Latest / NTC's Temporal 3 / Episode 36 | ECF and ECFI devices, Separation requirements, code-compliant wiring, and more
Transcript
- 0:01SPEAKER_00: Hello, everyone, and welcome to this edition of the Temporal 3 Podcast, where we talk all about fire alarm.
- 0:08SPEAKER_00: I'm joined by my co-host, Charles Ulner.
- 0:11SPEAKER_00: Hello, Charles.
- 0:12SPEAKER_00: Hello, everyone.
- 0:13SPEAKER_00: Hi, Brian.
- 0:14SPEAKER_00: And my other co-host, Chris Godwin.
- 0:17SPEAKER_00: Hello, Chris.
- 0:18SPEAKER_00: Hey, Brian.
- 0:19SPEAKER_00: Hey, Charles.
- 0:20SPEAKER_00: Howdy.
- 0:21SPEAKER_00: Well, guys, this morning I'd like to talk about the most common mistakes that our students make.
- 0:27SPEAKER_00: Now, don't get me wrong, I love our students.
- 0:30SPEAKER_00: I love talking to our students both during and after and before class.
- 0:34SPEAKER_00: Any opportunity I have to engage with a student is always a good thing for me.
- 0:38SPEAKER_00: I really enjoy helping people to achieve their training goals.
- 0:43SPEAKER_00: However, sometimes I do find that our students make mistakes, even despite some things and some guidance that me we may give them.
- 0:52SPEAKER_00: Chris, what's one of the common mistakes that you've seen some of our students make?
- 0:58SPEAKER_02: One of the bigger things that comes up is not taking full advantage of you've gone through a whole class with us and we've given you access to online training and not taking advantage of the online training.
- 1:12SPEAKER_02: We get emails a lot back from students uh that go in and take the nights at exam, or they go out and they go do, you know, they struggle out in the field with whatever aspect that we've taught them to.
- 1:24SPEAKER_02: And one of the first things we look at is did you use the online training?
- 1:28SPEAKER_02: No, I didn't, I didn't use it.
- 1:29SPEAKER_02: I I did the class, I didn't need the online training.
- 1:32SPEAKER_02: It's a reinforcement.
- 1:35SPEAKER_02: A one-day class is not going to teach you what you need to know.
- 1:39SPEAKER_02: It's going to open your eyes to the things that you didn't know that you were missing.
- 1:43SPEAKER_02: And so when they don't take advantage of the online training, it's like you're skipping out on the actual training.
- 1:51SPEAKER_02: Like, I learned out in the field how to do the install one time of a device.
- 1:57SPEAKER_02: Six months later, they were I was told, hey, I need you to go install this.
- 2:01SPEAKER_02: Cool.
- 2:01SPEAKER_02: Are you gonna go with me so you can help me with it?
- 2:04SPEAKER_02: No.
- 2:05SPEAKER_02: One time's not enough.
- 2:07SPEAKER_02: You need to train it.
- 2:08SPEAKER_02: And that's the same thing that a lot of students don't end up doing is doing the actual training.
- 2:14SPEAKER_02: Train this, learn how to do more than just what we talked about.
- 2:18SPEAKER_02: And that's one of the things, Charles.
- 2:21SPEAKER_01: Building on that, you know, when we teach a class, I like to call it instructional intervention.
- 2:29SPEAKER_01: So we'll take someone's level of knowledge that's here and boost it significantly, but our knowledge in this industry is never complete.
- 2:40SPEAKER_01: Training and learning continue on and on and on as long as our career progresses.
- 2:47SPEAKER_01: Codes change, technology changes, learning is something we have to commit ourselves to uh throughout our career.
- 2:57SPEAKER_01: The online training is one aspect of that, and included with that is coaching, and that's something that you do extremely well.
- 3:06SPEAKER_01: Uh, Chris also works as a coach for all of our students to help them continue their learning as well.
- 3:14SPEAKER_00: Absolutely.
- 3:15SPEAKER_00: That level of encouragement is helpful.
- 3:18SPEAKER_00: And I want to circle back to the online training where we talk about coaching.
- 3:21SPEAKER_00: So uh maybe one of the objections people have is well, that's an extra cost.
- 3:25SPEAKER_00: Do we charge for the online training that comes with our classes?
- 3:29SPEAKER_02: No, that's that's included.
- 3:30SPEAKER_00: It's included.
- 3:31SPEAKER_00: It's free.
- 3:32SPEAKER_00: Part of the class.
- 3:33SPEAKER_00: Part of the class, and something we mention over and over and over again.
- 3:36SPEAKER_00: Please use the online training.
- 3:38SPEAKER_00: We're almost to the point of calling people after the class and saying, hey, you haven't used the online training yet.
- 3:43SPEAKER_00: Why not?
- 3:43SPEAKER_00: We don't do that, obviously, but we do encourage it.
- 3:46SPEAKER_00: We want people to use it.
- 3:48SPEAKER_00: We encourage them to use it.
- 3:49SPEAKER_00: Now, the coaching, Chris, we do that in the NISET fire alarm.
- 3:53SPEAKER_00: Tell our uh listeners how that works.
- 3:55SPEAKER_02: So when you take a NISET fire alarm class with us here at NTC, the very next week, or I actually we set it up.
- 4:05SPEAKER_02: I've been setting it up recently where it is in the class, you'll get your first email, and then the very next week you'll get your second email.
- 4:12SPEAKER_02: You will be given four emails of here's what you should be looking at this week.
- 4:18SPEAKER_02: Here's what you should be looking at this week.
- 4:19SPEAKER_02: We go over the a little bit in that email of the here are the sections of training in the online.
- 4:25SPEAKER_02: Here are other things that you can look at from the code perspective.
- 4:29SPEAKER_02: If you have any of our additional books that we might send out to you or you might want to get, here's things to look at in there.
- 4:35SPEAKER_02: And it is week one, two, three, four weeks of that.
- 4:39SPEAKER_02: You have access to the online training for most of our classes for 90 days.
- 4:45SPEAKER_02: You don't have to do all that training that we send out in the, you know, every single week, but it is something to help you out with.
- 4:52SPEAKER_02: And a lot of people, they don't, they just don't use it.
- 4:55SPEAKER_01: They just, no, I don't need it.
- 4:58SPEAKER_01: And and having the coach available is a big deal.
- 5:01SPEAKER_01: I recently got uh an email from a student saying, hey, I don't understand class D circuits, and that's something uh we are able to help with deepen their understanding on a specific subject.
- 5:15SPEAKER_01: Absolutely.
- 5:16SPEAKER_00: So Charles, uh, what about study time?
- 5:20SPEAKER_00: Do our students or do people sometimes uh, shall I say, not devote adequate study time to prepare for this exam, the nice exam?
- 5:28SPEAKER_01: Well I'll study tomorrow.
- 5:32SPEAKER_01: I'll get to that next week.
- 5:34SPEAKER_01: I'm busy right now is a common thing.
- 5:37SPEAKER_01: The uh one of the most important things I think in study is practicing strategy.
- 5:43SPEAKER_01: Yes.
- 5:44SPEAKER_01: And our online training is uh very well suited for that with the sample tests and rotating questions.
- 5:52SPEAKER_01: You can practice your strategy for taking the test.
- 5:56SPEAKER_01: And I see so many students, even though we go over strategy, make mistakes in that regard.
- 6:03SPEAKER_01: Uh Brian, talk about a few common strategic mistakes that you've got to do.
- 6:09SPEAKER_00: Well, uh, one of my personal favorites is lingering on a question, not being willing to let a question go.
- 6:16SPEAKER_00: And that's the difference between the real world and the nice it exam.
- 6:20SPEAKER_00: In the real world, if you have a ground fault, do you just say, okay, well, I'm just gonna bypass the device or you know, just hit the reset button and walk away and not solve that ground fault?
- 6:29SPEAKER_00: Absolutely not.
- 6:30SPEAKER_00: In the nice it exam, if you run into that challenging situation, you get to guess that question, certainly mark it for review and come back to it later.
- 6:38SPEAKER_00: You don't want to spend five or ten minutes on a question.
- 6:42SPEAKER_00: It is just not worth it in the exam.
- 6:44SPEAKER_00: That's one of the big ones that really drives me crazy.
- 6:46SPEAKER_00: And then I hear from people, oh, I got to the exam and I looked up and I had five minutes left and 20 questions I have even had a chance to look at because I spent all this time on this one question.
- 6:57SPEAKER_00: All the questions in the exam have equal weight.
- 6:59SPEAKER_00: Why would you spend five or ten minutes on one question when the next question may be an easy one to answer?
- 7:05SPEAKER_00: Chris, what have you seen?
- 7:06SPEAKER_02: A lot of that same, there's not a practice with strategy.
- 7:11SPEAKER_02: We talk about strategy in classes, and students will understand and grasp it in the class.
- 7:17SPEAKER_02: But one of the things that we tell them is this has to be practiced.
- 7:21SPEAKER_02: You're not just gonna do it the one time and and and okay, I've got it.
- 7:25SPEAKER_02: And me personally, I can tell you in my own nice at testing, going in without the strategy and the idea of I'm gonna answer questions as they come up, it's not good.
- 7:36SPEAKER_02: I mean, I failed level two two times, and I had to take level three two times because I did not employ a strategy.
- 7:45SPEAKER_02: I my idea was get in it and let's let's, you know, as the questions come up, answer them and move on.
- 7:52SPEAKER_02: Having a strategy is so big and it's such uh it is such an underrated thing when it comes to the exam itself, and a lot of people just don't do that.
- 8:04SPEAKER_02: Look, the goal is to move forward, the goal is to pass.
- 8:07SPEAKER_02: Yes, putting something in play to make you get to that point is how you're going to pass the exam.
- 8:14SPEAKER_02: And a lot of people just they they don't employ the strategies, they don't practice things, and that is uh it's a it's a hard thing to do, but it's also uh it it's it kind of is sad when we get people back that hey, I didn't I didn't do well.
- 8:29SPEAKER_02: Well, what was your strategy?
- 8:30SPEAKER_02: I I didn't have a strategy, I spent you know, this much time on one question.
- 8:34SPEAKER_02: Come on, we talk about let's let's practice, let's talk about these things.
- 8:38SPEAKER_02: And so it's a it's very, very important.
- 8:42SPEAKER_02: An ISAT exam is not how good are you at your job.
- 8:46SPEAKER_02: You gotta do that.
- 8:47SPEAKER_01: One other thing I'd like to uh bring up is people who take uh our training uh statistically they do very well on the NISAT exam.
- 8:59SPEAKER_01: We have ninety-three percent of our students pass the test after they take our training.
- 9:06SPEAKER_01: Yep.
- 9:07SPEAKER_01: That's much higher than the typical NISAT pass rate, Brian.
- 9:11SPEAKER_00: Yeah, absolutely it is.
- 9:13SPEAKER_00: Absolutely it is, and yeah, that's really important at 93% threshold, and that's the first time passing it the first time.
- 9:19SPEAKER_00: How awesome is that?
- 9:20SPEAKER_00: Because the NISAT exam is expensive.
- 9:23SPEAKER_00: It requires an investment of money, it requires an investment of time, and it's not something that's I would look personally look forward to going back and redoing over and over again.
- 9:32SPEAKER_00: I want to be one and done with it.
- 9:34SPEAKER_00: And but as a part of that passing strategy, we ask our students to do some things.
- 9:40SPEAKER_00: We ask them to invest in their success.
- 9:43SPEAKER_00: You got to be willing to invest in your success.
- 9:45SPEAKER_00: But if you are willing to follow the guidance that we give you as instructors, that Chris gives you as a coach, you will significantly increase your chances of passing that exam the first time.
- 9:58SPEAKER_00: Don't become a uh a source of revenue to dice that but retaking exams.
- 10:05SPEAKER_01: Students who take advantage of the coaching and the online training after attending a class, their pass rate goes up significantly from gas three.
- 10:15SPEAKER_01: I mean Absolutely.
- 10:16SPEAKER_01: I'm reluctant to say 100%, but can't say that.
- 10:21SPEAKER_01: Yeah.
- 10:21SPEAKER_01: Yeah, it's it's it's very unlikely that a student who goes through coaching will fail the test.
- 10:30SPEAKER_01: Absolutely.
- 10:31SPEAKER_02: But again, one of the things that you brought up, you brought up, Brian, was this is an investment.
- 10:36SPEAKER_02: One other thing that that students don't do is put this as an investment and get the books.
- 10:45SPEAKER_02: Get the code books.
- 10:47SPEAKER_02: Uh a lot of them are well, that's not what we use in my jurisdiction.
- 10:50SPEAKER_02: Or the new books are expensive.
- 10:53SPEAKER_02: They are.
- 10:54SPEAKER_02: They absolutely are.
- 10:55SPEAKER_02: So is taking the exam more than once.
- 10:58SPEAKER_02: And having the correct codes is I can't tell you going into class, sometimes I get very frustrated because oh, I don't have any of the books.
- 11:06SPEAKER_02: Oh, yeah, that's hard.
- 11:08SPEAKER_02: Come on, we we gotta have the books.
- 11:10SPEAKER_02: We're gonna teach you how to use them.
- 11:12SPEAKER_02: I can't teach you how to use them from the air.
- 11:14SPEAKER_02: I we we gotta have the books.
- 11:15SPEAKER_02: So it it is an investment, and having not just the code books, but the correct code books is huge.
- 11:23SPEAKER_02: It's a huge thing.
- 11:25SPEAKER_01: Charles, how often do we how often does code get updated?
- 11:28SPEAKER_01: Every three years.
- 11:30SPEAKER_01: And once you do all this, take the training, get the codes, pass the NISAT test, you'll find that you'll become better looking.
- 11:40SPEAKER_01: You'll have more friends.
- 11:44SPEAKER_01: There's big advantages to passing the NISAT test, and we can help you get it.
- 11:50SPEAKER_00: I don't know about those two statements that Charles made, but I'll tell you what, you will be wealthier because you will be NISAT certified, and you won't have to be spending a lot of money with NISAT to retake an exam.
- 12:03SPEAKER_00: All right, guys.
- 12:03SPEAKER_00: Well, next thing I'd like to talk about today is NFTA 72 chapter one, which is ECF, emergency control functions.
- 12:11SPEAKER_00: Chris, what's an emergency control function?
- 12:14SPEAKER_02: Emergency control functions are those other functions in the building that have been installed for making the building safer for the occupants.
- 12:24SPEAKER_02: HVAC shutdown, elevator recall, elevator shutdown, things like that, where when there is an activation, the purpose is to make everything safer for the occupants.
- 12:34SPEAKER_02: And what we are trying to do, we being the intent of the emergency control function, is to control the spread of the fire long enough to get the people out of the building.
- 12:46SPEAKER_02: So that's what your emergency control functions are.
- 12:50SPEAKER_02: We have to tie into that.
- 12:52SPEAKER_00: Well, since I'm already hitting on you, I'll hit on you again.
- 12:55SPEAKER_00: Uh an integral part of an emergency control function is an ECFI.
- 12:59SPEAKER_00: What the heck is an ECFI?
- 13:01SPEAKER_02: That is a very long way to describe what would typically be called a relay or module, an emergency control function interface device.
- 13:11SPEAKER_02: It's like five, six words to say relay or module.
- 13:15SPEAKER_02: Now, not all relays and modules are emergency control function interface devices, but that's a lot of time what we're using.
- 13:22SPEAKER_02: And it is how we are interfacing the fire alarm system to that emergency control function.
- 13:27SPEAKER_02: It's how we're going to tie them in together.
- 13:30SPEAKER_02: And you got some rules.
- 13:32SPEAKER_02: You got some rules when it comes to them, especially when it comes to location.
- 13:36SPEAKER_02: Yep, absolutely.
- 13:36SPEAKER_02: Charles, what are those rules about locations?
- 13:40SPEAKER_01: Well, one rule is the three-foot rule for ECF.
- 13:46SPEAKER_01: Uh we have to have our relay located within three feet of the controlling emergency function.
- 13:53SPEAKER_01: So code puts that in place for supervision reasons.
- 13:57SPEAKER_01: We want to make sure that our wiring from the control panel to the relay is properly supervised all along the path.
- 14:05SPEAKER_01: And having it within three feet ensures that we have adequate supervision for that wiring.
- 14:13SPEAKER_01: Absolutely.
- 14:14SPEAKER_00: There was an interesting change that occurred in 72 and the 2025 edition that that three-foot rule kind of got expanded upon.
- 14:24SPEAKER_00: And now there's different rules depending upon how the wiring between that ECFI and the function is uh is set up.
- 14:32SPEAKER_00: If it's unprotected, yes, it is three feet.
- 14:35SPEAKER_00: But now in 72, 2025, and that's assuming your AHJ adopts 72, 2025, it can be within 20 feet if the wiring is in metal conduit or armored cable.
- 14:47SPEAKER_00: So that's an interesting thing that they did, but that's again 2025.
- 14:50SPEAKER_00: So that's a jurisdictional specific thing, yes, sir.
- 14:54SPEAKER_01: Brian, what wiring specifically are they talking about?
- 14:58SPEAKER_01: Wiring from the control panel to the device or from the device to the fan or what great question.
- 15:05SPEAKER_00: So, yeah, that's the wiring from the ECFI to the controlled circuit or device.
- 15:11SPEAKER_00: And there's a different set of requirements from the wiring from the panel to the ECFI.
- 15:16SPEAKER_00: Chris, I can tell you're wanting to talk about that.
- 15:19SPEAKER_02: So I I want to talk about this because there's not a lot of I wouldn't say there's not a lot of clarity.
- 15:26SPEAKER_02: With the code, how it's set up, if it is in some kind of conduit or metal clad from your relay to the actual control function, it can be much, much more distance, up to 20 feet.
- 15:41SPEAKER_02: If it is not, it has to be within three feet.
- 15:43SPEAKER_02: Okay, I can grasp that.
- 15:44SPEAKER_02: Cool, cool, cool, cool.
- 15:46SPEAKER_02: What 2025, and they kind of push this into 22 as well, is that none of that is a necessity if you're using class D.
- 15:56SPEAKER_02: Okay, wire class D wiring is method.
- 15:59SPEAKER_02: Okay, aren't we already doing that?
- 16:01SPEAKER_02: So are we not having to do three feet?
- 16:04SPEAKER_02: Are we having to do 20 feet if it's in?
- 16:06SPEAKER_02: And that is one of the things that's like, can we get a little bit more of a clever picture to this?
- 16:14SPEAKER_02: Because, hey, if it's class D, none of those rules apply.
- 16:19SPEAKER_02: Wait.
- 16:20SPEAKER_02: And y'all aren't doing class D for this?
- 16:22SPEAKER_02: What is Class D?
- 16:25SPEAKER_02: Class D is our fail-safe, uh, fail-safe circuit, where um when you have a fault, nothing is enunciated back at the panel.
- 16:34SPEAKER_02: However, the intended function happens.
- 16:37SPEAKER_02: It fails in what I I refer to fail-safe as it fails in the safest way for the occupants of the building.
- 16:43SPEAKER_02: So if we're looking at a perfect example, HVAC shutdown.
- 16:46SPEAKER_02: When you have HVAC shutdown, what happens?
- 16:48SPEAKER_02: Well, Duck Detector sends information to the relay, relay says, all right, shut it down.
- 16:53SPEAKER_02: HVAC shuts off.
- 16:54SPEAKER_02: No indication back at the panel that the air handling unit's been shut off, but the intended function has happened.
- 17:01SPEAKER_02: And, you know, it how the code sets it up on that last part with the emergency control function interface device.
- 17:08SPEAKER_02: It's who's not already doing that as Class D?
- 17:13SPEAKER_02: So does the rule apply or does it not apply?
- 17:16SPEAKER_00: What are we doing here?
- 17:18SPEAKER_00: I guess it could theoretically be a non-class D circuit, but yeah, you're absolutely right.
- 17:22SPEAKER_00: That is the big exception in the code and all the additions, uh, or at least more of the more recent additions, anyway, that that three feet or 20 feet doesn't apply if it's a fail-safe.
- 17:31SPEAKER_00: And it certainly makes sense because, as you said, with a fail-safe, uh, either by operation of the function or a break in the wiring, a failure of the circuit, it performs its intended function.
- 17:44unknown: All right.
- 17:44SPEAKER_00: Well, great, guys.
- 17:46SPEAKER_01: I have another issue with this whole subject.
- 17:49SPEAKER_00: Okay.
- 17:50SPEAKER_00: You've got many issues, my friend.
- 17:51SPEAKER_00: Let's talk about this one in particular.
- 17:54SPEAKER_01: The code uses these acronyms that get so confusing.
- 17:58SPEAKER_01: There's ECF and ECS.
- 18:01SPEAKER_01: So, Brian, what is ECS?
- 18:04SPEAKER_00: ECS is Emergency Communications Systems, which is a voice system, which is chapter 24 of the 72 as of 2010.
- 18:17SPEAKER_00: So it's going back a couple of editions.
- 18:19SPEAKER_00: And what ECS covers is voice systems, voice communication systems that include emergency voice alarm communication, i.e.
- 18:28SPEAKER_00: voice EVAC, also mass notification, and other voice systems within the building, like area of refuge, area of rescue systems, older editions of the code, even covered elevator telephone and stairwell systems and stuff like that.
- 18:43SPEAKER_00: Newer edition only covers uh area of refuge, area of rescue systems, but basically a system that involves voice communication.
- 18:52SPEAKER_01: So, all you people who sit on an NFPA committee, I want you to think about this.
- 18:57SPEAKER_01: For those of us in the field that don't deal with these acronyms every single day, ECF and ECS is confusing.
- 19:06SPEAKER_01: Come up with a different acronym here somewhere.
- 19:09SPEAKER_01: Communication systems for emergencies, CSD or something.
- 19:15SPEAKER_02: Yeah.
- 19:15SPEAKER_02: Voice good luck with that.
- 19:17SPEAKER_02: Chapter 24, voice, voice systems.
- 19:20SPEAKER_00: Yep.
- 19:21SPEAKER_00: Good luck with that.
- 19:22SPEAKER_00: I'm sure the uh the people on the committees will definitely take that up at the next meeting.
- 19:26SPEAKER_00: I'm sure they will.
- 19:29SPEAKER_00: Well, gentlemen, our our last topic for today is questions from the field.
- 19:34SPEAKER_00: So, a question from our students is what are the separation requirements between fire alarm circuits and other circuits?
- 19:40SPEAKER_00: Chris, you want to lead us off on that?
- 19:42SPEAKER_02: I'll take the lead on it.
- 19:44SPEAKER_02: What we look at with your fire alarm circuits and other circuits.
- 19:50SPEAKER_02: A lot of what 70 stipulates with this comes back to kind of one big thing.
- 19:56SPEAKER_02: Do the jackets match?
- 19:58SPEAKER_02: Jackets match, you're good to go.
- 20:00SPEAKER_02: Jackets don't match.
- 20:02SPEAKER_02: Okay, well, probably not, unless it's one of these other aspects.
- 20:08SPEAKER_02: And then, yes, but only kind of.
- 20:12SPEAKER_02: And so, yeah, you can definitely have your circuits mixed in together, but jackets gotta match.
- 20:20SPEAKER_02: And with what we work at with Fire Alarm, most of the time it's power limited.
- 20:24SPEAKER_02: So as long as we are working with other power limited circuits, typically there's not an issue.
- 20:30SPEAKER_02: But does the jacket match?
- 20:32SPEAKER_02: And that is wherein lies a lot of the problem for things that are not gonna be power limited.
- 20:39SPEAKER_02: Your your power supply, your light and power of the building, things like that.
- 20:45SPEAKER_02: Not gonna be power limited.
- 20:46SPEAKER_02: And you have issues there where you're gonna need to have separation.
- 20:51SPEAKER_00: Where would they where would uh somebody find this information?
- 20:54SPEAKER_00: How would they know what the limitations are and uh what the requirements are?
- 20:59SPEAKER_00: What code would govern that?
- 21:01SPEAKER_02: We're going into 70.
- 21:03SPEAKER_02: We're talking about cable, going into 70.
- 21:05SPEAKER_02: Talking about wire, going into 70.
- 21:07SPEAKER_02: Absolutely.
- 21:08SPEAKER_02: And talking about fire alarm?
- 21:11SPEAKER_02: 760.
- 21:13SPEAKER_02: Yes, sir.
- 21:13SPEAKER_00: So it's interesting that uh the separation, you mentioned uh non-power limited circuits like electric light and power and NPLFA fire alarm.
- 21:21SPEAKER_00: And uh you know, we we're always dealing with those within panels, but there are some specific rules in 760 and 760.30.136 specifically that says you can't have those circuits together unless you meet certain requirements.
- 21:36SPEAKER_00: And one of those is separated by a barrier.
- 21:38SPEAKER_00: Okay, that's kind of a difficult thing.
- 21:40SPEAKER_00: If they're associated circuits within an enclosure, there has to be a one-quarter inch separation.
- 21:46SPEAKER_00: So if I'm bringing power 120 volts into my fire alarm panel, which is electric light and power, has to be at least a quarter-inch separation from that and the fire alarm circuits.
- 21:57SPEAKER_00: You know, my SLC and my NAC and my IDCs.
- 22:00SPEAKER_00: In hoist waves, there are some specific requirements.
- 22:02SPEAKER_00: Has to be in conduit.
- 22:04SPEAKER_00: Any other application where they're not associated, there has to be a two-inch separation.
- 22:10SPEAKER_00: But as Chris, as you mentioned, there are different rules depending upon if they are similar similar types of circuits, similar voltage limitations, where you have uh PLFA like with class two, class three, and communication circuits.
- 22:27SPEAKER_00: Charles, do you want to talk about those a little bit?
- 22:29SPEAKER_00: What the rules are there?
- 22:31SPEAKER_01: Well, one thing that comes to my mind, especially for a hoistway application with CI cable.
- 22:38SPEAKER_01: Um can I use CI cable that's not in conduit in a hoistway?
- 22:44SPEAKER_01: I would say not.
- 22:45SPEAKER_02: Not in an elevator hoist way.
- 22:48SPEAKER_01: So it still has to be in conduit.
- 22:51SPEAKER_01: According to 760, yeah.
- 22:53SPEAKER_01: And uh class two, class three wiring, that's all power limited as well.
- 23:00SPEAKER_01: Uh when we get into class one, that's higher voltage, higher current, that's a bigger issue.
- 23:05SPEAKER_01: But if I have power-limited cable in a class two or three, running with class two or three circuits, that's fine.
- 23:14SPEAKER_01: Uh there's no problem with 70 in that respect.
- 23:19SPEAKER_00: They do say and they differentiate between uh class two and class three because class two has a hundred and fifty volt insulation and class three and communications have three hundred volt.
- 23:29SPEAKER_00: So as Chris mentioned, it's all about the jacket rating.
- 23:32SPEAKER_00: So you can have a class two circuit if you have a class two circuit that has a cable with a 300-volt jacket installation.
- 23:41SPEAKER_00: That way they're the same.
- 23:43SPEAKER_00: But if it's a class three or communications, those are by default.
- 23:46SPEAKER_00: You know, CL3 cable and CM cable are by default 300 volt jacket installation.
- 23:51SPEAKER_00: So those can be with power limited fire alarm.
- 23:55SPEAKER_01: And uh there are, go ahead.
- 23:57SPEAKER_01: Are you familiar with any cables that actually have a hundred and fifty volt installation?
- 24:04SPEAKER_00: Uh in distribution, I know we had some CL2 cables that were specifically CL2, but most of them, honestly, were CL3 or C unlisted, which is the 300 volt.
- 24:14SPEAKER_01: Yeah, and in practicality, really any cable we would be using would be 300 volts minimum.
- 24:23SPEAKER_01: Right.
- 24:24SPEAKER_00: Yeah, absolutely.
- 24:24SPEAKER_00: You just want to check the ins check the rating on it because you know there's gonna be that AHJ that's gonna look at it and call you out on it.
- 24:31SPEAKER_01: I mean, even if you look at Cat 5, that's 300 volts.
- 24:35SPEAKER_00: Right.
- 24:35SPEAKER_00: So and that's a CM, yep.
- 24:37SPEAKER_00: You're absolutely right.
- 24:38SPEAKER_00: But yeah, it's I think it's gonna be uncommon to find a uh a strictly CL2 cable.
- 24:44SPEAKER_00: It's probably gonna be a CL3, which is considered superior to CL2, or a or dual-listed CL3 CM cable.
- 24:51SPEAKER_00: Awesome.
- 24:52SPEAKER_00: Well, guys, thank you once again for joining me to talk all about fire alarm.
- 24:56SPEAKER_00: I want to ask all of our listeners out there to please like and subscribe.
- 25:01SPEAKER_00: And uh we'll see everybody again next time.
- 25:04SPEAKER_00: Thanks again, gentlemen.
- 25:06SPEAKER_00: Thank you.
- 25:07SPEAKER_00: Thank you.