Latest / Silent Sentinels- Protective Relays for A-C and D-C Systems / 007 - Automatic Control
Transcript
- 0:01Speaker 1: Chapter five of Silent Sentinels by Westinghouse Electric and Manufacturing Company.
- 0:10Speaker 1: This LibriVox recording is in the public domain. Automatic control substations,
- 0:20Speaker 1: depending on the method used in their operation, may be
- 0:25Speaker 1: divided into three classes, manual, semi automatic, and automatic. Regardless
- 0:32Speaker 1: of its type, a station must be a highly reliable
- 0:36Speaker 1: source of power supply. The necessary operations in a substation
- 0:43Speaker 1: which serves the purpose of transforming alternating current into direct
- 0:48Speaker 1: current by means of synchronous converters or motor generators are
- 0:53Speaker 1: therefore the starting and stopping of such machines when the
- 0:57Speaker 1: system demands it, and the provision of adequate protection against
- 1:02Speaker 1: faulty action, either in case of some trouble out on
- 1:06Speaker 1: the system or in case of trouble within the substation equipment.
- 1:11Speaker 1: The automatic substation today is more dependable than is the
- 1:16Speaker 1: manually operated station. The design and development of relays with
- 1:22Speaker 1: a high degree of accuracy, sensitivity, and reliability have made
- 1:28Speaker 1: such an automatic substation a possibility. The characteristics of the
- 1:34Speaker 1: automatic substation, which must be supplied by adequate relays, might
- 1:40Speaker 1: be roughly divided into two classes, namely control and protection.
- 1:47Speaker 1: The control methods consist in the automatic starting of one
- 1:51Speaker 1: or more of the machines in the station. This may
- 1:55Speaker 1: be introduced in any one of several ways, depending on
- 1:59Speaker 1: the conditions to be met, and is generally accomplished through
- 2:04Speaker 1: some form of remote control or by means of a
- 2:08Speaker 1: voltage relay which closes its contacts at some predetermined value
- 2:14Speaker 1: of reduced line voltage. Starting due to momentary drop in
- 2:20Speaker 1: voltage or when the alternating current voltage conditions are incorrect
- 2:25Speaker 1: is prevented by an induction type alternating current voltage relay.
- 2:31Speaker 1: While many of the operations are common to both synchronous
- 2:36Speaker 1: converters and motor generators, the following outline of system is
- 2:41Speaker 1: especially applicable to synchronous converters. When conditions are favorable for starting,
- 2:50Speaker 1: a sequence of relay actions serves to perform the necessary
- 2:54Speaker 1: functions such as lifting the converter brushes, connecting the converter
- 3:00Speaker 1: to the starting tap of the power transformers, and other
- 3:04Speaker 1: operations depending on the type of substation. After the converter
- 3:09Speaker 1: has started to rotate. Synchronism and polarity are indicated by
- 3:14Speaker 1: a polarized motor relay, which, in case of reversed polarity,
- 3:19Speaker 1: causes the polarity of the machine to be corrected by
- 3:23Speaker 1: reversing the field. The armature of the relay motor is
- 3:28Speaker 1: connected to the converter pilot brushes, and during the period
- 3:33Speaker 1: of starting, the polarity of the relay becomes that of
- 3:36Speaker 1: the machine. As the converter comes up to synchronous speed,
- 3:41Speaker 1: alternating current of diminishing frequency flows through the motor armature
- 3:47Speaker 1: until synchronism is reached without causing rotation. At that time,
- 3:53Speaker 1: the armature will revolve in drive a drum switch in
- 3:56Speaker 1: the direction corresponding to the converter pole. If the polarity
- 4:02Speaker 1: is incorrect, the drum switch causes the field connection to
- 4:06Speaker 1: reverse by means of a double throw contactor switch. The
- 4:10Speaker 1: reversed connection is maintained only long enough for the voltage
- 4:15Speaker 1: default to zero and then to release the controlling relay,
- 4:19Speaker 1: which causes the normal field connection to be re established.
- 4:24Speaker 1: By this operation, the converter has been caused to slip
- 4:29Speaker 1: a pull and thus correct the polarity. The polarized motor
- 4:34Speaker 1: relay continues to operate and causes a transfer relay to function.
- 4:40Speaker 1: This relay in turn opens the starting contactor, causing operation
- 4:46Speaker 1: of the direct current brush operating mechanism. Which lowers the
- 4:50Speaker 1: brushes to the commutator. At this time, the main direct
- 4:55Speaker 1: current switches are closed and the machine is connected to
- 4:58Speaker 1: the load. The final function of the control part of
- 5:02Speaker 1: the substation equipment is to disconnect the machine from service.
- 5:08Speaker 1: This operation is introduced by the action of a sequence
- 5:11Speaker 1: of light load control relays. Protective equipment is provided not
- 5:17Speaker 1: only in the automatic substations, but also in the manually
- 5:22Speaker 1: operated or the semi automatic stations. It is provided by
- 5:26Speaker 1: induction type single and polyphase relays, which prevent the station
- 5:31Speaker 1: from starting under abnormal conditions of alternating current line voltage,
- 5:36Speaker 1: such as low voltage, open phase or reverse phase. The
- 5:41Speaker 1: same type of relay causes the station to shut down
- 5:45Speaker 1: on unbalanced phase conditions. If the trouble is within the station,
- 5:50Speaker 1: a lock out relay prevents restarting, and if the unbalanced
- 5:54Speaker 1: phase condition is outside the station, the automatic equipment functions
- 5:59Speaker 1: to the apparatus into service as soon as the line
- 6:03Speaker 1: is restored to normal. Each bearing is equipped with a thermostat, which,
- 6:09Speaker 1: in case of a hot bearing, locks the machine out
- 6:12Speaker 1: of service until the contexts of the thermostat device has
- 6:16Speaker 1: been reset by hand. A thermal relay also protects the
- 6:21Speaker 1: winding of the machine from overheating due to continued overload.
- 6:26Speaker 1: Other protective devices are the direct current directional relay, an
- 6:31Speaker 1: overspeed device, an inductive type alternating current overload relay, a
- 6:37Speaker 1: thermostat preventing overheating of the current limiting resistors, and a
- 6:42Speaker 1: lockout relay which locks the equipment out of service in
- 6:46Speaker 1: case of failure of any part of the apparatus. The
- 6:50Speaker 1: protection of the equipment is complete and responds immediately in
- 6:55Speaker 1: case of trouble, thus eliminating the losses which often occur
- 6:59Speaker 1: in man only operated substations because of the vary impossibility
- 7:04Speaker 1: of handling an emergency in the required time or the
- 7:08Speaker 1: inability of the operator to do so. In addition to
- 7:13Speaker 1: this automatic operation of the substation, a number of automatic
- 7:18Speaker 1: selective relay equipments are in use for automatically cutting out
- 7:23Speaker 1: a short circuited line, or for automatically reclosing and other
- 7:28Speaker 1: types of necessary feeder operation. It can be seen from
- 7:33Speaker 1: this description what a large part the relays play and
- 7:36Speaker 1: automatic substation equipment, and also how absolutely necessary it is
- 7:42Speaker 1: to have relays which are not only highly reliable and
- 7:46Speaker 1: accurate at the time of their installation, but also which
- 7:51Speaker 1: will maintain this high degree of accuracy and reliability throughout
- 7:56Speaker 1: continued service. Thus, success of the Westinghill Automatic substations and
- 8:02Speaker 1: past experience have proved the induction types of relays, first
- 8:08Speaker 1: developed and manufactured by the Westinghouse Company, to be especially
- 8:12Speaker 1: suitable for this type of service. By the use of
- 8:16Speaker 1: the induction type relays, precision of operation is not only assured,
- 8:22Speaker 1: but the exact calibration can be maintained throughout a long
- 8:26Speaker 1: period of operation. Thus, the induction relay has solved many
- 8:31Speaker 1: of the difficulties which were formally experienced when plunger type
- 8:36Speaker 1: relays had to be depended on for various functions. Most
- 8:41Speaker 1: of the relays supplied with the present day automatic substation
- 8:46Speaker 1: equipment are standard protective relays, as described elsewhere in this publication.
- 8:52Speaker 1: In some cases it is necessary to somewhat modify the
- 8:57Speaker 1: characteristics of the relay, but the fundamental principles of design
- 9:02Speaker 1: and operation are maintained. The CV voltage relay is used
- 9:07Speaker 1: throughout as a timing voltage relay to provide a definite
- 9:12Speaker 1: time delay where necessary. A slight modification of this relay
- 9:17Speaker 1: consists in having the contacts geared to the disc shaft
- 9:21Speaker 1: rather than mounted directly on it, which provides a relay
- 9:26Speaker 1: with a much longer time delay characteristic than the standard.
- 9:30Speaker 1: The GK time delay relay, also used largely in automatic
- 9:35Speaker 1: substation equipment, is motor operated and is highly reliable. A
- 9:41Speaker 1: recent addition to the relay family is the MF flash relay,
- 9:46Speaker 1: which is used in automatic substation protection to disconnect the
- 9:51Speaker 1: rotary in case of a flashover occurring between the commutator
- 9:55Speaker 1: and the frame and of Chapter five five