- 0:00Speaker 1: Chapter four of Silent Sentinels by Westinghouse Electric and Manufacturing Company.
- 0:07Speaker 1: This LibriVox recording is in the public domain. Direct current systems.
- 0:14Speaker 1: The direct current systems of today, though small in comparison
- 0:17Speaker 1: with the alternating current systems, offer relay problems. Equally important,
- 0:22Speaker 1: comparable to the service demanded of other public utilities, is
- 0:25Speaker 1: at which congested cities demand from street railway companies. The
- 0:30Speaker 1: growth and interconnection of some of these systems have created
- 0:32Speaker 1: a demand for adequate direct current relay protection. This demand
- 0:37Speaker 1: for service brought about both the development of service restoring
- 0:40Speaker 1: equipment and the supervision of feeder apparatus by supervisory control.
- 0:45Speaker 1: Protection against overcurrents caused either by accidental faults on feeders
- 0:49Speaker 1: or lines, or by excessive overloads onlines can be affected
- 0:53Speaker 1: by the use of overcurrent relays. The short circuit detector
- 0:56Speaker 1: type of equipment meeting the demands of railway systems, permits
- 1:00Speaker 1: heavy overloads due to acceleration, but gives protection upon the
- 1:04Speaker 1: occurrence of a short circuit on the line. Service restoring
- 1:09Speaker 1: system as in the case of alternating current service, the
- 1:14Speaker 1: question of continuity of service often makes necessary some sort
- 1:17Speaker 1: of device to restore service after it has been interrupted.
- 1:21Speaker 1: Where a feeder has been tripped out because of a fault,
- 1:23Speaker 1: it may sometimes be necessary to provide means for automatically
- 1:27Speaker 1: reclosing the breaker several times, allowing a definite interval of
- 1:30Speaker 1: time between each reclosing. Thus, if the fault is of
- 1:34Speaker 1: a transient nature and clears itself quickly, the breaker will
- 1:38Speaker 1: remain closed and service will be continued on the line. However,
- 1:42Speaker 1: if the fault is of a permanent nature, the breaker
- 1:45Speaker 1: will open each time it is reclosed until the specified
- 1:47Speaker 1: number of reclosures have occurred, and then it will remain
- 1:50Speaker 1: open permanently, indicating that the line requires attention. Another method
- 1:56Speaker 1: used for service restoring is to have a relay which
- 1:59Speaker 1: has included an it designed characteristics, whereby it discriminates between
- 2:02Speaker 1: a good and a bad feeder. In this case, the
- 2:06Speaker 1: feeder is opened under overcurrent or short circuit conditions and
- 2:10Speaker 1: the breakers reclose automatically as soon as the excessive load
- 2:13Speaker 1: is removed. After the breaker has been opened, it may
- 2:16Speaker 1: be reclosed by a resistance measuring relay. This relay determines
- 2:20Speaker 1: when the fault has been cleared sufficiently to allow the
- 2:23Speaker 1: circuit breaker to be closed with safety. When continuity of
- 2:27Speaker 1: services of great importance, and when the capacity behind the
- 2:30Speaker 1: feeder is large, it is desirable to have the breaker
- 2:33Speaker 1: remain closed, except in cases of actual short circuits or
- 2:36Speaker 1: violent overloads. Operators of large urban railway systems demand this
- 2:41Speaker 1: class of service as it permits heavy peaks for acceleration
- 2:44Speaker 1: of the cars and prevents untimely interruption of the service. Nevertheless,
- 2:50Speaker 1: in meeting this demand, the feeder circuits must be protected
- 2:53Speaker 1: against short circuits and heavy overcurrents. The short circuit detector
- 2:57Speaker 1: type of equipment provides this protection without interrupting the circuit
- 3:01Speaker 1: on ordinary overloads. Except for heavy railway service, it is
- 3:05Speaker 1: usually desirable to open a circuit on a definite overcurrent.
- 3:09Speaker 1: For this application, the overcurrent type of equipment with an
- 3:11Speaker 1: overcurrent relay is used instead of the short circuit detector.
- 3:15Speaker 1: The overcurrent setting is usually for instantaneous tripping, but occasionally
- 3:19Speaker 1: a time element is provided protection of direct current apparatus.
- 3:26Speaker 1: The protection of the direct current apparatus might be classified
- 3:29Speaker 1: as protection against overcurrent, reversed current, and over temperature. In
- 3:33Speaker 1: most cases, such protection on motors and generators is secured
- 3:37Speaker 1: by means of circuit breakers equipped with necessary overcurrent or
- 3:40Speaker 1: reverse current coils or by fuses of suitable capacity. In
- 3:45Speaker 1: many installations, however, it is found necessary to use a
- 3:48Speaker 1: protective relay in order to secure the needed accuracy and
- 3:52Speaker 1: reliability of protection. In such cases, the D or to
- 3:56Speaker 1: overcurrent relay is used, and in cases where protection is
- 3:59Speaker 1: really required against reverse current, the d reverse current relay
- 4:02Speaker 1: is applicable. Over temperature protection of direct current apparatus is
- 4:08Speaker 1: obtained in a manner similar to that described under alternating
- 4:11Speaker 1: current apparatus. The BD oil filled thermal relay is used
- 4:16Speaker 1: largely for motor protection, while in some cases where it
- 4:19Speaker 1: is possible to have exploring coils in the windings, the
- 4:22Speaker 1: DT temperature relay is used electrochemical work when a line
- 4:29Speaker 1: supplies a load. For such work as electrochemical processes where
- 4:33Speaker 1: a reversal of polarity is extremely dangerous, it is sometimes
- 4:36Speaker 1: necessary to supply a highly sensitive relay which serves to
- 4:40Speaker 1: disconnect the circuit when any condition shows that the polarity
- 4:43Speaker 1: is liable to reverse the A polarity directional relay has
- 4:46Speaker 1: been used very successfully for this purpose, fulfilling the protective
- 4:50Speaker 1: requirements and passing the underwriter's inspection. The sensitivity and design
- 4:55Speaker 1: of this relay are such that the contacts will be
- 4:57Speaker 1: closed upon any reversal of the polarity of the curve
- 5:00Speaker 1: to which it is connected, or upon a fall in
- 5:02Speaker 1: the voltage to below twenty percent of normal value. End
- 5:08Speaker 1: of Chapter four