- 0:00Speaker 1: Chapter three, Part one of Silent Sentinels by Westinghouse Electric
- 0:06Speaker 1: and Manufacturing Company. This LibriVox recording is in the public domain.
- 0:13Speaker 1: Alternating current Systems, Section one General theories of line troubles.
- 0:22Speaker 1: Alternating current systems suffer from more severe short circuits than
- 0:25Speaker 1: do direct current systems, primarily because of their better inherent
- 0:29Speaker 1: regulation and often because of the greater power concentration. Modern
- 0:33Speaker 1: polyphase systems have become so large and complicated that they
- 0:37Speaker 1: present many difficult problems due to the various unbalanced faults
- 0:40Speaker 1: which can occur. Alternating current transmission systems may be divided
- 0:45Speaker 1: into two general classes, first those having the neutral insulated
- 0:50Speaker 1: from ground, second those having the neutral connected to ground metallically.
- 0:56Speaker 1: The second classification may be further subdivided into four groups,
- 1:00Speaker 1: known respectively as solidly grounded neutral systems, low resistance grounded
- 1:05Speaker 1: neutral systems, medium resistance grounded neutral systems, and high resistance
- 1:09Speaker 1: grounded neutral systems. The solidly grounded neutral system is one
- 1:14Speaker 1: having its connected metallically to ground without any limiting resistance
- 1:18Speaker 1: in the circuit. The terms low resistance, medium resistance, and
- 1:23Speaker 1: high resistance refer to the relative values of limiting resistance
- 1:27Speaker 1: inserted in the neutral connection between the neutral point of
- 1:30Speaker 1: the system and ground, and are dependent on the neutral
- 1:33Speaker 1: voltage of the system under consideration. As a general rule,
- 1:37Speaker 1: a system may be considered as low resistance grounded neutral
- 1:40Speaker 1: if the grounding resistor is of such a value as
- 1:42Speaker 1: to produce in any circuit for a fault to ground
- 1:45Speaker 1: a current which, under minimum generating capacity conditions is at
- 1:49Speaker 1: least four times the line relay current setting. A medium
- 1:53Speaker 1: resistance grounded neutral system has a grounding resistor of such
- 1:56Speaker 1: a value as to limit the current for a fault
- 1:59Speaker 1: to ground to less than four times the current setting
- 2:03Speaker 1: as to limit the current for a fault to ground
- 2:05Speaker 1: to less than four times the current setting for the
- 2:08Speaker 1: line relays of that circuit. This fault current will, still, however,
- 2:12Speaker 1: be greater than the maximum load current over the feeder,
- 2:16Speaker 1: even under abnormal operating conditions. A high resistance grounded neutral
- 2:21Speaker 1: system has its grounding resistor of such a value that
- 2:24Speaker 1: the current for a fault to ground is on the
- 2:26Speaker 1: order of full load current of the grounding transformer. Bank
- 2:29Speaker 1: or less. Protection for faults from wires to ground may
- 2:33Speaker 1: or may not be possible, depending on certain local conditions,
- 2:36Speaker 1: which will be discussed under methods of clearing ground faults
- 2:41Speaker 1: Solidly grounded systems. Systems having their neutrals solidly grounded are
- 2:47Speaker 1: subject to short circuits between one wire and ground whenever
- 2:50Speaker 1: that wire becomes accidentally grounded. They can also suffer from
- 2:54Speaker 1: short circuits between only two wires of the system, as
- 2:57Speaker 1: well as between two wires and ground. In addition to
- 3:01Speaker 1: these unbalanced short circuits, such a system can suffer from
- 3:04Speaker 1: a balanced three phase short circuit. In considering a system
- 3:07Speaker 1: which has its neutral grounded, it is customary to assume
- 3:11Speaker 1: that the ground resistance between the neutral and the fault
- 3:13Speaker 1: is comparatively low, so that it does not decrease the
- 3:16Speaker 1: value of the short circuit current by any great amount. However,
- 3:21Speaker 1: in some localities the ground resistance may be high, but
- 3:24Speaker 1: such conditions are not of common occurrence. In calculating the
- 3:27Speaker 1: quantity of ground current likely to flow, it is important
- 3:30Speaker 1: to bear in mind that the impedance of the circuit
- 3:32Speaker 1: is high because of the great separation between the line
- 3:35Speaker 1: wire and the path through the ground unngrounded systems. On
- 3:42Speaker 1: systems having an isolated neutral, the three wire short circuit
- 3:46Speaker 1: and two wire short circuit are the same as on
- 3:48Speaker 1: grounded systems, but an accidental ground does not produce a
- 3:52Speaker 1: short circuit as it does in the solid the grounded system.
- 3:55Speaker 1: If the system is small, an accidental ground will make
- 3:58Speaker 1: little disturbance, or at least it will not cause any
- 4:01Speaker 1: abnormal value of current to flow. But if the system
- 4:04Speaker 1: is large in extent so that the electrostatic capacity between
- 4:07Speaker 1: conductors and ground is high, a noticeable charging current will
- 4:10Speaker 1: flow into the fault. On a large system, there is
- 4:13Speaker 1: always a charging current flowing in the conductors, but such
- 4:16Speaker 1: a charging current is normally balanced and is distributed throughout
- 4:19Speaker 1: the network. When an accidental ground occurs on one wire,
- 4:23Speaker 1: the potential between each of the other two conductors and
- 4:26Speaker 1: ground throughout the system is increased beyond its normal value
- 4:29Speaker 1: by the factor one point seventy three, and these wires
- 4:32Speaker 1: therefore require a greater charging current than that which they
- 4:35Speaker 1: normally carry. As shown in Fig. Ten, each of these
- 4:39Speaker 1: wires represents the plate of a condenser, the ground being
- 4:42Speaker 1: the other plate, and the wire leading to the fault
- 4:44Speaker 1: represents the connection between the source of potential and the
- 4:47Speaker 1: ground plate. Therefore, this grounded wire must carry all the
- 4:51Speaker 1: charging current for the two condensers. The value of this
- 4:55Speaker 1: current is difficult to calculate accurately, but an approximate value
- 4:58Speaker 1: can be very easily obtained, and it is about twice
- 5:01Speaker 1: the normal charging current of the system. The normal charging
- 5:05Speaker 1: current can be calculated from tables which take into account
- 5:07Speaker 1: the size and spacing of the conductors and the frequency
- 5:10Speaker 1: of the circuit. Reason for grounding through resistance. If an
- 5:17Speaker 1: unngrounded system is small with a consequently small charging current,
- 5:21Speaker 1: it is possible to operate the system when one of
- 5:23Speaker 1: the conductors is accidentally grounded, so that the necessity for
- 5:26Speaker 1: cutting out the disabled section is not urgent. Furthermore, most
- 5:30Speaker 1: grounds are usually of a temporary nature, such as a
- 5:33Speaker 1: flashover on an insulator, and they will clear themselves without damage.
- 5:38Speaker 1: If the system is large, these disturbances will become more frequent,
- 5:42Speaker 1: and the charging current will increase due to the greater
- 5:45Speaker 1: electrostatic capacity of the system, to such a value that
- 5:48Speaker 1: an arc over the insulator will not break, but will
- 5:50Speaker 1: continue until serious damage has been done and until the
- 5:54Speaker 1: line probably is burned down. Therefore, on large systems it
- 5:58Speaker 1: is necessary to provide some means of cutting out a
- 6:01Speaker 1: disabled section, and this usually requires some method of grounding
- 6:05Speaker 1: the neutral grounding is also necessary in order to relieve
- 6:09Speaker 1: strains on insulators, because, as has been shown, when one
- 6:12Speaker 1: line is accidentally grounded in an unngrounded system, the voltage
- 6:16Speaker 1: between the other two lines and the ground is increased
- 6:18Speaker 1: one point seventy three times. The solidly grounded neutral has
- 6:22Speaker 1: been considered, and it was shown that an accidental ground
- 6:25Speaker 1: on a conductor results in a short circuit. This causes
- 6:29Speaker 1: considerable disturbance, which is frequently so severe that some of
- 6:32Speaker 1: the load, particularly synchronous motors, will be forced to drop
- 6:36Speaker 1: off the system before the fault can be cleared. This
- 6:39Speaker 1: disadvantage may be overcome by inserting sufficient resistance in the
- 6:42Speaker 1: neutral connection to limit the current to a small value
- 6:45Speaker 1: so that an accidental ground will not seriously disturb the load.
- 6:49Speaker 1: Sometimes this resistance is so low that the ground current
- 6:52Speaker 1: approaches a short circuit in magnitude and can therefore be
- 6:55Speaker 1: handled by ordinary relays intended for short circuit protection. It
- 7:00Speaker 1: is becoming a common practice to use a resistance of
- 7:02Speaker 1: such magnitude that the ground current is kept below the
- 7:05Speaker 1: full load value of the current in any of the feeders.
- 7:08Speaker 1: This is particularly useful in cable systems because cable faults
- 7:11Speaker 1: usually start between one conductor and the grounded lead sheath,
- 7:15Speaker 1: and as the ground current is held to a small value,
- 7:17Speaker 1: it is possible by means of suitable relays to disconnect
- 7:21Speaker 1: the faulty cable before the trouble is developed into a
- 7:23Speaker 1: short circuit with a consequent interruption to the nearby load.
- 7:28Speaker 1: Nature of open wire short circuits, the nature of a
- 7:32Speaker 1: short circuit and its effect upon relay operation have been
- 7:35Speaker 1: determined both by experiment and years of experience on overhead lines.
- 7:40Speaker 1: Short circuits are usually arcs, and the resistance across them
- 7:43Speaker 1: is small and of a fairly stable value. Short circuits
- 7:47Speaker 1: of this nature sometimes cause extensive trouble wherever there are
- 7:50Speaker 1: several transmission lines on the same structure, due to the
- 7:53Speaker 1: blowing of the arc from one circuit to the adjacent ones.
- 7:57Speaker 1: Flashovers caused by lightning are a particular annoying because the
- 8:00Speaker 1: lightning usually strikes on the windward side of the structure.
- 8:04Speaker 1: The lightning coming with the storm, and the wind then
- 8:07Speaker 1: may blow the arc across all the other circuits. For
- 8:10Speaker 1: this reason, it is advantageous if possible, to disconnect the
- 8:15Speaker 1: first line in trouble before the arc has had time
- 8:17Speaker 1: to involve the neighboring lines, but this is always difficult
- 8:21Speaker 1: and usually impossible to accomplish. Several cases are known where
- 8:25Speaker 1: trouble has communicated itself in this manner to several parallel circuits,
- 8:29Speaker 1: each of which was equipped with practically instantaneous relays, and
- 8:32Speaker 1: yet the circuit breakers could not open fast enough to
- 8:35Speaker 1: clear one line before the arc had blown across to
- 8:37Speaker 1: the other lines. In checking some of these faults, the
- 8:41Speaker 1: Weather Bureau records were consulted, and it was found that
- 8:43Speaker 1: the average wind velocity at that station was about four
- 8:47Speaker 1: miles per hour, which corresponds to approximately six feet per second.
- 8:51Speaker 1: When it is considered that an arc has no inertia,
- 8:54Speaker 1: it is easy to see why trouble on one circuit
- 8:56Speaker 1: will involve the neighboring circuit, even on a quiet day.
- 9:01Speaker 1: It sometimes happens that in testing lines, after an extensive interruption,
- 9:05Speaker 1: the switchboard operator closes in the good lines first and
- 9:08Speaker 1: then closes in the bad line, thus starting trouble which
- 9:11Speaker 1: involves all the lines and trips them out again. Therefore,
- 9:15Speaker 1: in testing circuits it is good policy to vary the
- 9:18Speaker 1: sequence of closing the breakers after one sequence of operation
- 9:22Speaker 1: is failed to hold. On systems having a large connected
- 9:25Speaker 1: generating capacity, the length to which an arc can be
- 9:28Speaker 1: drawn out by the wind is almost unbelievable. Arcs more
- 9:32Speaker 1: than twenty feet long within a station have been seen,
- 9:35Speaker 1: and authentic cases are recorded of arcs having a length
- 9:37Speaker 1: of two hundred feet or more on high voltage lines.
- 9:41Speaker 1: These long arcs usually occur on lines of sixty six
- 9:44Speaker 1: thousand volts or above, but where towers are used to
- 9:47Speaker 1: support the structure, it is surprising how seldom they jump
- 9:50Speaker 1: from one circuit to another. This is probably because the
- 9:54Speaker 1: grounded steel tower acts as a shield between the circuits
- 9:57Speaker 1: at the point where the trouble starts, namely at the insulators.
- 10:03Speaker 1: Nature of trouble in cables. Because trouble in cables usually
- 10:08Speaker 1: occurs at the joint in manholes where there is danger
- 10:10Speaker 1: of injuring adjacent cables, it is essential that the defective
- 10:14Speaker 1: section be disconnected within a reasonable time. Tests have been
- 10:18Speaker 1: made on an eleven thousand volt system which prove that
- 10:20Speaker 1: the voltage across the arc between the two conductors amounts
- 10:23Speaker 1: to two or three percent of normal voltage, the value
- 10:26Speaker 1: being practically independent of the current. This is easily explained
- 10:31Speaker 1: if we assume that the resistance of the arc decreases
- 10:33Speaker 1: as the current through it is increased. These tests were
- 10:37Speaker 1: made by sawing off the cable and allowing the arc
- 10:39Speaker 1: to form between the conductors at its end. It is
- 10:42Speaker 1: not only possible, but also probable that when the arc
- 10:46Speaker 1: is combined in the cable, its resistance will increase as
- 10:48Speaker 1: the pressure increases due to the generated gases, and this
- 10:52Speaker 1: naturally will increase the voltage across the arc. This voltage
- 10:57Speaker 1: will ensure the correct operation of directional relays even when
- 11:00Speaker 1: a fault occurs close to the switching station. Most faults
- 11:04Speaker 1: start as a ground between one conductor and the lead sheath,
- 11:07Speaker 1: usually due to the entrance of moisture into the cable.
- 11:11Speaker 1: By means of a suitable relay installation, it is often
- 11:14Speaker 1: possible to disconnect any of these faulty cables before the
- 11:17Speaker 1: arc has involved the other two conductors. One operating company
- 11:21Speaker 1: is found by an analysis of defective sections of the
- 11:24Speaker 1: cable that about fifty percent of the cable troubles are
- 11:27Speaker 1: cleared without developing short circuits. Power factor of short circuits.
- 11:34Speaker 1: It is the general impression that short circuits are of
- 11:37Speaker 1: low power factor, but this is usually not so. It
- 11:41Speaker 1: is true, of course, that the total reactance of the
- 11:43Speaker 1: circuit involved in the short circuit is high compared to
- 11:46Speaker 1: the resistance, but most of this reactance is in the
- 11:49Speaker 1: apparatus and is not usually of importance in relay work.
- 11:55Speaker 1: We are interested usually in the power factor of the
- 11:57Speaker 1: line itself during times of short circuit, and this of
- 12:00Speaker 1: course depends on the relative resistance and reactants of the
- 12:04Speaker 1: line conductor, and is therefore independent of its length. High
- 12:08Speaker 1: voltage sixty cycle overhead transmission lines sometimes have a power
- 12:12Speaker 1: factor of less than fifty percent, but that is not
- 12:15Speaker 1: the rule, and twenty five cycle lines in all cable
- 12:18Speaker 1: circuits have a much higher power factor. It should be remembered, however,
- 12:23Speaker 1: that the power factor of a short circuit or ground
- 12:25Speaker 1: fault may vary widely according to conditions, and this fact
- 12:29Speaker 1: should always receive consideration when applying relays, especially those dependent
- 12:34Speaker 1: for their operation upon both voltage and current distortion of phases.
- 12:42Speaker 1: In faults involving all three wires of a three phase system,
- 12:45Speaker 1: the only abnormal conditions which ordinarily will exist are the
- 12:49Speaker 1: excess flow of current into the fault and the low
- 12:51Speaker 1: voltage in its vicinity. But these present no difficulties in
- 12:55Speaker 1: relay protection. Any other fault which may occur, such as
- 12:58Speaker 1: a two wire short circuit or a ground on one
- 13:01Speaker 1: or two wires three wire three phase system considered, will
- 13:05Speaker 1: not only cause an abnormal current flow, but will also
- 13:08Speaker 1: necessarily result in an unbalanced or distorted condition of phases
- 13:12Speaker 1: on account of the abnormal current flow being in only
- 13:15Speaker 1: one or two of the three lines. This distortion is
- 13:18Speaker 1: greatest in the vicinity of the fault and gradually lessens
- 13:21Speaker 1: as the distance from the fault increases. Exact conditions existing
- 13:26Speaker 1: after a short circuit or ground has occurred are hard
- 13:29Speaker 1: to determine because so many conditions and characteristics are present
- 13:32Speaker 1: in every system, which vary widely in different systems. Some
- 13:37Speaker 1: few years ago, mister G. H. Gray and mister L. N.
- 13:40Speaker 1: Crichton made extensive tests respecting such conditions, using an artificial
- 13:45Speaker 1: transmission line for the purpose. Figures twelve, thirteen, fourteen, fifteen, sixteen,
- 13:51Speaker 1: and seventeen shows some of the results of these tests,
- 13:54Speaker 1: plotted vectorially. The values plotted were taken from the selograms
- 13:59Speaker 1: and thus re present actual conditions existing after the fault occurred.
- 14:04Speaker 1: Effect of phase distortion on relay operation phase distortion has
- 14:09Speaker 1: no effect on the operation of straight over current relays.
- 14:13Speaker 1: In the case of directional relays, however, where the correct
- 14:16Speaker 1: operation of the relay is dependent on the operation of
- 14:18Speaker 1: a watt meter element, phase distortion must be considered. A
- 14:22Speaker 1: true watt meter will reverse if the angle between the
- 14:25Speaker 1: current andly applied voltage becomes greater than ninety degrees. Therefore,
- 14:30Speaker 1: the problem in the application of directional relays is to
- 14:33Speaker 1: make the voltage in current phase relations such that the
- 14:35Speaker 1: worst conditions of phase distortion will never cause the angle
- 14:39Speaker 1: between the current and the voltage to exceed ninety degrees.
- 14:42Speaker 1: The vector diagrams Figures eighteen and nineteen show the conditions
- 14:46Speaker 1: which may exist. In Figure eighteen, the current and voltage
- 14:50Speaker 1: vectors of only one phase are shown. Ao represents the
- 14:54Speaker 1: voltage from A to neutral and isob one represents the
- 14:57Speaker 1: current in leg A with a slightly lagging power factor.
- 15:01Speaker 1: Figure nineteen shows a possible distortion of phases when a
- 15:04Speaker 1: short circuit occurs from line A to C. A short
- 15:08Speaker 1: circuit of unity power factor would mean a heavy current
- 15:10Speaker 1: in phase with voltage AC, but due to the reactants
- 15:14Speaker 1: of the circuit, the current would probably lag considerably more
- 15:17Speaker 1: and would take a direction as shown by the vector
- 15:19Speaker 1: ISoP two AO. The voltage to neutral changes its direction
- 15:24Speaker 1: only slightly, and as is evident, the angle between AO
- 15:28Speaker 1: and isob two may easily be greater than ninety degrees. Now,
- 15:33Speaker 1: if a directional relay with a wat meter winding has
- 15:35Speaker 1: its voltage coil connected to AO and its current coil
- 15:39Speaker 1: to phase A, it will tend to reverse as soon
- 15:41Speaker 1: as the angle OAI exceeds ninety degrees. It will thus
- 15:45Speaker 1: close its contacts and trip the circuit breaker with current
- 15:49Speaker 1: flowing in the normal direction opposite to that for which
- 15:52Speaker 1: the relay is supposed to trip. Actual tests have shown
- 15:56Speaker 1: that the angle OA ISoP two may be as great
- 15:59Speaker 1: as a hunder twenty degrees with a short circuit between
- 16:02Speaker 1: A and C. This will cause directional relays to close
- 16:05Speaker 1: their contacts on normal direction of power flow, when the
- 16:08Speaker 1: directional contacts should be held positively open. The most satisfactory
- 16:14Speaker 1: solution of this problem is to connect the potential coil
- 16:17Speaker 1: of the relay to a voltage which is thirty degrees
- 16:19Speaker 1: behind the current at one hundred percent power factor, referring
- 16:23Speaker 1: to Figures eighteen and nineteen. If the voltage were taken
- 16:26Speaker 1: from phase A to C, then under short circuit conditions,
- 16:30Speaker 1: the angle CAI always would be less than ninety degrees
- 16:34Speaker 1: and the directional relay contacts would never close on normal
- 16:37Speaker 1: direction of power flow phase relations with Delta Star connected transformers.
- 16:44Speaker 1: Where directional relays are to be applied to substations having
- 16:47Speaker 1: Delta Star connected power transformers, it is often desirable to
- 16:51Speaker 1: connect the voltage transformers on the low voltage side, while
- 16:54Speaker 1: it is necessary to have the current transformers connected in
- 16:57Speaker 1: the high voltage leads in order to get the true
- 17:00Speaker 1: current flowing. Special care is necessary in such cases in
- 17:04Speaker 1: order to secure the connections which will give the proper
- 17:07Speaker 1: phase relations between the voltage and current for the relay.
- 17:10Speaker 1: As already stated, in order to assure proper operation of
- 17:14Speaker 1: the relay with the phase distortion accompanying a short circuit
- 17:17Speaker 1: or ground, the relay current should lead the relay voltage
- 17:20Speaker 1: by thirty degrees under normal conditions with one hundred percent
- 17:24Speaker 1: power factor on the system. Figures twenty twenty one, twenty two,
- 17:29Speaker 1: and twenty three show the correct connections for such combinations
- 17:32Speaker 1: to be used in applying Type CR directional relays. The
- 17:36Speaker 1: vectors show the relative phase relations for each step of
- 17:38Speaker 1: the transformation. Section two Methods of clearing short circuits. The
- 17:46Speaker 1: simplest system of distribution is one having a single source
- 17:49Speaker 1: of power with a number of feeders leaving the generator
- 17:52Speaker 1: bus bar, each feeder in turn being subdivided into a
- 17:56Speaker 1: number of small feeders. This is termed the radial distributions system.
- 18:00Speaker 1: The protection of such a system against short circuit may
- 18:03Speaker 1: be secured by overcurrent protective devices. The smaller branches may
- 18:08Speaker 1: be disconnected automatically from the remainder of the system by
- 18:11Speaker 1: the blowing of a fuse or the operation of instantaneous
- 18:14Speaker 1: circuit breakers. The circuit breakers near the generator should be
- 18:18Speaker 1: equipped with definite time relays. A time interval between the
- 18:22Speaker 1: successive relays long enough to assure a reasonable margin of
- 18:25Speaker 1: safety above that required for the circuit breaker to operate
- 18:29Speaker 1: is allowed. Relays at the generator bus are given the
- 18:32Speaker 1: highest time settings. The settings of the other relays are
- 18:36Speaker 1: decreased as their distance away from the generator increases, until
- 18:39Speaker 1: the most remote relay has an instantaneous setting. Fig. Twenty
- 18:44Speaker 1: four shows a typical radial system. The smallest branches, such
- 18:48Speaker 1: as those leading out from substation C and D may
- 18:52Speaker 1: be sufficiently protected by fuses, while other remote feeders carrying
- 18:56Speaker 1: greater power may require a circuit breaker, which may be
- 18:59Speaker 1: equiped with an overcurrent trip coil, so that the breaker
- 19:02Speaker 1: will be opened almost instantly upon the occurrence of a
- 19:05Speaker 1: short circuit on the feeder as we proceed back towards
- 19:09Speaker 1: the generating station. A over current relays such as the
- 19:13Speaker 1: co relays, are necessary in conjunction with the circuit breakers
- 19:17Speaker 1: to give a definite time for tripping. Assuming that there
- 19:21Speaker 1: is a short circuit at M, the excess current will
- 19:23Speaker 1: flow through relays numbers one and four, but number four
- 19:26Speaker 1: will trip in one second, thus cutting off the short
- 19:29Speaker 1: circuited line before number one has had time to trip. Likewise,
- 19:34Speaker 1: with a faulted n both relay numbers two and five
- 19:38Speaker 1: will be affected, but number five will trip its breaker first.
- 19:42Speaker 1: It is common practice to allow approximately zero point five
- 19:46Speaker 1: second between the successive relays and two point zero seconds
- 19:49Speaker 1: as the maximum permissible setting. In addition to securing discrimination
- 19:55Speaker 1: on the part of the relays by means of a
- 19:56Speaker 1: definite time feature, it is also possible to discrimin eight
- 20:00Speaker 1: by the current setting, because trouble which occurs at the
- 20:03Speaker 1: far end of one of the branch lines will not
- 20:06Speaker 1: draw so heavy a current as if it were near
- 20:08Speaker 1: the generating station. Relays such as number seven and eight Fig.
- 20:13Speaker 1: Twenty four on the remote lines may therefore be given
- 20:17Speaker 1: a setting which will cause them to operate on a
- 20:19Speaker 1: much lower current than will the relays near the generator.
- 20:23Speaker 1: The Westinghouse COO relay is especially adapted for such installations
- 20:27Speaker 1: because it combines the inverse and definite minimum time characteristics,
- 20:31Speaker 1: and because it also may be set to operate on
- 20:33Speaker 1: various values of current. In radial systems in which the
- 20:38Speaker 1: number of branches becomes so great that it is difficult
- 20:41Speaker 1: to allow the necessary time setting between successive relays without
- 20:44Speaker 1: making the time setting on the relays at the generating
- 20:47Speaker 1: station extremely high, the CZ distance or impedance relay may
- 20:51Speaker 1: be used instead of the COEO relay. When this relay
- 20:55Speaker 1: is used, the relay nearest the fault operates the quickest,
- 20:58Speaker 1: thus making time settings unnecessary. This type of relay is
- 21:02Speaker 1: slightly more expensive than the COO and requires voltage connections
- 21:06Speaker 1: in addition to the current connections. The ring or a
- 21:11Speaker 1: loop system The ring or loop system as indicated by
- 21:15Speaker 1: the name is simply a continuous transmission line running through
- 21:19Speaker 1: a series of substations and finally terminating at its starting point.
- 21:23Speaker 1: This forms one of the best ways of securing uninterrupted
- 21:26Speaker 1: service with a minimum expense for feeders. The number of
- 21:30Speaker 1: substations which may be thus tied together depends upon the
- 21:33Speaker 1: geographical location and the relay protection that is desired. Where
- 21:37Speaker 1: the CEO and CR relays are used, the number of
- 21:40Speaker 1: stations is limited due to the fact that the required
- 21:43Speaker 1: time intervals necessary between successive relays add up to an
- 21:47Speaker 1: unsafe value. With the advent of the CZ relay, however,
- 21:51Speaker 1: this difficulty is largely removed on a simple loop system
- 21:56Speaker 1: having only one source of power. Directional over current relays
- 22:00Speaker 1: with definite time limit characteristics may be used for protection
- 22:03Speaker 1: against short circuits. The time setting of each successive relay
- 22:07Speaker 1: must be increased by an amount sufficient usually zero point
- 22:10Speaker 1: five second in practice, to allow time for the circuit
- 22:13Speaker 1: breaker and the preceding substation to open. The directional relays
- 22:17Speaker 1: applied at each substation are fixed so that they will
- 22:20Speaker 1: trip only when excess current is flowing away from the
- 22:22Speaker 1: substation bus. It is therefore evident that with successive time settings.
- 22:28Speaker 1: The relays at each end of any faulty section will
- 22:31Speaker 1: be the first to operate, serving to isolate this section
- 22:33Speaker 1: of the loop. Straight over current relays may be used
- 22:37Speaker 1: at the generating station or source of power, as any
- 22:40Speaker 1: fault on the system can cause power flow in only
- 22:42Speaker 1: one direction from this point. Fig. Twenty six shows a
- 22:45Speaker 1: typical loop system tying in four substations with the generating station.
- 22:50Speaker 1: It shows the application of directional overcurrent relays on each
- 22:53Speaker 1: side of the substations and straight over current relays at
- 22:56Speaker 1: the generating station. The arrows indicate the direction in which
- 23:01Speaker 1: the overcurrent must flow to trip the relay, and the
- 23:04Speaker 1: figures show the definite minimum time setting of the relay.
- 23:07Speaker 1: Considering a fault at M, current will flow to it
- 23:10Speaker 1: from substations B and C, the zero point six second
- 23:14Speaker 1: relay will trip out the substation C end, and the
- 23:17Speaker 1: one point six second relay at the substation B end.
- 23:20Speaker 1: It should be noted that the same fault current flows
- 23:23Speaker 1: through the one point one second relay at substation D
- 23:26Speaker 1: in the proper direction and the one point six second
- 23:29Speaker 1: relay at D. The relay at C, however, trips first,
- 23:33Speaker 1: clearing the fault. The same current flows through the zero
- 23:36Speaker 1: point six second relay at D and the zero point
- 23:38Speaker 1: one second relay at E, but in the wrong direction
- 23:41Speaker 1: to cause them to close their contacts. A fault at
- 23:44Speaker 1: any point may be similarly checked out. Where a loop
- 23:47Speaker 1: system has more than one source of power, the application
- 23:51Speaker 1: of relays become somewhat more complicated. The same type of
- 23:54Speaker 1: relay may be applied with the same system of successive
- 23:57Speaker 1: time settings. One difficulty that is encountered in such a
- 24:01Speaker 1: system is that if the relays are set for a
- 24:03Speaker 1: condition with both sources of power connected, such settings must
- 24:07Speaker 1: be changed somewhat when one source of power is disconnected.
- 24:10Speaker 1: In this case, the entire relay system has to be readjusted.
- 24:14Speaker 1: This illustrates the necessity for using relays whose adjustment can
- 24:18Speaker 1: be changed quickly type CO and CR relays. The Westinghouse
- 24:25Speaker 1: CO and CR relays are specially adaptable for use on
- 24:28Speaker 1: loop systems, as they embody the definite time limit characteristics
- 24:32Speaker 1: with a very flexible adjustment for values of operating current.
- 24:36Speaker 1: In addition to the dependable accuracy of the relay settings
- 24:39Speaker 1: and the speed of action, Any necessary changes in the
- 24:42Speaker 1: settings or adjustments may be made quickly and conveniently type
- 24:47Speaker 1: CZ impedance relay. Sometimes it is very difficult to arrive
- 24:52Speaker 1: at a suitable method of protection for a loop system
- 24:55Speaker 1: due to the fact that when applying the standard time
- 24:57Speaker 1: element relay and allowing the necessary time intervals in order
- 25:01Speaker 1: to secure selectivity, the time settings of the relays at
- 25:04Speaker 1: the ends of the loop become necessarily higher than is
- 25:07Speaker 1: either safe or advisable. A more recent and flexible relay
- 25:11Speaker 1: application for such complicated systems is the use of the
- 25:15Speaker 1: impedance or distance relay developed by the Westinghouse Company. With
- 25:19Speaker 1: the proper application of the CZ relay, all time settings
- 25:23Speaker 1: are taken care of automatically. After each relay has been
- 25:26Speaker 1: set to protect its own section of the line, each
- 25:29Speaker 1: relay is set to trip out its own section of
- 25:31Speaker 1: the line in a time corresponding to the distance to
- 25:34Speaker 1: the fault, the maximum time required being zero point seven
- 25:37Speaker 1: to five second, which corresponds to a short at the
- 25:40Speaker 1: far end of the line. Regardless of on what section
- 25:44Speaker 1: of the system the fault takes place, the proper relay
- 25:46Speaker 1: will trip out and at no time will the isolation
- 25:49Speaker 1: of the faulty line require more than zero point seventy
- 25:52Speaker 1: five to one second to accomplish. The other CZ relays
- 25:56Speaker 1: on other sections of the line will start the function,
- 25:58Speaker 1: but by reason of their greater distance from the fault,
- 26:01Speaker 1: they will not trip out their breakers, but will return
- 26:04Speaker 1: to their normal position as soon as the relays on
- 26:06Speaker 1: the faulty line have isolated the fault. This automatic increase
- 26:10Speaker 1: in timing with increase in distance to the fault is
- 26:13Speaker 1: the unique feature of a CZ installation. With the addition
- 26:17Speaker 1: of a directional element to the relay main element, this
- 26:20Speaker 1: relay may be applied on loop systems in the same
- 26:22Speaker 1: way as CO and CR relays. The choice between the
- 26:26Speaker 1: use of the two applications is dependent mainly on the cost.
- 26:30Speaker 1: The CO CR application is preferable whenever it can be
- 26:34Speaker 1: supplied satisfactorily, inasmuch as the relays themselves are less expensive
- 26:38Speaker 1: and the COO relays do not require a voltage connection.
- 26:42Speaker 1: Where the system is complicated and the sections of sufficient
- 26:45Speaker 1: length long enough to give approximately three percent voltage drop
- 26:49Speaker 1: between ends of the section, the CZ relay is applicable
- 26:52Speaker 1: and should be used. This voltage, which is a measure
- 26:56Speaker 1: of the impedance voltage drop to the point of short circuit,
- 27:00Speaker 1: is supplied to the voltage element of the relay by
- 27:02Speaker 1: potential transformers connected either to the high or the low
- 27:05Speaker 1: side of the power transformers. If connected to the high
- 27:09Speaker 1: side of the power transformers, the potential transformers will supply
- 27:13Speaker 1: to the relay elements voltages corresponding exactly to the line voltage,
- 27:17Speaker 1: and accordingly, the relays will function properly. In case only
- 27:21Speaker 1: potential transformers connected to the low side of the power
- 27:24Speaker 1: transformers are available, it sometimes becomes necessary to use voltage
- 27:28Speaker 1: compensators similar to those used with voltage regulators, to compensate
- 27:33Speaker 1: for the drop through the transformer which has been inserted
- 27:36Speaker 1: between the relay and the line to be protected. Compensators
- 27:40Speaker 1: are provided one to compensate for the impedance drop in
- 27:43Speaker 1: the power transformer, which drop is present when short circuit
- 27:47Speaker 1: current is flowing through the transformer into the line that
- 27:50Speaker 1: is shorted. Two to compensate for the shift in the
- 27:54Speaker 1: neutral at the unngrounded substation end of a solidly grounded system,
- 27:58Speaker 1: which shift occurs in case of an accidental ground on
- 28:01Speaker 1: the high side. Figures twenty seven, twenty eight, and twenty
- 28:05Speaker 1: nine show typical CZ applications with and without compensation as
- 28:11Speaker 1: required protection of parallel feeders. Where two or more identical
- 28:17Speaker 1: or similar lines connect a generating station and a substation,
- 28:21Speaker 1: two substations, or two generator stations, they are termed parallel feeders.
- 28:26Speaker 1: Such an arrangement of feeders may be applied to either
- 28:29Speaker 1: radial systems or loop systems, and it has come into
- 28:32Speaker 1: very common use too, not only to the fact that
- 28:35Speaker 1: it is an economical and convenient means of increasing transmission capacity,
- 28:39Speaker 1: but also to the fact that it forms a most
- 28:42Speaker 1: flexible system for economical operation of lines and lends itself
- 28:46Speaker 1: very readily to relay protection CO and CR relay scheme.
- 28:53Speaker 1: In general, the standard application of CO overcurrent and CR
- 28:57Speaker 1: directional overcurrent relays may be applied to parallel feeders in
- 29:01Speaker 1: the same way as in the case of single lines
- 29:03Speaker 1: of loop systems. Where the system is large, however, the
- 29:07Speaker 1: time settings on some of the relays must necessarily be
- 29:09Speaker 1: high in order to secure selectivity, and this in itself
- 29:13Speaker 1: is often a difficulty which cannot be overcome. Balance power scheme.
- 29:20Speaker 1: A general solution of this problem is to use a
- 29:22Speaker 1: balance system of relays. Separate parallel circuits which normally carry
- 29:27Speaker 1: equal currents, are balanced against one another. If the currents
- 29:31Speaker 1: maintain their equality in spite of their magnitude, it is
- 29:34Speaker 1: a good indication that no fault exists in that particular group.
- 29:38Speaker 1: On the other hand, a certain degree of unbalancing would
- 29:41Speaker 1: be a safe indication of trouble. The problem, therefore, is
- 29:46Speaker 1: in general to separate a current which is representative of
- 29:50Speaker 1: the actual unbalancing and pass it through proper relays so
- 29:53Speaker 1: that the faulty feeder may be disconnected. One method of
- 29:57Speaker 1: solving this problem is by balancing the current fel lowing
- 30:00Speaker 1: in the two feeders by the cross connection of directional relays.
- 30:04Speaker 1: This scheme may be applied to any system, no matter
- 30:07Speaker 1: how complex. If its feeders are run parallel between the
- 30:10Speaker 1: switching points, the relays may be set to act almost instantaneously.
- 30:14Speaker 1: With this system, the relays can be set to operate
- 30:17Speaker 1: on currents smaller than the full load value of each feeder.
- 30:20Speaker 1: This arrangement enables the clearing of trouble on a system
- 30:24Speaker 1: having the neutral grounded through a high resistance when the
- 30:27Speaker 1: total trouble and load current flowing through a single cable
- 30:30Speaker 1: may be less than the maximum load current of that cable.
- 30:34Speaker 1: The schematic diagram Figure thirty two shows the scheme of
- 30:38Speaker 1: cross connection of directional relays applied to a system of
- 30:41Speaker 1: four parallel feeders. Figure thirty three shows a complete diagram
- 30:46Speaker 1: of standard connections for a pair of three phase feeders,
- 30:49Speaker 1: except that the tripping circuit is omitted. By reference to
- 30:53Speaker 1: these two figures, it will be seen that all the
- 30:55Speaker 1: current transformers in the generating station are connected in series,
- 30:59Speaker 1: likewise those in the substation. Each relay is a unidirectional
- 31:04Speaker 1: relay and is shunted across its own current transformer. Under
- 31:08Speaker 1: normal conditions, the load in each of the cables will
- 31:11Speaker 1: be the same, and since the relays are of a
- 31:13Speaker 1: higher impedance than the current transformers, the current from the
- 31:17Speaker 1: latter will circulate through all of the transformers and series
- 31:20Speaker 1: without any flowing through the relays. If the trouble occurs
- 31:23Speaker 1: at any point outside the section protected by these cross
- 31:26Speaker 1: connected relays, the current through the protected lines will still
- 31:29Speaker 1: be balanced, and consequently there will be no unbalanced current
- 31:33Speaker 1: tending to operate the relays. On the other hand, if
- 31:36Speaker 1: trouble occurs on a line within the section, the current
- 31:40Speaker 1: through the defective cable will be higher than that in
- 31:42Speaker 1: the other, and the excess current from its current transformer
- 31:45Speaker 1: must therefore pass through the relays. While the system is
- 31:49Speaker 1: in this unbalanced condition, current will flow through all the relays,
- 31:53Speaker 1: but in the proper direction to cause only the relay
- 31:55Speaker 1: at each end of the defective cable to act. Fig.
- 31:59Speaker 1: Thirty three shows auxiliary pallette switches connected in the transformer
- 32:03Speaker 1: secondary circuit. These switches are also connected mechanically to the
- 32:07Speaker 1: operating mechanism of the breakers, so that when the braker opens,
- 32:11Speaker 1: the current transformers on the feeder will be short circuited.
- 32:15Speaker 1: By this method, a line can be cut out of
- 32:17Speaker 1: service without interfering with the electrical balance in the remaining
- 32:21Speaker 1: transformer circuit. However, these pallet switches are not needed in
- 32:26Speaker 1: the transformer circuits except where low ratio bushing type current
- 32:30Speaker 1: transformers are used. Ordinarily, the impedance of the current transformer
- 32:34Speaker 1: secondaries is sufficient when the primaries are open circuited to
- 32:38Speaker 1: prevent any appreciable current from passing through them. By referring
- 32:43Speaker 1: to Figures thirty two and thirty three, it will be
- 32:46Speaker 1: observed that under balance conditions, no current is flowing in
- 32:49Speaker 1: the relay current coil. When a fault develops on one line,
- 32:53Speaker 1: the current voltage and that group of relays are in
- 32:56Speaker 1: such a relation as to close the directional element contacts,
- 33:00Speaker 1: while in the other group of relays the voltage is
- 33:02Speaker 1: in the opposite direction and so opens the directional element contacts.
- 33:06Speaker 1: It is therefore apparent that if the directional element were
- 33:09Speaker 1: made double throw, one set of relays could be made
- 33:12Speaker 1: to protect two parallel feeders by cross connecting the current transformers.
- 33:17Speaker 1: Such a relay is available under the name of the
- 33:20Speaker 1: duodirectional type CR relay. Its chief disadvantage is that either
- 33:25Speaker 1: abnormal phase distortion or mechanical vibration may displace the relatively
- 33:29Speaker 1: light directional element and trip the circuit breaker before the
- 33:32Speaker 1: fault has been isolated, thereby interrupting service over the good line.
- 33:37Speaker 1: A further adaptation of the cross connected CR relay protective
- 33:40Speaker 1: scheme gives both short time low current protection when two
- 33:44Speaker 1: feeders are operating in parallel and longtime directional over current
- 33:48Speaker 1: protection when one of the feeders is operating singly. As
- 33:51Speaker 1: a part of a transmission loop. Fig. Thirty four shows
- 33:56Speaker 1: the complete connections for two incoming feeders to a substation.
- 34:00Speaker 1: Volage and current connections to the relays are so made
- 34:03Speaker 1: that the relays of each set close their directional element
- 34:06Speaker 1: contacts when unbalanced power is flowing out over the line
- 34:09Speaker 1: which those relays protect. Each relay is provided with a
- 34:13Speaker 1: tap between the directional element contacts and the overcurrent element contacts,
- 34:18Speaker 1: and these taps are joined to a common bus for
- 34:20Speaker 1: each pair of lines, so that any overcurrent element can
- 34:23Speaker 1: trip either circuit breaker by acting through the directional element
- 34:26Speaker 1: contacts of the corresponding relays. With the feeders carrying equal loads,
- 34:31Speaker 1: there is no current flowing through the current windings of
- 34:33Speaker 1: the relays. As soon as a fault develops on one line,
- 34:36Speaker 1: an unbalanced circuit circulates through the relays, causing the directional
- 34:40Speaker 1: element contacts on the faulty line group to close and
- 34:43Speaker 1: those of the good line group to open. The faulty
- 34:46Speaker 1: line circuit breakers tripped by the closing of the contacts
- 34:48Speaker 1: of the overcurrent element having the short time setting. As
- 34:52Speaker 1: soon as the faulty line circuit breaker is open, the
- 34:55Speaker 1: control circuit to the short time overcurrent element is broken
- 34:58Speaker 1: by the series connection through the circuit breaker auxiliary switches.
- 35:02Speaker 1: The remaining line then has directional overcurrent protection, only the
- 35:05Speaker 1: time and current settings of the overcurrent element being determined
- 35:08Speaker 1: by operating conditions on the loop. It is general practice
- 35:12Speaker 1: to base such settings on the assumption that with a
- 35:15Speaker 1: loop composed of normally balanced lines, not more than two
- 35:18Speaker 1: sections will be operating as single lines. It is interesting
- 35:22Speaker 1: to note that this scheme of connection obviates the use
- 35:25Speaker 1: of a circuit opening definite time delay direct current relay
- 35:29Speaker 1: to prevent improper operation of the good line circuit breaker.
- 35:32Speaker 1: It has been found necessary in many instances to employ
- 35:35Speaker 1: such relays with cross connected schemes in order to prevent
- 35:38Speaker 1: unnecessary tripping. Balance power relays are satisfactory, particularly where there
- 35:44Speaker 1: is no source of power available at one end of
- 35:46Speaker 1: the parallel lines, but the use of differential current relays
- 35:49Speaker 1: is simpler and is usually preferred where power can be
- 35:52Speaker 1: supplied from both ends of the group of lines. Type
- 35:57Speaker 1: CD selective differential relay scheme. Another scheme which is coming
- 36:02Speaker 1: into common use for parallel line protection is a scheme
- 36:05Speaker 1: using the balance current relay, known as the type CD relay.
- 36:09Speaker 1: It may be used at the transmitting end of any
- 36:12Speaker 1: number of parallel lines and at the receiving end of
- 36:15Speaker 1: any number of parallel lines in a system having a
- 36:17Speaker 1: source of power at both ends or at the receiving
- 36:20Speaker 1: end of three or more parallel feeders. In a radial system,
- 36:24Speaker 1: it cannot be used on a single pair of radial
- 36:26Speaker 1: parallel feeders. For in case of a fault on one line,
- 36:30Speaker 1: there would be an equal and opposite current in the
- 36:32Speaker 1: two elements and the relay would not operate. The same
- 36:36Speaker 1: condition will exist after one of three parallel lines has
- 36:39Speaker 1: been disconnected at the receiving end. For this reason, cross
- 36:43Speaker 1: connected power directional relays are usually used at such points.
- 36:47Speaker 1: With three PAARA lines protected by these relays, number one
- 36:50Speaker 1: line is balanced against number two, number two line is
- 36:53Speaker 1: balanced against number three, and number three line is balanced
- 36:56Speaker 1: against number one. In this way, complete balance protection is
- 36:59Speaker 1: secured until only one line remains in service, after which
- 37:04Speaker 1: overload protection is left on this line. If four or
- 37:07Speaker 1: more lines are thus protected, complete balance protection cannot be
- 37:11Speaker 1: assured after more than two lines have been removed from service. Thus,
- 37:15Speaker 1: with four parallel lines, number one being balanced against number two,
- 37:19Speaker 1: number two against number three, number three against number four,
- 37:23Speaker 1: and number four against number one, any one line can
- 37:26Speaker 1: be disconnected and the remaining lines will still be balanced. If, however,
- 37:31Speaker 1: numbers one and three lines both have been disconnected, numbers
- 37:35Speaker 1: two and four will be left with only over current protection.
- 37:38Speaker 1: On the other hand, if number two or number four
- 37:41Speaker 1: lines were disconnected with number one, remaining two lines would
- 37:45Speaker 1: still be balanced. Inasmuch as the action of the balance
- 37:49Speaker 1: current relay is practically instantaneous in clearing faulty lines, it
- 37:53Speaker 1: makes an ideal application for the protection of parallel lines
- 37:56Speaker 1: between generating stations. On other parallel feeders, it is often
- 38:00Speaker 1: very advisable to use overcurrent relays in connection with balanced
- 38:04Speaker 1: current relays, thus securing single line protection in addition to
- 38:08Speaker 1: quick balance protection when both lines are in service. The
- 38:12Speaker 1: chief advantages of the CD balanced current relay scheme are
- 38:15Speaker 1: as follows. One, the relay operates on current a loan,
- 38:20Speaker 1: no source of potential being required. Two. The differential current
- 38:25Speaker 1: setting is automatically doubled when one line is opened at
- 38:28Speaker 1: one end. This permits the use of a minimum differential
- 38:31Speaker 1: current setting and eliminates the necessity of additional apparatus in
- 38:35Speaker 1: the trip circuit in order to render it non automatic
- 38:38Speaker 1: until the two lines are again in service. Three, each
- 38:42Speaker 1: current transformer may be grounded, thus giving maximum protection to
- 38:46Speaker 1: the apparatus. This is not possible ordinarily with balance protection.
- 38:52Speaker 1: Four only one relay is required for two lines five
- 38:57Speaker 1: relay action is practically instantaneous. Type CZ impedance relay. The
- 39:05Speaker 1: CZ impedance relay may be used for parallel line protection
- 39:08Speaker 1: in the same way as the CO and CR relays.
- 39:12Speaker 1: The CZ directional relay is applicable in places where the
- 39:15Speaker 1: CR is used. The advantages of the impedance relay have
- 39:18Speaker 1: been explained in detail on page twenty. Network systems. The
- 39:25Speaker 1: simple radial and loop or ring systems, very often involving
- 39:29Speaker 1: parallel lines between stations, lend themselves very readily to a
- 39:32Speaker 1: scheme of relay protection, as has been outlined. However, when
- 39:37Speaker 1: additional tie lines are added, connecting substations and several sources
- 39:41Speaker 1: of power into the system at different points, it becomes
- 39:44Speaker 1: what may be termed a network, and then the relay
- 39:47Speaker 1: protection problem becomes more difficult. Type CO and CR scheme.
- 39:54Speaker 1: The CO overcurrent and CR directional overcurrent relays are sometimes
- 39:58Speaker 1: applied to such a system, vision being made to have
- 40:01Speaker 1: certain lines trip out almost instantly with a short circuit
- 40:04Speaker 1: in the vicinity. With such an arrangement, the network is
- 40:08Speaker 1: often converted into a simple ring. After the tie lines
- 40:11Speaker 1: have been disconnected and the usual scheme of time and
- 40:14Speaker 1: current settings clears up the trouble. The cutting out of
- 40:17Speaker 1: the tie line or lines in such cases does not
- 40:20Speaker 1: in any way jeopardize the service and serves to make
- 40:23Speaker 1: selective relay protection possible. For example, in Fig. Thirty eight,
- 40:28Speaker 1: the tie line between substations E and B may be
- 40:31Speaker 1: disconnected without disturbing the service supplied by the network type
- 40:36Speaker 1: CZ impedance relay scheme. A more recent and flexible relay
- 40:42Speaker 1: application for such complicated systems is the use of the
- 40:45Speaker 1: impedance or distance relay. With proper application of this type
- 40:48Speaker 1: of relay, all time settings are taken care of automatically,
- 40:52Speaker 1: the inherent characteristics of the relay being such that the
- 40:55Speaker 1: one nearest to the fault will operate first. Pilot wise
- 41:00Speaker 1: scheme of relay protection on systems where definite time relay
- 41:04Speaker 1: protection is desired. The number of substations which may be
- 41:08Speaker 1: connected successively in a system is limited by the sum
- 41:11Speaker 1: of the time intervals which it is necessary to allow
- 41:13Speaker 1: between successive relays. When such a difficulty is encountered and
- 41:17Speaker 1: the distance between some of the substations is small, a
- 41:20Speaker 1: pilot wire scheme of protection may be used on the
- 41:23Speaker 1: shorter sections. As this scheme acts almost instantaneously upon the
- 41:27Speaker 1: occurrence of a fault within the section and is unaffected
- 41:30Speaker 1: by the faults outside of the section, the section may
- 41:33Speaker 1: be disregarded entirely. When applying other relays, the system may
- 41:37Speaker 1: be considered as if that particular section were entirely cut out.
- 41:42Speaker 1: The pilot wire scheme has current transformers at each end
- 41:44Speaker 1: of the conductor short circuited upon each other through the
- 41:47Speaker 1: pilot wire see Fig. Forty. The relays are connected between
- 41:51Speaker 1: the pilot wire for each respective transformer and the common return.
- 41:55Speaker 1: When a short circuit or fault occurs on the line
- 41:58Speaker 1: between the two substations, the current transformers at the two
- 42:02Speaker 1: ends are no longer short circuited upon each other, but
- 42:05Speaker 1: the currents which they produce are opposed to each other,
- 42:08Speaker 1: so the current must flow through the relays, and the
- 42:10Speaker 1: faulty section will thus be tripped out. Inasmuch as the
- 42:14Speaker 1: current flowing through the pilot wire must be kept at
- 42:17Speaker 1: the minimum, special current transformers and co relays with special
- 42:21Speaker 1: windings to operate on low current are used for the
- 42:23Speaker 1: pilot wire protection scheme. Split conductor scheme. The split conductor
- 42:31Speaker 1: scheme is a modification of the current balance scheme of
- 42:33Speaker 1: parallel line protection, in which a special cable is used
- 42:36Speaker 1: to obtain a division of the current which is susceptible
- 42:39Speaker 1: to being balanced as ordinarily installed. The split conductor cable
- 42:44Speaker 1: is a three strand cable in which the transforming each
- 42:47Speaker 1: conductor are separated into two parts, a central portion and
- 42:51Speaker 1: a circumferential portion, the two being separated from each other
- 42:55Speaker 1: by the necessary installation. Thus, by the use of current
- 42:59Speaker 1: transforms a differential connection between the two halves of each conductor,
- 43:03Speaker 1: and overcurrent relays connected in the circuit, a very effective
- 43:07Speaker 1: system of protection is obtained. This system is not widely
- 43:11Speaker 1: used in the United States, due largely, perhaps to the
- 43:14Speaker 1: high cost of the special cable. End of Chapter three,
- 43:19Speaker 1: Part one