disconnect the apparatus from the line before a phase
- 24:39Speaker 1: to phase short circuit can develop, makes the protection of
- 24:43Speaker 1: apparatus against internal faults rather a difficult problem. A differential
- 24:48Speaker 1: scheme of protection, making use of either standard over current
- 24:52Speaker 1: relays or special over current relays operating on very small current,
- 24:56Speaker 1: is the most general scheme for protection against internal faults.
- 25:00Speaker 1: This form of protection consists of balancing the current entering
- 25:03Speaker 1: the apparatus against the current flowing from it. This scheme
- 25:07Speaker 1: of protection is usually accomplished by connecting a current transformer
- 25:11Speaker 1: at each end of each phase winding, connecting their secondaries
- 25:14Speaker 1: in series, and then connecting a current relay across these secondaries.
- 25:19Speaker 1: As long as the secondary currents are equal, no current
- 25:22Speaker 1: will flow through the relay windings. Any leakage of current, however,
- 25:28Speaker 1: to other phases or to ground, will upset this balance
- 25:31Speaker 1: and send current through the relay. The relay, in turn
- 25:34Speaker 1: operates to trip the circuit breaker and disconnect the faulty apparatus.
- 25:39Speaker 1: The principle of operation used in this scheme allows relatively
- 25:42Speaker 1: low current settings on the over current relays because obviously
- 25:46Speaker 1: no current will flow under normal conditions. It is also
- 25:50Speaker 1: free from trouble due to circulating current when synchronizing or
- 25:53Speaker 1: switching on any part of the system is taking place,
- 25:56Speaker 1: inasmuch as such current should be balanced in each phase.
- 26:00Speaker 1: This scheme is very flexible in its application and might
- 26:03Speaker 1: be applied to machines of any size either star or
- 26:06Speaker 1: delta connection, provided that both ends of each phase winding
- 26:09Speaker 1: are capable of being brought out and connected to current transformers.
- 26:14Speaker 1: No definite rule can be set down in regard to
- 26:17Speaker 1: the size of apparatus to which relay protective scheme should
- 26:20Speaker 1: be applied. It is largely a question to be decided
- 26:23Speaker 1: from a consideration of the importance of limiting the amount
- 26:26Speaker 1: of damage that can be done to the machine. In
- 26:28Speaker 1: other words, it resolves into an economic consideration in which
- 26:32Speaker 1: the cost of relay protection must be balanced against the
- 26:35Speaker 1: value of service rendered and then compared with the cost
- 26:38Speaker 1: of possible damage to the apparatus. In the case of
- 26:42Speaker 1: large generators and sometimes motors, where the neutral is grounded
- 26:46Speaker 1: directly or through resistance, and the faulty currents may or
- 26:49Speaker 1: may not be of any great value, a relay sensitive
- 26:52Speaker 1: to very small current is required. The low energy COO
- 26:57Speaker 1: relay is especially adapted for the differential protection of such applications.
- 27:03Speaker 1: An improvement on this method has been made by designing
- 27:05Speaker 1: a relay the type CAA that trips on a percentage
- 27:09Speaker 1: of the line current rather than on a given value
- 27:11Speaker 1: of current. This makes it possible to get more sensitive
- 27:14Speaker 1: protection without danger of having the relay operate due to
- 27:17Speaker 1: the circulating currents which usually occur at times of through
- 27:20Speaker 1: short circuits. In the differential protection of transformers, highly sensitive
- 27:26Speaker 1: settings are not so necessary and in many cases are undesirable,
- 27:30Speaker 1: as they would only serve to disconnect the transformers upon
- 27:33Speaker 1: some transient condition which accompanies a momentary unbalance but not
- 27:37Speaker 1: a fault. The standard over current co relay is therefore
- 27:42Speaker 1: applicable for the differential protection of transformers. A special form
- 27:48Speaker 1: of the type caa relay with taps provided so that
- 27:50Speaker 1: unequal currents can be balanced without the use of auto transformers,
- 27:54Speaker 1: has been developed for transformer protection. This tap arrangement, combined
- 27:58Speaker 1: with its adaptability to cases where circulating current appears under
- 28:02Speaker 1: transient conditions, makes it of particular value, especially when bushing
- 28:06Speaker 1: type transformers are to be used. Open or reverse phase protection.
- 28:13Speaker 1: In many installations of polyphase motors and rotary converters of
- 28:17Speaker 1: any size, it is becoming a common practice to provide
- 28:21Speaker 1: protection against running in case of an open phase or
- 28:24Speaker 1: in case of reversal phases. A reversal of two phases,
- 28:27Speaker 1: of course, reverses the direction of rotation of any motors
- 28:30Speaker 1: on the line, and so it is especially desirable to
- 28:33Speaker 1: have this condition protected against. In cases where a reversal
- 28:37Speaker 1: of the direction of rotation of any driving motors, such
- 28:40Speaker 1: as one in an elevator service, may be disastrous, the
- 28:44Speaker 1: CQ phase balance current relay gives ample protection against the
- 28:48Speaker 1: occurrence of such conditions on a system. Temperature protection of
- 28:53Speaker 1: windings inasmuch as the overheating of the windings and electrical
- 28:58Speaker 1: apparatus is closely realid to the overcurrent protection, the overcurrent
- 29:02Speaker 1: protection is often adequate to provide the necessary temperature protection.
- 29:07Speaker 1: In some cases, however, it is more desirable to furnish
- 29:10Speaker 1: protective apparatus which will include in its operation not only
- 29:14Speaker 1: the load on the apparatus, but also the existing temperature
- 29:17Speaker 1: of the windings. In other cases, the temperature of the
- 29:21Speaker 1: winding alone is taken as the determining factor in the
- 29:24Speaker 1: operation of a temperature protective scheme. In most of the
- 29:29Speaker 1: larger generating stations or substations, where constant supervision of the
- 29:33Speaker 1: operation of the various machines as possible, temperature indicating devices
- 29:37Speaker 1: are used to show the attendant when the temperature of
- 29:39Speaker 1: the windings in questions becomes such that some means should
- 29:42Speaker 1: be used to reduce it. Such indications are usually provided
- 29:46Speaker 1: by means of exploring coils embedded in the windings of
- 29:49Speaker 1: the apparatus, serving either to actuate a signal when the
- 29:52Speaker 1: temperature reaches some predetermined point or to operate some temperature
- 29:56Speaker 1: indicating instrument. Thus, when the critical degree of heat is indicated,
- 30:01Speaker 1: the operator may relieve the condition, either by reducing the
- 30:04Speaker 1: load on the apparatus or by increasing any existing cooling means,
- 30:08Speaker 1: such as the flow of air or water, as the
- 30:10Speaker 1: case may be oil filled thermal relays where manual supervision
- 30:17Speaker 1: is not possible, such as in automatic substation equipment and
- 30:21Speaker 1: in plants using numerous motors, it is necessary to have
- 30:24Speaker 1: temperature protection that will disconnect the apparatus when any predetermined
- 30:28Speaker 1: conditions exist. A common scheme for providing such protection is
- 30:32Speaker 1: to apply in a protective relay a heating element with
- 30:35Speaker 1: thermal characteristics similar to those of the machine. To be protected,
- 30:40Speaker 1: a current proportional to the load current in the apparatus
- 30:43Speaker 1: itself flows through the heating element of the relay. The
- 30:48Speaker 1: characteristics of this element are such that its temperature will
- 30:51Speaker 1: be approximately the same as that of the protected apparatus
- 30:54Speaker 1: under all loads and at all times. When the temperature
- 30:57Speaker 1: of this element reaches the critical points, it serves to
- 31:00Speaker 1: trip the apparatus offline. The Westinghouse BA and BD oil
- 31:05Speaker 1: filled thermal relays serve to provide this class of protection
- 31:10Speaker 1: type CT temperature relay. Another scheme used for the temperature
- 31:15Speaker 1: protection of windings is to have the protective apparatus depended
- 31:18Speaker 1: on the current flowing at any given time, and also
- 31:21Speaker 1: at the same time, on the temperature within the windings
- 31:24Speaker 1: of the apparatus to be protected. In such a scheme,
- 31:28Speaker 1: the temperature is usually determined by means of copper exploring
- 31:31Speaker 1: coils buried in the windings and connected in some sort
- 31:34Speaker 1: of bridge arrangement, so that the change in resistance of
- 31:37Speaker 1: the exploring coils due to any change in the temperature
- 31:40Speaker 1: of the windings will give the proper temperature indication to
- 31:43Speaker 1: the protective relay by using the change in the resistance
- 31:46Speaker 1: values to cause a flow of current. In addition to this,
- 31:50Speaker 1: a current proportional to the current flowing in the apparatus
- 31:54Speaker 1: flows through another winding of the relay, and thus the
- 31:57Speaker 1: following three conditions are necessary before the apparatus is disconnected
- 32:00Speaker 1: from the source of power. First, the temperature of the
- 32:04Speaker 1: windings of the apparatus must be above the value for
- 32:07Speaker 1: which the relay is set to operate. Second, the current
- 32:11Speaker 1: flowing in the apparatus must be above the normal value,
- 32:14Speaker 1: and third, these two conditions must have existed for a
- 32:18Speaker 1: given period of time. Thus, the liability of the machines
- 32:22Speaker 1: being disconnected upon the occurrence of a transient overload is
- 32:25Speaker 1: guarded against. The CT temperature relay provides such protection and
- 32:30Speaker 1: embodies the necessary characteristics to assure maximum continuity as service.
- 32:35Speaker 1: The simplest form of over temperature protection is that in
- 32:38Speaker 1: which the temperature of the surrounding material is alone used
- 32:41Speaker 1: as an indication of the temperature of the winding and
- 32:44Speaker 1: is taken as the determining factor in the operation of
- 32:47Speaker 1: any protective relays used. Such a scheme is used largely
- 32:51Speaker 1: in the protection of transformers, where the exploring coils, expansion bulbs,
- 32:56Speaker 1: or whatever means are used for measuring the temperature of
- 32:59Speaker 1: the surrounding material may be embedded between the coils of
- 33:02Speaker 1: the transformers in such a way that an approximate indication
- 33:05Speaker 1: of the temperature of the windings is secured. The HM
- 33:09Speaker 1: thermostat relay is sometimes used for this purpose. Temperature protection
- 33:14Speaker 1: of bearings. In the case of rotating machinery, it is
- 33:19Speaker 1: often necessary to provide some scheme of protection whereby any
- 33:22Speaker 1: overheating in the bearings will either cause a signal to
- 33:25Speaker 1: operate or else cause the machine to be disconnected entirely.
- 33:29Speaker 1: Where actual supervision is possible, such protection may provide only
- 33:33Speaker 1: for the operation of a signal to call the attendant's
- 33:36Speaker 1: attention to the fact that all is not well with
- 33:38Speaker 1: this machinery. In cases such as automatic substations, it is
- 33:43Speaker 1: usually necessary to have the protective apparatus disconnect the machine entirely,
- 33:47Speaker 1: either shutting down the station or else disconnecting the individual
- 33:51Speaker 1: piece of apparatus. The HM thermostat relay is used largely
- 33:55Speaker 1: for this application. End of Chapter three, Parts two